Foreword Several books have been written on microclimatology and boundary-layer physics, beginning with Rudolph Geiger's Climate near the Ground (first German Edition in 1927). Until now, however, nobody has produced a book on the effects of small-scale climate variability around and inside buildings, monuments and other cultural objects. So Professor Camuffo's well illustrated account, Microclimate for Cultural Heritage will be greatly welcomed by architects, engineers, preservers and restorers of cultural property, and the wider community of microclimatologists. What has "cultural heritage" to do with microclimatology? Forty years ago, the response from meteorologists would have been: "Very little". Let me cite a personal example. Back in the 1950s while studying engineering meteorology at the University of Michigan, I wrote a term paper on the weathering of exposed surfaces by atmospheric pollution, which was given an A grade, and which was subsequently published (Munn, R.E., 1959: Engineering Meteorology: the Weathering of Exposed Surfaces by Atmospheric Pollution. Bull. Am. Meteorol. Soc. 40, 172-178). But several scientists (including a famous professor of physics at McGill University in Montreal) were alarmed that such a topic should find its way into the meteorological literature, and made their views known. Thirty-five years later, the importance of microclimatological gradients is widely recognized in the preservation and restoration of cultural objects. Credit for this attitude change is largely due to the efforts of a few people like Dario Camuffo, who recognized early on, the importance of micrometeorology in studies of the preservation and restoration of cultural heritages. This monograph contains many practical examples of ways in which micrometeorological knowledge can help in assessments of the deterioration of surfaces that have been exposed to the environment over long periods of time. Not only does the book include interesting outdoor examples from the author's own experience but also indoor cases, like horizontal cross-sections of temperature in the Sistine Chapel and of mixing ratio in the Giotto Room in the Uffizi Gallery in Florence. I know that this book will be widely consulted by specialists in the cultural heritage field, and I am pleased to have been involved in a very small way by contributing this foreword. R.E. Munn
Institute for Environmental Studies
University of Toronto, Toronto, Canada
vii
Preface This book has been designed as a useful microphysics handbook for conservators and specialists in chemistry, architecture, engineering, geology and biology who work in the multidisciplinary field of the environment, and, in particular, in the conservation of works of art. It has been especially written following the continuous d e m a n d to fill a gap in the literature related to this i m p o r t a n t application of atmospheric sciences, i.e. to apply the thermodynamic processes of clouds, or the dynamics of the planetary boundary layer, to a m o n u m e n t surface or to a room of a m u s e u m . The aim is to furnish them with a b a c k g r o u n d familiarity with the u n d e r l y i n g physics behind mathematics, and to give a detailed description and interpretation of the main microphysical p h e n o m e n a which play a fundamental role in practical applications. Correct application of formulae is only possible when all the approximations made in their derivation and the limitations intrinsic to the basic hypotheses are known. In this complex field an effort is m a d e to substitute scientific d e m o n s t r a t i o n s for c o m m o n opinions or popular beliefs. The basis are given for non-destructive diagnostics to evaluate causes of damage and predict outdoor deterioration, determined by meteorological factors, as well as the negative effects in exhibition rooms, due t o u n s o u n d use of technology and mass tourism. To this aim, suggestions are given on the fundamental principles in designing heating, air conditioning, lighting and in reducing the deposition of pollutants on works of art. Theory and experience are coupled to describe the complex condensation mechanisms and the fundamental role played by water in the stone deterioration and the formation of crusts on monuments. Urban meteorology, air-surface interactions, atmospheric stability, dispersion and deposition of airborne pollutants are also key topics of this book, whose main aim has been to make comprehensible to a wider audience a matter that is only familiar to a few specialists. This book combines a theoretical background with m a n y years of accurate laboratory research, field surveys and practice. The first part, devoted to applied theory, is a concise treatise on micro physics, which makes a survey on the basic ideas especially on classical, kinetic and statistical t h e r m o d y n a m i c s which are necessary for e n v i r o n m e n t a l diagnostic and conservation. The second part,
Performing Microclimate Field Surveys, is devoted to the practical utilisation and shows in detail how measurements should be performed, with many suggestions and examples and the indication of some common errors that should be avoided.
viii
Acknowledgments
The book is based on direct experience on a large number of case studies, most of them funded by the European Commission (DG XII: Science Research and Development, Programmes STEP and Environment, Contracts ENV-757-I-SB, EV4V-0051-I-A, STEPCT90-0107-SSMA, ENV4-CT95-0088, ENV4-CT95-0092) and some of them supported by the National Research Council of Italy (CNR), e.g. Finalized Project 'Beni Culturali', ENEL, e.g. project Effects of Air Pollution on Human Health and Cultural Heritage, the Consorzio per la Torre di Pisa and the Consorzio Padova Ricerche. Studies also were made in the occasion of special commissions (e.g. European Union, UNESCO, NAPAP, Vatican, Italian Ministry of Scientific Research). This text utilises also lectures of Atmospheric Physics taken during the last ten years at the Physics Department, University of Padova, as well as those on microclimate and physical weathering of monuments at international schools (e.g. European University Centre for Cultural Heritage of the Council of Europe in Ravello; Community of Mediterranean Universities; UNESCO-ICCROM). A number of original contributions that were published in scientific journals, or presented at international symposia, are here summarised. Special thanks are due to whoever has contributed: all my co-workers, i.e. Dr. A. Bernardi, Mr. A. Ongaro, Dr. G. Sturaro, Dr. A. Valentino and Arch. P. Schenal for their cooperation especially in the field surveys and data analysis; the scientific officers of the European Commission, and particularly Dr. J. Acevedo for her interest, kind encouragement and friend assistance; the good friends and colleagues Prof. A. Arnold (Swiss Federal Institute of Technology, Ziirich), Prof. N.S. Baer (New York University), Dr. E. Bell (Trinity College, Dublin), Prof. P. Brimblecombe (University of East Anglia, Norwich), Dr. L. De Boek (Antwerp University), Prof. M. Del Monte (Bologna University), Prof. B. Fitzner (Technischen Hochschule, Aachen), Dr. P. Bacci (ENEL, Milan), Dr. C. Price (University College, London), Dr. C. Sabbioni (CNR FISBAT, Bologna), Prof. C. Saiz-Jimenes (CSIC, Seville), Prof. R. van Grieken (Antwerp University), Dr. S. Vincenzi (CNR-ISDGM, Venice), Dr. Th. Warscheid (Freie Hansestadt, Bremen) and Prof. F. Zezza (Bari Polytechnic) for having contributed in different ways. For figures, we must acknowledge the following: Fig.l.4, 2.6 and 4.4 are reprinted from European Cultural Heritage Newsletter on Research, and Bollettino Geofisico, joint edition 14, 3, 1-123, Camuffo D. and Bernardi, A.,: The microclimate of Leonardo's "Last Supper" (1991) with kind permission from the European Commission, DG XII, and the Bollettino Geofisico. Fig.l.6 is reprinted from Science of the Total Environment, 46, 243-260, Bernardi, A., Camuffo, D., Del Monte, M., and Sabbioni, C.:. Microclimate and Weathering of an Historical Building: the Ducal Palace in Urbino (1985) with kind permission from Elsevier Science - NL, Sara Burgherharstraat 25, 1055 KV Amsterdam, the Netherlands. Fig.l.13 and Fig.4.5b are reprinted from Bollettino Monumenti Musei Gallerie Pontificie, 6, 211257, Camuffo, D. and Bernardi, A.: Dinamica del microclima e scambi termoigrometrici tra pareti e atmosfera interna nella Cappella Sistina (1986) with kind permission of the Vatican Museums and Galleries. Fig.1.14 is reprinted from Bollettino d'Arte special issue "Giotto a Padova", Camuffo, D. and Schenal, P.: Microclima all'interno della Cappella degli Scrovegni: scambi termodinamici tra gli affreschi e l'ambiente, pp. 107-209 (1982) with kind permission of Ministero dei Beni Culturali ed Ambientali, via di S. Michele 22, Rome and Poligrafico dello Stato, Rome. \ Fig.5.7 has been kindly supplied by Prof. Marco Del Monte, Department of Geology, Bologna University. Fig.5.8a,b is reprinted from Water Soil and Air Pollution 21: 151-159, Camuffo, D.: Condensation-Evaporation Cycles in Pore and Capillary Systems According to the Kelvin Model Fig.2 and 3 pages 154 (1984) with kind permission from Kluwer
ix Academic Publishers, P.O. Box 17, 3300 AA Dordrecht, The Netherlands. Fig.6.1 is similar to Fig.3 page 44 in Camuffo, D.: Environment and Microclimate; pp. 37-50 in: N. Baer, C. Sabbioni and A. Sors (ed.s): Science Technology and European Cultural Heritage (1991) with kind permission from Butterworth Heinemann, Linacre House, Jordan Hill, Oxford OX2 8DP, UK. Fig.6.2a is reprinted from Atmospheric Environment 18 (19): 2273-2275, Camuffo, D.: The Influence of Run-Off in Weathering of Monuments. Fig.la, page 2274 (1984) with kind permission from Elsevier Science Ltd., The Boulevard, Langford Lane, Kidlington 0X5 1GB, UK. Fig.6.4 has been kindly supplied by Dr. Giancarlo Rossi, ENEL, Venezia-Mestre. Fig.6.6 is reprinted from the book Le deposizioni acide - I precursori. L'interazione con l'ambiente e i materiali, (L. Morselli ed.): Camuffo, D., Aspetti Microfisici delle precipitazioni acide in relazione al degrado dei monumenti, Fig. 2 page 348 (1991) by kind permission of Maggioli Editore, Guerrazzi 10, Bologna. Fig.6.10 is reprinted from American Journal of Science, 251, 884-898, Gordon, J. and MacDonald, F.: Anhydrite-Gypsum Equilibrium Relations, Fig. 3 page 892 (1953) with kind permission of American Journal of Science, 217 Kline Geology Laboratory, Yale University, New Haven, CT 06520-8109, USA. Fig.8.8 and Fig.8.9 are reprinted from Museum Management and Curatorship 10, 373-383, Camuffo, D.: Wall Temperature and Soiling of Murals Fig.1 and Fig.2 page 176 (1991) with kind permission from Elsevier Science Ltd., The Boulevard, Langford Lane, Kidlington 0X5 1GB, UK. Fig.8.20 is reprinted from Vercelli, F., L'Aria, UTET, Torino (1933). Photo taken on 1920. Fig.11.4 is reprinted from Environmental Monitoring and Assessment 6, 165-170. Camuffo, D. and Valcher, S.: A Dew Point Signaller for Conservation of Works of Art, Fig.1 page 167 (1986) with kind permission from Kluwer Academic Publishers, P.O. Box 17, 3300 AA Dordrecht, The Netherlands. The climatological analyses of meteorological data for the Venice and Rome were based on observations taken by the Meteorological Service of the Italian Air Force. A grateful thought to the memory of two good friends and leading scientists: Prof. O. Vittori, who was specialist of Atmospheric Physics and my Director, and Dr. G. Urbani, who was preserver and Director of the Istituto Centrale del Restauro, Rome, for their unforgettable scientific discussions and for their stimulating contributions to apply atmospheric microphysics theory and environmental survey practice to monument conservation. Finally, special acknowledgements are due to my family for all my missing time.
CHAPTER 1
Microclimate, Air and Temperature
1.1. THE MICROCLIMATE First of all, it m a y be useful to define the w o r d 'microclimate' to which we refer, as in the e v e r y d a y practice some terms such as 'global climate', 'macroclimate',
'mesoclimate', 'climate', 'microclimate', 'nanoclimate' and 'picoclimate' are used by people with different meaning, and the same is done also by specialists. It is clear that all these terms have been utilised to define the climate of a specific area, and the prefix is chosen to indicate the size of the area involved. Of course, we cannot proceed in the apparently most straightforward way, i.e. by stating a scale with the appropriate size unit, e.g. one kilometre in diameter, and then apply the well k n o w n definitions, i.e. milli = 10 -3, micro = 10 -6, nano = 10 -9, pico = 10-12, as in this case the 'micr0climate' w o u l d apply to a site sized only 10 -6 km =1 mm, and this is obviously ridiculous. S o m e b o d y uses the term 'microclimate' for an u r b a n area, 'nanoclimate'
for a
m o n u m e n t and 'picoclimate' for a very small portion of a m o n u m e n t , but this definition has not gained popularity. In principle, the prefix varies with the actual area size, as determined by geographic, topographic or other local factors, e.g. the requirement of reaching a basic homogeneity in some key parameters, but it m a y also vary with reference to the actual interest, in view of a peculiar application, and the list of the subjective elements which intervene in the choice of the appropriate w o r d may continue. In climate research, meteorology and physical geography, the distinction is rather clear and is determined by the field of interest, i.e. the 'global climate' refers to our planet, the 'regional climate' to a geographical homogeneous area, the 'local climate' to a small limited area like a mountain, a valley, a city. Similarly, for conservation, it is useful to use clear terms, derived from the above mentioned sciences, e.g. 'regional
climate' for the main characteristics of the geographic area where the m o n u m e n t is found, 'urban', 'rural', 'mountain', 'valley', 'coastal' and so on for the next dimensional Step, and 'microclimate' relating to the small location, e.g. a corner of street, a square, a
room, where the m o n u m e n t or the object is sited. This definition does not imply a precise size, but focuses the attention on a specific artefact (e.g. a historic building, a statue, a small exhibit) and its surrounding, so that the same term can also apply w h e n studying the interactions between a portion of a m o n u m e n t and the air nearby. In practice, it refers to the whole ambient which is necessary to study in order to know the factors which have a direct influence on the physical state of the monument and the interactions with the air and the surrounding objects. N o w that the prefix 'micro' has been explained, it might be useful to clarify also the w o r d 'climate'. The following definitions can be found: 'climate is the synthesis of the day-to-day weather conditions in a given area', 'climate is the statistical description of weather and atmospheric conditions as exhibited by the patterns of such conditions, in a given region, over a specified period of time long enough to be representative (usually a n u m b e r of decades)', 'climate is the fluctuating aggregate of atmospheric conditions characterised by the states and developments of weather in a given area' (Maunder, 1994). It is evident that in our case the w o r d 'weather' is inappropriate; only in exceptional cases observations exist over a n u m b e r of decades and in general new indicative measurements must be taken in the short term before undertaking restorations; the same definition should be applied either to indoor or outdoor environments. By adapting the previous definitions to our aims, the following interpretation can be given: 'microclimate is the synthesis of the ambient physical conditions (e.g. time and
space distributions, fluctuating values and trends, average and extreme values, space gradients and frequency of oscillations) due to either atmospheric variables (e.g. temperature, humidity, sunshine, airspeed) or exchanges with other bodies (e.g. infrared emission, heating, lighting, ventilating) over a period of time representative of all the conditions determined by the natural and manmade forcing factors'. When a survey cannot continue for a time interval which is statistically representative of all the conditions, it should at least d o c u m e n t one or a few examples of the main different conditions, just to understand the nature of the problem. Another key question is whether meteorological data, taken from a standard w e a t h e r station sited at a few km (or less) from a m o n u m e n t , can be used for the estimation or interpretation of microclimatic situations, or it is always necessary to carry out specific and expensive field tests. It is clear that the acquisition of existing data m a y be helpful for a more complete interpretation of the p h e n o m e n a , but we will see in the following (Chapter 9) that s t a n d a r d w e a t h e r stations operate m e a s u r i n g p a r a m e t e r s with different criteria and methodologies, so that some m e a s u r e m e n t s are useful to our aims, other of scarce relevance and other useless. In addition, several p a r a m e t e r s n e e d e d for the science of conservation are not
considered in w e a t h e r stations. For this reason special field s u r v e y s are indispensable, and only a few parameters, measured by weather stations in a compatible way, appear as a duplicate and could be omitted. However, it is more convenient to record in the same data acquisition system and with the same criteria the whole set of data which is useful for a specific study, and then add or compare further observations, if any.
In the field of conservation or for other particular
e n v i r o n m e n t a l purposes, observations are made to study certain individual problems, so that the instrumental apparatus as well as the operative methodologies are specifically tailored to fit the actual problem. On the other hand, it is evident that weather stations are planned and standardised for meteorological measurements as defined by international protocols, so that they are in principle interchangeable. Not only instruments and methods are generally inappropriate for conservation purposes, but also the free position where the standard weather station is located is not representative of the specific site of the monument, perturbed by nearby buildings, trees or other obstacles. For instance, it is sufficient to consider that, in the wake which forms downstream to a building, the wind direction is opposed to the unperturbed flow measured by the weather station. One of the aims of a field test for cultural heritage is just to describe the complex and 'perturbed' situation originated by the presence of all the obstacles near the monument, whereas the weather station is aimed to monitor the 'unperturbed' situation. It is absolutely restrictive to consider the individual parameters separately, omitting interactions and feed-backs. The microclimate is determined by the complex interaction of several factors and not always an accurate interpretation of what is h a p p e n i n g is possible, or also to forecast the future development of a certain situation. However, our knowledge progresses with small steps and the atmospheric thermodynamics offers a good start. Air and precious surfaces to study and preserve can be found everywhere, either indoors or outdoors. Although traditionally the indoor and the outdoor environments are considered very distinct, in practice they present similar problems: both undergo daily cycles of temperature and humidity, either forced by the solar cycle or by heating, ventilating and air-conditioning systems (HVAC); both are exposed to intense shortwave radiation which may be the direct solar irradiation on the open sky or through window, or artificial light; both are affected by advective air movements, i.e. wind, or air currents, or air infiltration through cracks and openings, or turbulence generated by sources of momentum, e.g. people movements, heat sources, surface roughness in the presence of advective movements. Rainfall and dew are considered typical of outdoor environments, but often rainfall penetrates inside through disconnections, or condensation forms on the
window panes, on the surface of cold objects or inside pores. External pollutants can penetrate through windows and doors and are transported from room to room, and deposit via the same mechanisms, either outside or inside. The same problems can be found outside or inside, although the scale may change as well as the level of complexity. The most important distinction is that the indoor microclimate can be controlled, at least in principle, and it is very important to know how to do it. Although the importance of the indoor microclimate has been stressed for a long time (Benoist, 1960; Camuffo, 1983; De Guichen, 1984; Tomson, 1986; Michalski, 1993; Padfield, 1994; Camuffo and Bernardi, 1995a) very often inappropriate standards of comfort are used, which are based on human well-being and not on the science of material conservation. Are museums oriented towards the well-being of humans or exhibits? Is the main aim of museums to show objects for cultural and educational purposes, or to preserve artefacts in the most appropriate conditions for conservation, to which visitors should adapt? Of course it is necessary to combine the two needs paying attention that the effects on works of art are cumulative and often irreversible. In Europe, the situation was better more than 35 years ago, when Benoist (1960) wrote: 'In winter, museums should be heated not only for visitors and
guardians, but also for works of art. In Europe, visitors are content with 15~ and in America with 21 ~ In Western Europe the above thermal level was appropriate for safely obtaining a correct relative humidity without the need of supplying continually too much moisture to mitigate the exceedingly dry environmental conditions. Unfortunately, Europe is today following the d a n g e r o u s USA temperature standard. In the past, local climate was carefully observed and exploited to the full to adapt buildings and activities to the external ambient and benefit of a natural
microclimate. For example, Hippocrates (De locis), Pliny (Epistulae, II, 17, 7-19), Vitruvious (De Architectura, VI, 4, 1-2) and Palladium (Quattro libri dell'architettura, Book II, Chap. XII), show how a building was constructed with respect to its exposure to the sun, wind and precipitation. Rooms were exploited according to the temperature and type of light that could enter through the windows. Nowadays, the modern technology often induces to think that the climate outside can be ignored, and that a new independent, artificial microclimate can be created inside a building, controlling humidity and temperature with advanced sensors and microprocessors. By maintaining intake air in excess of exhaust of air, commercial buildings and museums are maintained at an indoor pressure higher than the outdoor value, which reduces infiltrations of external air and pollutants, but creates an internal atmosphere, with its artificial microclimate, which is usually not in equilibrium with
walls, floors, ceilings, exhibits, and needs many frequent heat and moisture transfers, to balance the people influence, the air leakage, and the exchanges between air and surfaces. It has been calculated that about 30% of the moisture supplied to a room is absorbed by the room surface (Rosenhow et al., 1985) with the consequence that the benefit in mitigating the air dryness is negatively compensated in moistening surfaces. The excessive confidence on HVAC and their huge use caused in general more damage than advantages. The indoor temperature is regulated on man well-being without keeping into consideration the regional climate and in particular the natural value of the seasonal moisture content (except for calculating the power needed for the HVAC) in order to obtain a reasonable relative humidity. The desired level of temperature is assumed as a primary need, and the concentration of water vapour is increased or decreased accordingly, to create a new artificial microclimate. Several systems which control the humidity level in historical buildings or museums have been analysed with a number of field tests; however, although these systems are good in theory, and the machines operate correctly, the environmental impact has been often found to be disastrous. In fact, a cloud of moist, cool air is generated by these devices that are generally located near the walls where paintings or other precious works of art are positioned. This cloud moves with the internal air motions, and affects all the works with abrupt humidity and temperature changes. The technological limit of HVAC is not in designing new powerful or sophisticated machines, but rather in being able to distribute in a room the new air steadily and homogeneously. The homogeneous distribution of heat and vapour in a room would require too many diffusers, scattered everywhere at short distances. The inflows cause undesired air movements which increase inertial deposition of suspended particles. Unfortunately, present technological research is focused on making more and more sophisticated machines, not in studying and controlling their use. Atmospheric thermodynamics is a precious tool in environmental diagnostics and in the progress of our knowledge on the basic processes of m o n u m e n t deterioration, evidencing causes and effects.
1.2. AIR, WATER VAPOUR AND PERFECT GASES The dry air is composed of a mixture of several gases, mainly nitrogen (N2, 78.084% volume), and oxygen (02, 20.946%), with Argon (Ar, 0.934%), and some
other minor constituents, i.e. carbon dioxide (CO2, 360 ppm, variable), neon (Ne 18.182 ppm), helium (He, 5.24 ppm), methane (CH4, 1.77 ppm), krypton (Kr, 1.14 ppm); hydrogen (H2, 0.5 ppm), Xenon (Xe, 0.09 ppm). Many other trace gases and particles, considered pollutants, are dispersed in the atmosphere, some of them are non-reactive and most of the are reactive, e.g. SO2, NOx. Atmospheric chemistry studies the behaviour and effects of these substances which are reactive especially in association with atmospheric water. For sake of simplicity, the air is often treated as it were an ideal gas, composed of particles having the mass M = 28.96 which is the average weight of the molecules of this mixture. Water vapour is a variable constituent of the atmosphere, whose concentration depends on air temperature and weather vicissitudes, and generally ranges between 0.5 and 4%. This variability is a consequence of the fact that water vapour m a y change state, becoming liquid or solid, and may precipitate or be in different ways transferred from the atmosphere to the earth's surface, or vice-versa. The water molecule itself is far from being a "perfect gas" particle as it is composed of one oxygen and two hydrogen atoms which are 0.95 A far from the oxygen nucleus, and are disposed forming an angle H-O-H equal to 105 ~ This asymmetrical configuration generates an unbalance between positive and negative charges, so that the water molecule is an electric dipole which can orient in an electric field (exerting a strong dielectric action), or may interact with other molecules or bodies exerting van der Waals and electric forces. However, in a first approximation, when the water vapour does not undergo changes of state, for several purposes it can be treated as it were a perfect gas, although some departures may occur and must be considered, as we will see later. Main problems arise w h e n the water vapour approaches saturation, or w h e n a vapour molecule impacts on a surface whose temperature is below the dew point, or which is contaminated with hydrophilic salts. In these conditions, instead of exerting elastic impacts, the vapour molecule will stick on the cold surface, or on the salts (the same holds for condensation nuclei), and the effective number of "free" gaseous molecules decreases. In order to simplify things, the state of a gas is statistically represented by some key p a r a m e t e r s which characterise the average properties of the population of particles. A 'perfect gas' is an ideal reference gas, where the molecules do not exert any force on each other and all impacts are elastic; it is perfectly described by the so called state equation
p V = n .;,r
(1.1)
where p is the pressure, V the volume, n the n u m b e r of moles n = m/M (where m is the actual mass of the gas and M its molar mass),. ~/?~ the universal gas constant, i.e. .~/2~ = 8.3169x107 erg mo1-1 K - l = 1.986 cal mo1-1 K-l; T is the absolute temperature (degree Kelvin, K). For a particular gas X the gas constant is defined as .J2x = .~/2/Mx so that for dry air Ma = 28.965 g mo1-1 and .~/?~a = 0.2870x107 erg g-1 K-1 = 0.06857 cal g-1 K-l; for water v a p o u r Mv = 18 g mo1-1 and .t2v = 0.4615x107 erg g-1 K-1 = 0.1102 cal g-1 K-1. For the gas X the state equation becomes Px V = mx .~/2x T
(1.2)
where Px and mx are the partial pressure and the actual mass. Although a real gas may depart from the perfect gas model, this is, however, the basic equation which will be useful in the following treatment and can also be applied, within certain limits, to the water vapour.
1.3. TEMPERATURE
Temperature is the condition which determines the direction of the net flow of heat between two bodies, i.e. from the w a r m e r to the colder one. For this p r o p e r t y , a t h e r m o m e t e r can be p u t into equilibrium with a b o d y , in o r d e r to read the temperature of the b o d y on the thermometer, if the thermometer does not perturb the original temperature of the body and is not influenced by other factors. From the t h e r m o d y n a m i c point of view, the temperature T represents the average translation
kinetic energy Ec of the gas molecules, according to the principle of equipartition of the energy 3
Ec - -~k T
(1.3)
where k = 1.38x10 -16 erg K -1 is the Boltzmann constant, which represents the ratio .J2/.1J/fvhere ....l / - 0.6023x1024 is the Avogadro number, i.e. the n u m b e r of atoms or molecules which form a mole; the latter is obviously the a m o u n t of substance whose weight (expressed in g) equals the atomic or molecular weight of the substance. As the air is p r e d o m i n a n t l y composed of diatomic molecules characterised by 5 degrees
10 of freedom, the total kinetic energy Et is 5 Et = -2 k T.
(1.4)
For these relationships T is also called molecular temperature. In meteorology it is also called the dry bulb temperature as opposed to the wet bulb temperature which will be seen later. In the following the absolute thermodynamic temperature (K) will be indicated with the capital letter T and the temperature in degrees centigrade (~
with the
lower case t. As t = T-273.16, then AT = At. The value 273.16 is the thermodynamic temperature of the triple point of water, and is usually approximated 273. The concept of temperature can be easily extended from a gas to a liquid or a solid, and a theoretical thermodynamic definition is preferred to the empirical one:
the temperature is the variable measured by a thermometer. As it will be discussed in the following, in the absence of errors, the thermometer measures only the temperature of its bulb, which is not necessarily the same of the object under investigation. In fact, the thermodynamic equilibrium involves a balance between conductivity, convection and radiant heat exchange, which are different for each body. In particular, radiant heat is exchanged with other external bodies either nearby or far away, and this contribution is not included in the definition of temperature. The temperature is a consequence of the present and past energy balance which also includes advective contributions due to the transport of air masses, and only in rare cases is homogeneous in a body or in a room.
1.4. MECHANISMS OF TEMPERATURE DEGRADATION The temperature is a very important factor in conservation of works of art, as changes of this parameter induce differential expansions in the materials and tensile strengths between the surface and the subsurface structure. Temperature cycles induce a n u m b e r of mechanical weathering mechanisms and accelerate fatigue failure in susceptible materials; the faster the cycle, the greater the temperature gradient inside the material, the steeper the front of the thermal wave propagating inside the material, the greater the strength, the faster the ageing and the damage in the surface layer. In fact, the material acts as a low pass filter which attenuates the penetration of the rapid surface temperature changes: the shorter the duration of the
11 fluctuation, the thinner the layer affected by it (Camuffo et al., 1984). However, it must be remembered that the key part of the artistic value of monuments lies in the surface layer. For these reasons daily (or shorter) temperature cycles are much more important than the seasonal ones. Thermal cycles may cause mechanical disgregation of outer part of stones, beginning at the discontinuities included into the rock and the interfaces between the different minerals which form the stone. It is to be noted, however, that the pure thermal effect is an academic abstraction, as in the field the water activity is always superimposed to this variable with synergistic effects. A typical effect is the granular disgregation of magmatic and metamorphic rocks. The thermal anisotropy of the crystalline lattice, the size of the granules and their spatial association determine a system of internal tensions which result in surface disgregation of the granules. The greater the granules, the greater the tensions and the faster the deterioration rate. Sedimentary rocks are characterised by a more regular structure and composition, but the nature of the binding cement between granules acts as a discontinuity factor (Veniale, 1995).
Fig.l.1 The leaning Pisa Tower surrounded by loggias. In the daytime, the solar heating causes the expansion (and compression) of the columns and an additional temporary bending of the Tower which follows the apparent course of the sun.
12 The expansion mechanism may be also important for structural stability. For example, the Pisa Tower (Fig.l.1) is composed of a cylindrical body contoured by six orders of loggias, having thin columns. In the sunny days of the hot season, the stone temperature of the thick central body remains nearly unchanged, but the external parts, and in particular the columns, undergo daily cycles of some 20~
which cause
the expansion of the hot stone (Camuffo et al., 1996). Considering that the expansion coefficient for limestone is 8x10 -6 ~ and that the Tower extends for some 50 m in height, the above daily excursion causes 8 mm vertical expansion of the hot side and temporary bending of the tower. The daily movements of the top, which are forced by solar radiation (and/or wind) have been measured with a pendulum, and the maximum excursion is some 4 seconds of arc from East to West (Jamiolkowski, 1995), which corresponds to about 1 mm of horizontal displacement. The limestone expansion produces a compression of the thin columns and their capitals, most of them are severely damaged or have been substituted in the past. Another consequence of temperature variations are changes in the degree of saturation of the water vapour, and the amount of water adsorbed in the bodies. Several materials, e.g. wood, parchment, ivory, plaster, change their dimension with water content, expanding or contracting, shrinking, micro or macro fissuring and so on. The effects of an external temperature forcing are in general very complex. For instance, wood is characterised by a small heat conductivity, and the internal propagation of a temperature change is preceded by the propagation of a change of relative humidity due to the diffusion of vapour molecules dispersed in air, and this is followed by redistribution of the water absorbed into the grains. As a consequence, delayed differential stresses and shrinking are induced. Again, changes of temperature in porous stones cause changes of relative humidity, which in turn is related to the evaporation of the water in the pores, increasing the concentration of dissolved salts and arriving at the precipitation of them when the solution becomes supersaturated. In sunny days monuments are overheated by the solar radiation and dramatic temperature changes (thermal shocks) occur when the sun appears or disappears; in addition, marked short term (3-15 minutes) temperature fluctuations are a response to variations in wind speed and light cloud cover (Camuffo, 1981; Jenkins and Smith, 1990). Granular disgregation is frequently found on stones with granula r or crystalline texture, e.g. granite or marble, where stresses generated between grains or large crystals with crystallographic axes differently oriented, or having different expansion coefficients, produce fatigue failure along grain or crystal interfaces. For
13 example, calcite crystals expand along the principal axis and contract along the secondary one in the case of a temperature rise. In the long run, heating-cooling cycle will slightly displace crystals from their original position forming a less regular, weaker structure, which will lead to the disgregation and loosing of granules, called
sugaring. The damage is irreversible and cannot be restored (Fig.l.2). In addition to temperature forcing, also wetting-drying cycles cause expansion and contraction cycles in some kinds of stones. However, although disagreement persists over the effectiveness of insolation weathering as a direct cause of rock breakdown, the opinion is that most granular disgregation occurs as a result of a previous weakening of the rock, normally due to chemico-physical weathering mechanisms acting in combination or sequence and involving intrinsic rock properties (e.g. albedo, thermal conductivity and heat capacity, mechanical strength, porosity and specific surface), thermal variations, repeated stressing of the material and role of moisture and dissolved salts (Smith, 1978; Warke and Smith, 1994).
Fig.l.2 Granular disgregation of marble. The restoration had dramatic consequences. Aurelian Column, Rome. Finally, the air temperature is a key factor in determining the habitat for biological life and in controlling metabolisms. At temperatures below 20~ the metabolic processes are reduced and the biodegradation due to bacteria can be often prevented with an appropriate choice of this and other environmental variables (e.g. humidity, light, ventilation). However, although the temperature range from 20 ~ to 35~
generally favours the microbiological activity, the variable response and
adaptability of microorganisms to lower or higher temperatures, as well as to other extreme and stressing environmental conditions (e.g. water activity, pH-value,
14 ionic/osmotic strength), has to be strictly considered when preventive remedies against the microbial attack should be undertaken. Microbial biofilms covering the surface of stones or other materials have several negative consequences: they may enhance the deposition of particles, and the deposited material, as well as the biofilm form a composite layer which changes the albedo of the surface, the porosity and water vapour diffusion inside the material, the thermal conductivity and the water balance, especially in the outer, endangered uppermost layer (Warscheid and Krumbein, 1996). On the other hand, in some cases biofilms exert a protective function with their polymeric matrix, so that it is difficult to formulate an accurate balance between negative impacts and positive factors, especially in view of the variable response of the material contaminating mizroflora (Warscheid and Kuroczkin, 1997). A comparison can be made with the van't Hoff's rule for chemical reactions, which states that the conversion rate is doubled when the temperature is increased by AT = 10~
or is halved for the same drop of temperature. Although this
rule may describe in general the response of biology to temperature, it cannot be simply adapted to all biological reactions.
1.5. THE TEMPERATURE IN A BUILDING, A ROOM In a building, the external forcing (e.g. solar radiation, heat conduction across roof and walls, air exchanges through openings) depends upon the architectural features, and the materials choice. Thin or conductive walls are sensitive to the apparent daily course of the sun; windows may allows for penetration of solar beams and behave as a green-house; in addition they can regulate exchanges of external air. Different exposures in a building have a different heat balance, and not all the rooms have the same temperature. The inner rooms are more shielded and the external forcing is smoothed out; and this is particularly true for the ground floor, where the soil has an enormous heat capacity. The opposite holds for the last floor, being topped by a roof that receives solar radiation during the day and looses infrared (IR) radiation during the night. HVAC or people may completely change the natural equilibrium. Although rooms are often provided with one thermostat for the temperature control, the temperature in a room cannot be described with only one, although timedependent value, but is a four-dimensional function, i.e. of the specific point (x,y,z) and time. As the air is mobile and has a very small specific heat, the inside temperature will be determined by exchanges with floor, ceiling, walls, windows,
15 doors, and all the other sources or sinks of heat, e.g. heaters, air-conditioning systems, solar radiation, lamps, people. If there are open w i n d o w s or doors, or forced flows of air at different temperature, the advection of new air might be the dominant factor. In a closed room hot air rises, but its ascent is stopped by the ceiling: the air distributes according to its density, i.e. the hot and less dense in the top, and the cold and more dense in the bottom. For this reason a stable atmospheric stratification with temperature rising with height tends to form. However, if there are some sources of sinks of heat, or all the surfaces are not exactly in thermal equilibrium with the air at their height, the mass conservation requires that the ascent of warm air is always associated with an equal flow of descending air, and vice-versa. This may happen in several ways, determined by the boundary conditions and room architecture, as we will see with some different examples. (i) Everything is in equilibrium, except for a heat source inside the room. Over the heat source a rising column of hot air will form, it will be stopped and diverge at the ceiling level, will form a new less dense layer on the top, and all the previous ones will remain below, with a general subsidence of the whole volume. If the source is not too hot, the convective motion develops in height up to it finds air less dense, and will be stopped and diverge at this level, leaving unaffected the upper layers. Similarly, if the heat source is not located on the floor but at a middle height, the descending flow stops at the source height, as below it founds colder and denser air. As the mass should remain the same, the ascending and the descending fluxes are equal, so that the ratio between the ascending and the descending velocities equals the ratio between the cross section of the room deprived of the section of the ascending column, and the cross section of the ascending column. (ii) Everything is in equilibrium, except for the floor which is colder (e.g. ground floor in the summertime), o r the ceiling which is warmer than the adjacent air (e.g. metal roof or domes in a sunny day during the hot season). The air-surface exchanges increase the intensity of the atmospheric layering, and the air remains motionless. (iii) Everything is in equilibrium, except for the floor which is warmer (e.g. floor heating), or the ceiling which is colder than the adjacent air (e.g. metal or glass roof in the winter). The air becoming into contactwith a warm floor forms convective rising cells, associated with other descending air, like the convective movements inside a pot of boiling water. Similarly, the air coming into contact with the cold ceiling becomes denser and sinks, forming rivulets of descending cold air associated with convective rise which result in a continuous mixing of the whole atmosphere.
16 (iv) Everything is in equilibrium, except for the walls which are warmer. The heat exchanges form an internal boundary layer of ascending, warm air along the walls; the w a r m air substitutes the previous top layer below the ceiling and slowly displaces downwards the whole mass of stratified layers. If the walls are colder, the internal boundary layer flow is downwards, cold air accumulates above the floor and rises the whole mass of stratified layers. From the above examples it appears that, in general, a natural layering is expected in an inside atmosphere and some air motions may derive from the presence of bodies with different temperature. Thick walls of historical buildings have an enormous heat capacity, tend to maintain the same equilibrium and the typical condition is a steady condition of thermal layering except for the presence of perturbing factors, e.g. HVAC systems, lamps or people. The thick walls of historical buildings are very effective in damping the daily temperature cycles and also, to a minor extent, the seasonal wave, so that internal microclimate is homogeneous, weackly dependent upon the daily cycles and the external weather conditions and the seasonal variability is reduced. The best situation happens when the seasonal time-lag of walls, floor and roof are similar; when they are different the internal stability changes seasonally. For instance, in the case of churches, the ceiling follows the seasonal variations with a shorter time-lag, and the floor based on the ground with a much more longer one, so that in the summertime the relatively warm ceiling and the fresh floor generate an internal layering; in the wintertime the relatively warm floor and fresh roof tend to destroy the air stability with some internal mixing shown by an isothermal vertical profile. An example is given for the Basilica of $. Maria Maggiore, Rome. The external temperature cycle is some 10~
and the internal one order of magnitude less, being
governed by the limited exchanges with the exterior, the walls, the floor and the ceiling, and the heat accumulated (or lost) by these structures in the previous months. In the late summer (Fig.l.3a), the walls have reached equilibrium with the season climate, and the inside temperature is near the average of the external temperature cycle. The external weather conditions have a limited influence on the indoor microclimate, whose changes are mainly governed by the doors and windows openings, and by the nocturnal cooling of the metal domes. The effect of the opening of the two front doors is visible in the early morning, when cold air enters and a lowering of the air temperature is found by the sensor at 3 m level, but not by the sensors at 7 and 11 m. In the autumn (Fig.l.3b), the indoor temperature is greater than the average external values, being close to the daily maxima which equal the temperature of the walls which show a memory of the heat accumulated in
17
36
./r
34 L,)
T outdoor
32
....,
.,,.;,~ ~
/"~
30
~ .
.
.,./--,,,,~~;~ T(7)
t~
~
.~
.,,~/~~~..
36
42
28 [-,
26 24 22 0
6
12
18
24
30
z
T i m e (hr)
24
22t G" ~
.=
20
I
7,7, --~-~....
. T(3L~..
18 16
~
14
[..
12 10 8
0
6
12
18
24
30
36
42
48
T i m e (hr) Fig.l.3. External and internal temperature (measured at the heights 3, 7 and 11 m) in the Basilica of S. Maria Maggiore, Rome, in summer (top) and autumn (bottom). The thick walls are very effective in damping out the external daily cycle, and in autumn the heat accumulated during the hot season makes the internal temperature higher than the external average value. Cold air entering through the door is visible at the 3 m level at the opening in the morning (upward arrows in the summer example, 9 to 10 August 1996), and a rise of temperature is visible during the liturgical offices on Saturday evening and Sunday (downward arrows in the autumn example, 19 to 20 Ocober 1996).
18 the hotter months. Peaks of temperature were found in all the seasons during the liturgical offices celebrated Saturday evening and Sunday morning and evening, for the lighting made with incandescence lamps and the massive participation of faithful people. Also interactions between rooms are important. The most common situation is to find consecutive rooms with air flowing through the door and spreading from a room to another (Fig.l.4). The circulation may be forced by HVAC systems or existing pressure differences generated by external winds through w i n d o w s or doors.
18.2
1
~//.#'/I.//x/////h
8.4
,.
~/i/////,
~ I / / / / / / . , / / / / / / / / / / X ~
_
~J 19.3
Fig.l.4 Air with a different temperature flowing through the door and spreading in the refectory of the Leonard's Last Supper, Milan (14 November 1982, after Camuffo and Bernardi, 1981a).
Fig.l.5 Interactions between different floors in the S. Rocco Oratory, Padova. In the winter, mild air rises from the cellar through the staircase, spreading in the Oratory. In the bottom of the room (i.e. the right of the map), the wall is milder, being contiguous with another, heated building (18 January 1996).
19 Other important interactions occur between different floors. For example, the San Rocco Oratory (Fig.l.5), Padova, has a staircase which connects the Oratory with an underground cellar. Both are without heating, but the cellar is less sensitive to the daily temperature changes and also attenuates the seasonal temperature wave. In the summertime, and especially during the daytime, the cellar is much colder than the Oratory, so that the cold air remains entrapped in the cellar without any exchange with the upper floor. In the wintertime, and especially during the night and morning hours, the cellar is milder, and this generated a continuous exchange through the staircase: cold air descends and mild air rises with some entrainment and mixing with ambient air up to the lighter air reaches the ceiling, and then spreads horizontally. In addition to the mild area near the staircase, another mild area is found near the opposite wall in the bottom of the room, as this wall is in common with another building which is heated. Another interesting example of interactions between an architectural structure and its surroundings was found at the Ducal Palace in Urbino, Italy (Fig.l.6). This
D
0
[]
[]
[]
[]
[]
Fig.l.6 The microclimate of the curtyard in the Ducal Palace, Urbino, is mainly determined by the daily course of the sun. On the right upper corner, the staircase drains out, as a gigantic chimney, the warm air, determining a cold airstream that invades the staircase (19 December 1982, after Camuffo and Bernardi, 1985, reprinted by permission of Elsevier Science).
20 beautiful Renaissance building has a courtyard which is surrounded by a loggia, and in a corner of the courtyard the staircase of honour connects the court with the upper floors. Particularly damaged are the decorations at the edge of the staircase, which has magnificent bas-reliefs in a local oolithic limestone which is not resistant to weather injuries, especially rainwater. Some field surveys were made to establish the cause of this degradation. In fine days the courtyard and the loggia h a d a t e m p e r a t u r e distribution that followed the apparent course of the sun and the middle of the courtyard was generally colder, for the better ventilation which is found increasing the distance from the architectonic structures, and colder was found also the staircase as the w a r m air was sucked in and drained a w a y as it h a p p e n s inside a gigantic chimney, but this situation was not linked with the damage. Also capillary rise was excluded as well a possible contamination from a back room that in the past was a deposit of sea salt. The cause was found during a rainy day, w h e n a stream of rainwater collected by the roof and gutters was seen to fall d o w n at each corner of the courtyard, being the building without drainpipes. The friction reached with the air after a few metres of free fall, caused the water stream to explode into a myriad of droplets, which were transported by the drainage flow through the staircase and splashed against the decorations. Of course the suggested solution was to apply a drainpipe, but the second hypothesis, i.e. a glass pane to protect the decorations and a glass door to stop the drainage was preferred. Modern buildings made of metal and glass have a conductivity which is higher than traditional brick walls and are more sensitive to the external w e a t h e r conditions. As the thermal capacity of walls and roof is relatively small, the building does not smooth out the seasonal wave. In the wintertime (and during the night) the outer structure cools and generally assumes a temperature which is intermediate between the heated interior and the cold exterior, so that the cold ceiling and walls generate a continuous internal mixing. For example, the Sainsbury Centre for Visual Arts, Norwich, which is built with metal and glass structures with some insulating panels, during a winter survey in a foggy week in December 1996 was found to have the internal air temperature Ti = 19.5~ were ranging between 14.2~
and 15.7~
the metal and glass ceiling panes and walls the outside temperature was To = 7.2~
The continuous mixing of the air masses generated by the contact with the cold structures is also artificially increased, and even in a much more enhanced extent, by the m a n y fans distributed all along the walls, to inject w a r m air in the room. In order to reach the interior of the wide room, and obtain a uniform temperature, the ventilation rate is very high. However, this violent mixing is not sufficient to produce a very uniform temperature (Fig.l.7) and exchanges of heat and moisture
21 are favoured, as well as the deposition of airborne particles. Possibly for this, for safety or other reasons, the main parts of objects is appropriately protected by an individual plexiglas case. On the other hand, in the sunny days of the w a r m season, the ceiling becomes hot forming internal layering, and the glass panes generate some green-house effect.
Fig.l.7 Horizontal cross section of the Sainsbury Centre for Visual Art, Norwich (U.K.), showing the temperature distribution. Modern buildings, made of metal and glass, do not benefit of the inertia of the thick wall, and the microclimate is conditioned by heat exchanges and forced mixing, but fans are not sufficient to obtain a very homogeneous temperature distribution. The 9 December 1996 at 16.30.
1.6. THE TEMPERATURE IN A SHOWCASE We have seen that inside buildings, the 'primary' external heat w a v e is smoothed out by the walls, but abrupt temperature changes are generated by local sources, and the perturbation spreads in different ways within the rooms. For this reason a further natural filter is often useful to smooth out these 'secondary' temperature changes, and show cases accomplish to this aim (Fig.l.8), in addition to protect delicate exhibits from dust deposition and accidental shocks. In this example taken from the Uffizi Gallery, the external daily wave reaches some 20~
and both
the room and the show case have waves with some 4~ amplitude, but the show case has a temperature which is smoothed out with a 2 hr time lag. The exhibits in the case are exposed to a slighly smaller temperature span as the unshielded objects in
22 the room, but are protected against rapid fluctuations or temperature (and humidity) changes. It might be useful to comment that the outside temperature was measured with a sheltered thermometer suspended 30 cm far from the wall, and the thermometer was immersed into the internal boundary layer of hot air which forms and rises along the wall when the latter is hit by solar radiation. This is actually the air which envelops the lighted side of the building, warms the window panes and penetrates through the windows fissures, but is different from the free air, as it would be measured with a standard weather station. 22 20
T case
18 16 Q,I
;= ~= I-i
14 12 lO
E
8
[-"
6
T outdoor i
0
,
l
6
i
,
i
12
i
,
i
18
i
i
i
24
i
!
i w
30
,
,
i
36
!
,
i
42
,
,
i
48
i
i
i
54
,
,
a
60
|
,
i
,
66
,
72
Time (hr) Fig.l.8 Comparison between the outdoor temperature, the indoor value and the temperature inside a show-case. Pollaiolo Room, Uffizi Gallery, Florence, 11 to 13 March 1997. The lighting should be obtained with lamps placed outside the case; on the contrary, a lamp inside will act as powerful heater and most of the heat dissipated will remain entrapped inside the case. However, although the light source is external, when a show case is made of a material which is not fully transparent to the IR, it becomes a green-house which causes a dangerous overheating of both the air
and the exhibits preserved inside, as well as a drop of relative humidity. It is popularly known that glass is relatively opaque to the IR radiation, and that more appropriate are plexiglas (i.e. polymethylmethacrylate), polycarbonate, poly-ethylene, polypropylene. However, for all these materials the transmittance in the IR band is neither 1 nor homogeneous, but is generally good except for some narrow absorption bands (Touloukian and DeWitt, 1972; Saint-Gobain, 1977; Michalski et al., 1991) whose relevance changes with the intensity of the spectral band of the IR radiation having the same specific wavelength. For this reason, only
23 looking at the absorption spectra, it is difficult to decide which material is the best one and a laboratory test is much more useful to clarify ideas. Some identical show cases have been built, sized 20 x 10 x 10 cm and with panes 5 m m thick, made one of glass, one of plexiglas and one of polycarbonate, as well as others with panes having twice this thickness. In the bottom of these cases, a black sheet of paper has been placed in order to transform absorbed light into IR radiation, and a thermometer. All these cases have been lighted from outside, with a tungsten incandescence lamp, supplying 500 lux at the top of the boxes in order to obtain a clear effect. The panes, being partially transparent to the IR radiation, absorb part of IR the incoming from the incandescence lamp as well as part of the outgoing radiation, and the heat accumulated in the panes is re-distributed part inside and part outside. The result of this balance is shown in Fig.l.9.
glass 0.5 cm ~3 LJ o
bib
plexiglas 0.5 cm and polycarbonate 0.5 cm
,,v-i
2 Q,I
plexiglas 1.0 cm
01
0
30
60
90
120
150
180
210
240
270
300
330
360
Time (min) Fig.l.9 Overheating, as a consequence of the green-house effect, of show cases made of: glass, plexiglas, polycarbonate. The cases are lighted with 500 lux from a tungsten incandescence lamp. It is clearly seen that plexiglas and polycarbonate practically behave in the same way, and that their overheating (i.e. 2.9~ 3.5~
is only slightly less than that of glass (i.e.
Making twice the pane thickness a delay is introduced because of the initial
advantage of a greater portion of the IR that is stopped (and accumulated) in the top pane and cannot penetrate inside; after some 2 hr this advantage is lost and the thicker thickness generates a more efficient green-house effect, as expected. After some 6 hr, the overheating is 3.1~
i.e. only 0.2~ more than the box having panes
with half thickness. This experiment clearly shows that, in the case of external
24 lighting with incandescence lamps, the plexiglas is slightly better than glass. A further advantage for short term lighting can be obtained increasing the thickness of the pane. This would reduce and make more gradual the internal overheating and, consequently, the drop in relative humidity. It is thus necessary to avoid the IR radiation, as far as possible, and fluorescent lamps might be a relatively good approach. The same experiment discussed above but with 500 lux generated with a fluorescent lamp led to no detectable overheating. However, these lamps should be controlled for the harmful ultraviolet (UV) emission, but the main drawback is that their irregular spectrum gives an unpleasant tune to colours. The best method consists of using fibre optic lighting, which are, or can be made, practically free of dangerous U V and IR radiation, as it will be discussed in Chapter 4. Showcases, wall display, display tables and so on are useful only if they are suitably built, with use of materials which are inert and no off-gassing, and are appropriately managed. Cases with forced ventilation do not meet the aim of smoothing out room temperature fluctuations. Airtight cases with a closed atmosphere to be dust free should be built with materials that do not release and accumulate noxious substances, or biological infection.
1.7. IS IT POSSIBLE TO COMBINE PEOPLE COMFORT, CONSERVATION NEEDS
AND LOW COST? When a building has a natural microclimate which is not comfortable for people (only rarely the problem is posed whether it is also suitable for conservation), HVAC systems are installed to obtain the desired conditions. Traditional systems are used, e.g. hot water radiators, fan coil convectors, radiant panels, humidifiers) following the everyday practice of keeping a temperature fluctuating around the desired level, or switching on/off the system according to the business times with sudden jumps or drops in temperature (and, consequently, in relative humidity). All these systems are characterised by intermittent use and are located in spot areas, so that they continually generate microclimate perturbations. The use of fans generally worsen the situation, forcing air currents in the rooms. The worst situation is reached in winter, in buildings used only at times, as in the case of churches attended weekly for the Saturday and Sunday liturgy. The first need for conservation is a constant climate, people need a mild climate, and a constant mild microclimate seems the most obvious conclusion, but it is expensive.
25 As it is not easy to combine man comfort, conservation needs and low costs, some different solutions have been attempted, but conservation is more often sacrificed. A compromise solution is to reduce at minimum the heating, warming only pews with electric wires at low temperature, when people is in. This method is aimed at giving a comfortable contact with pews where people seat and rest feet, and is acceptable for heavy dressed people and for a relatively short time. The air should remain unaffected or so. If the temperature is elevated and too much heat is transferred to the air, convective motions are generated, associated with downwards currents of cold air, having the ceiling and wall temperature. These cold flows are very unpleasant to people, and these internal air motions lead to increased deposition rate of candle smoke and other suspended particles. This method is not common in Italy, for the elevated cost of the electric power. Another popular compromise solution is to heat the floor in the pew area, just to mitigate the temperature where people stay. The underfloor heating system uses pipes which carry hot water, placed over an insulating layer and embedded in a conductive layer which constitutes the floor. Heat is transferred from the pipes to the floor and the room is heated by low temperature IR emission from the floor. An advantage of the floor heating is that a large mild temperature heating surface produces comfort at lower air temperature (about 2~
therefore reducing heating
requirement (Porges, 1995). However, when the warm surface is reduced to the pew area, the comfort is diminished, and in addition pews intercept the infrared radiation, leaving people in a relatively cold environment. In any case, floor heating is characterised by low risk for damage to frescoes, paintings, statues and other church decorations, but by high risk to historical pews which undergo enhanced temperature and humidity changes. When such a system is designed for daily use in business buildings, the highest efficiency is obtained with the combined effect of IR radiation and air heating via floor conductivity which generates important convective motions in the air. However, in the case of weekly use in churches, when walls and ceiling are much colder than the air temperature, the air which comes into contact with the cold surfaces sinks, forming down droughts of cold air which are harmful to both people and conservation. In order to avoid dangerous convective motions, the floor should radiate without transferring heat via conductivity to the air. For this reason materials with high IR emissivity and low surface conductivity should be used. Several materials are good emitters e.g. Dolomite which reaches 96% emissivity; granite 93%; brick, 93%; oak 90%, and have a different conductivity, e.g. the above materials have respectively 1.5, 2.9, 1.4, 0.16 W m -1 K -1, so that granite is much more conductive
26 than wood, which is quite an insulator. In most cases inappropriate materials are used for the floor, having a too low conductivity which reduces (or vanishes) the system efficiency or being too much conductive and generating enhanced convective motions, or being poor emitters. For example, the medieval church of Colle S. Lucia in the Italian Alps, 1400 m a.m.s.l., has an underfloor heating just below the pew, but with a w o o d floor. During a field survey in January, with the hot water in the pipe at 30~
the floor was at some 15~ and the air at 1 m was between 8 and 9~
the hot water temperature to 60~ the floor temperature rose to 23~
raising
but the gain in
air temperature was nearly insensitive, being only one degree or so (Fig.l.10). 25 23 ~-21 o
~ t~
19 17 T(floor) ~ 15 ...................................................
.....~
T(0.1) T(0.5\
~
[--11
0
I
I
!
I
I
!
I
I
!
I
3
6
9
12
15
18
21
24
27
30
33
Time (hr)
Fig.l.10 Floor and air heating in the church of Colle S. Lucia (Italian Dolomites) from 16 January 1997 at 00.00 to the next day at 9.00. Floor temperature (thick line) and air temperature at 0.1; 0.5 and I m; the measurement at 2 m shown the same temperature found at 1 m. The sharp rise in floor temperature in the afternoon of the 17th is due to the rise of hot water in the underfloor pipe from 30~ to 60~ The air heating from 10.00 to 17.00 of the 16th is due to the external sunshine and warming. Systems based on floor heating need several hours before to w a r m the surface layer and reach the highest efficiency, so that they must be put into operation one or two days before the use, determining dangerous environmental cycles and reducing the spare of money. In practice, in order to abate costs and shorten heating times, these systems are often integrated with other faster systems, e.g. with inflows of hot air w h i c h have the negative consequence of increasing the a m p l i t u d e
of
environmental changes. If costs were neglected, and the floor heating system were continually kept into operation for the whole season, in theory the whole room, walls and ceiling w o u l d reach equilibrium and the problem would be easily solved, at least for the well-being
27 of people, but such a practice is not completely safe for conservation. An example of that was found in the refectory of the Leonard's Last Supper, Milan (Camuffo and Bernardi, 1991a), with a terracotta floor heating. The air, heated from below, was continually mixed by convective motions which led to a heavy deposition of suspended particles and blackening of the painting. The blackening occurred at a so high rate that the restorations works were interrupted for a certain time waiting for an improvement of the ambiental conditions. This obliged tO apply a number of mitigative measures, e.g. to insulate the ceiling to reduce the source of instability aloft, and to forbidden the local traffic which was an important source of soot. However, returning to the problems connected with the heating system, although the floor temperature was kept as low and homogeneous as possible, the temperature distribution inside the room was often characterised by a strong gradient determined by the penetration of w a r m air from the nearby room, where the heating was planned at a higher level for custodians and visitors (as already seen in Fig.l.4). In the general case, the floor heating, which generates air mixing and blackening, is not recommendable in the case of historical buildings with painted walls or ceilings, and exhibits should exposed appropriately protected into show cases. However, although it is not recommendable, in certain cases it might be accepted, with a very soft use, in order to avoid also worse heating systems. A very common system, which is preferred for its low cost, is the hot air heating. Violent airflows of hot air are injected before the people entrance, and are stopped when the people go out. The airflow partially mixes with the indoor atmosphere, generating a wide spectrum of air temperature: hot air forced by its buoyancy reaches the ceiling and forms there a hot layer; on the other hand the dense, cold air originally present" in the room accumulates near the floor; finally, air parcels having intermediate densities find their level of equilibrium, resulting in a strong atmospheric layering. For instance, in a small mediaeval church in the Alps at 1140 m above sea level, in order to reach a benefit of a few degrees rise at the pew level (i.e. 5 ~ at 1 m), a rise of more than 20~
is attained at 3 m and 25~
at 4 m
(Fig.1.11a). These impressive temperature changes in turn generate dramatic drops of relative humidity (Fig.1.11b) with the consequence of forcing internal stress to the canvas paintings and wood statues, which will undergo thermal expansion and moisture shrinking that will destroy the wood artwork in a short time. In addition, the forced inflow generates great atmospheric mixing in the environment with the result of an increased deposition rate of the candle smoke which sticks the cold walls with paintings and frescoes. This is one of the worst heating methods. A mitigative intervention would be to mix vertically air with fans in order to
28 30
rO
25
o
20 r~
15 10
0
10
20
30
40
50
60
40
50
60
T i m e (hr)
90 80 ,.~
,1-1
70
~ i,,,,,i
t~
6o
~
50
9,-, r~
40
~
30 20 0
10
20
30
Time
(hr)
Fig.1.11 (a) Sudden heating and cooling, and strong atmospheric layering, generated by a hot air heating system inside the Church of Rocca Pietore, Italian Alps. The indoor air temperature measurements were taken at the heights 1, 2, 3, 4 m. The measurement at I m is evidenced with a thick line, followed by the others with maximum temperature increasing with height. The values monitored at 3 and 4 m are very similar. The figure reports data from 24 to 26 December 1996, and the peaks correspond to the heating for the Eve and Christmas celebrations. (b) Relative humidity variations caused by the above temperature changes at I m (thick line) and 4 m (thin line).
29 destroy the thermal layering. This would reduce the dramatic temperature rise aloft with the associate humidity drop, but would increase the deposition rate of particles on the surfaces. In order to reduce the room turbulence, the fan can be inserted into a vertical tube, with the lower opening near the floor and the upper near the ceiling. This mounting will generate turbulence only near the two ends of the tube, i.e. in the zones of convergence and divergence of the forced flow. An also worse system, that was especially widespread years ago, was the use of mantle stoves, which burned liquid gas. The chemical reaction of the liquid gas with the atmospheric oxygen generated carbon dioxide and water vapour. In addition to the effects of the hot air discussed above, the most negative consequence originated by the combustion was the enormous production of moisture. Only a small fraction of it was visible when condensed on the cold windows forming rivulets of water, but the main part was absorbed by the porous surfaces of walls and decorations, condensing into the micropores, weakening the stuccoes, shrinking the wood, fading the tissues, favouring the microbial decay and so on. From the above examples it is evident that it is not easy to combine h u m a n comfort, conservation needs and low costs, and that a compromise is required, where the conservation needs should dominate in proportion with the importance of the cultural heritage and the building use. For instance, it could be said that the choice of the microclimate in a museum, which should be aimed at conservation, and where m a n y important items are concentrated, should be more rigorous than in a church which is more oriented to people use. It is also clear that every system presents a number of negative aspects, some of which may have a major impact in certain circumstances, or minor one in others. It this thus important to carry out a careful pros and cons analysis and choose, time by time, the system that provokes the minimum damage. Sometimes a combination of different systems might be considered in order to avoid the excessive impact of specific adverse factors; e.g. in a mountain church the combination of a radiant floor with an electrical pew heating might reach an acceptable comfort with a modest ambient perturbation, and might be better than the more common solution of a radiant floor heating associated with hot air inflows. A general comment, on the ground of the above negative examples, is that it might be preferable to reduce interventions to a m i n i m u m level, in order to also reduce negative effects to a minimum level. It can be argued that many objects have survived till today just because the modern heating was not yet invented and now it constitutes a new challenge. This is true in several cases; nevertheless, it is also possible to use this modern technology to improve natural negative situations, as e.g.
30 w h e n a room temperature is below the dew point and condensation forms everywhere. The conclusion is that heating systems should be installed by experienced engineers, but under the strict directives of experts in conservation science; afterwards, also the use of these thermo-technical devices should be managed under the strict control of experts in conservation. The real problem is that the conservation needs are too often disregarded.
1.8.
MONITORING
AIR
TEMPERATURE
TO
STUDY
AIR-SURFACE
INTERACTIONS AND FOR MICROCLIMATE DIAGNOSTICS The use of a thermohygrograph sited in a corner of a room is very common, but this instrument furnishes data representative only of the point where the sensor is located, not of the whole room, which is generally characterised by spatial gradients continually variable, with fast or slow rates. When the heating or cooling systems are turned on/off, they provoke an abrupt change of temperature, which in general reach few degrees C (Fig.1.12). These frequent and dangerous step changes, when are relatively modest, pass nearly unobserved in the thermograph strip chart records, whose resolution is generally +0.5 ~ or +1~
in that they are smoothed out by the
friction of the pen on the strip chart, or the loose mechanical coupling. Electronic records which are much more accurate and are not affected by mechanical friction, show m u c h better this situation which is c o m m o n to all the most important m u s e u m s and also worse in other situations. Mechanical strip chart recorders can only monitor important changes, as e.g. those induced by hot air heaters, which in the extreme case of churches heated once a week, generate impressive temperature rises,~e.g. 20~ in one or two hours. Measurements of the air temperature and humidity distribution, taken in many points in proximity of surfaces or in horizontal cross sections of rooms, can be used as a diagnostic tool to individuate the air-walls interactions, the causes of microclimate perturbation, the space gradients, the exchanges of heat, the path of the air masses, some deposition mechanisms. Comparing subsequent sections, it is also possible follow the temporal evolution. It is practically impracticable to disseminate a large number of sensors in a room, each having a wire connected with the data logger for two reasons: the wires will form and entangled spider's web in which people cannot move; not all the sensors will exactly have the same transfer function or calibration, and the instrumental response departures will be interpreted as microclimate anomalies.
31 22
20
r"
v
I..i
18
I.,4
~16
T(3)~
[.-, 14
T(O.05)
12
I
I
I
0
I
I
3
I
l
6
9
I
I
I
I
l
I
12
Time
I
I
I
15
l
I
I
18
I
I
21
24
(hr)
30
? t=1
29
I..i
28 [.-
27
9
0
9
I
3
.
9
I
6
.
,
I
9
|
9
I
9
12
,
I
15
|
|
I
18
9
|
I
21
,
.
24
Time (h) Fig.1.12 (a) Abrupt rise and drop of temperature in winter (18 February 1997), w h e n the heating system is turned on in the morning and off in the evening. Measurements respectively taken at 0.05, 1, 2, 3 m from the floor. During the daytime the air is well mixed above 2 m, and the temperture is the same. (b) In summer (11 August 1992), similar step changes are generated by the air conditioning system, but the air is well mixed and the curves at the different heights are practically indistinguishable. For this reason only one has been reported. The Pollaiolo and the Giotto rooms, Uffizi Gallery, Florence.
32 The monitoring is better made moving the same fast-response instrument along a chosen regular grid with points close to the walls as well as inside the room. Repetiting in time these runs, also the time evolution of the temperature distribution is obtained. The method is very effective and has been originally devised for the diagnostic of indoor environments (Camuffo, 1983), in order to find risk areas, causes and effects, and has been applied in many circumstances either indoors or outdoors (Camuffo and Schenal, 1982; Bernardi et al., 1985; 1995a,b; Camuffo, 1986; 1991; 1994; Camuffo and Bernardi, 1988; 1991a,b; 1993; 1995a,b; 1996; 1997). As it is essential to avoid intercalibration errors, the same fast-response instrument is used, i.e. a precision electronic psychrometer (Chapter 11). The spacing between measuring points and hence the number of observations is conditioned by the size of the room and the rate of ambient change. It is essential that in the time employed for the observations the ambient conditions do not change too much. An
uncertainty principle holds:
the greater the spatial resolution, the larger the number of
observation, the longer the time elapsed and the less representative the whole monitoring. In several cases some 40 observations have represented a reasonable compromise solution. The series of measurements can be repeated every 2 or 3 hours d u r i n g the daytime. During the night-time the whole ambient system relaxes without violent perturbing factors, and all the gradients tend to flatten or disappear. The intervals between consecutive measurements can be therefore increased. Ideally, the first observation should be made near sunrise, to monitor the less perturbed situation; then the next observation should be made during the cleaning time, when the windows are open; then two or three hours later and so on, in order to arrive at the end of the visiting time; after the museum closure a few observations are needed. In practice, security reasons limit the possibility of doing measurement outside the m u s e u m business time; fortunately the most important situations are found during the business time. All the cross sections must be monitored exactly following the same order, for two reasons: (i) first of all because if there is a time-lag effect in the monitoring, it repeats identically in all the distributions, and for each point the interval between two successive readings is exactly the same; (ii) then because it is less easy to do errors, and the data must be filed with the same order in the computer. It is also important to repeat for some days the measurements for two reasons: the former is to see whether the results are repetitive, and really representative of the seasonal situation; the latter is that small variations can be found, and their repetition helps to distinguish regular trends from casual fluctuations, i.e. small repetitive variations are not casual.
33 The grid of the measuring points in the horizontal plane is composed of two interconnected series of data: a first series of points at the same height, measured at regular intervals close to the walls, i.e. at 2 mm and at 20 cm from the walls, in order to detect the existing gradients and the exchanges of heat and vapour; the second series (always at the same height) is aimed to show the temperature and humidity distribution inside the room, and is composed of other points, distributed following a regular grid, the points being the vertex of rectangles with the same dimension. All the observations are made exactly at the same level, although the choice of the level is not so important. The height of 1 or 1.5 m from the floor is often preferred for being comfortable for the operator and being representative for the most part of the exhibits. After the observed values of temperature (or humidity) are reported in the cross section, it is possible to use computer graphics or manual interpolation to show the space distribution of the parameter, the anomalies, the intensity and the shape of gradients. Close isolines show gradients. Closed isolines spreading like water waves contain in their centre the source of heat if the temperature value is radially decreasing, or a sink of heat if is increasing. Alternatively, they can show the zone of divergence (or convergence) of air when there is a three dimensional convective motion. In a room, isolines shaped like a tongue which begins from a door or a window show the penetration of external air masses and their path inside. Isolines parallel to the wall surface show that the wall is adsorbing heat if the temperature decreases approaching the wall, or vice-versa. In the same way a gradient of temperature is an index of transport of heat, a gradient of moisture content is an index of transport of vapour and condensation (if the minimum is at the air-surface interface) or evaporation from the surface (the maximum at the interface). Gradients of air temperature are also gradients of air density, and the lighter air gains buoyancy. A thermal minimum along a wall means that the air in contact with it is denser and sinks, a m a x i m u m means that is lighter and is rising up. Therefore, horizontal gradients of temperature may also help to interpret the dynamic state of the air inside a room, the transport and (partially) the deposition of pollutants. An example is shown in Fig.1.13 which reports two horizontal temperature distributions in the Sistine Chapel, first in the early morning when it is open for cleaning, and then a few hours after the entrance of visitors (Camuffo and Bernardi, 1986; 1995a). In the first map, the inside atmosphere was originally in equilibrium with the thick walls, but the opening of three doors (two on the top and one on the right) causes the entrance of cold air: chiefly from the door on the right. The air in the middle of the room, far from the doors, is warmer, but even more warmer is the air
34 close to the walls, which benefits of the heat released from the walls. This air gains buoyancy and forms an uprising current along the walls. This air current tends to increase the deposition rate of airborne pollutants via inertial impaction
(see
Chapter 8), although the positive gradient of temperature tends to partially to counteract it. In the second map, the external atmospheric warming, the presence of visitors and the energy released by the lamps have changed the situation: the air is now w a r m e r than the walls, and a heat island is formed in the central part of the room, where the visitors stay longer. The gradients near the walls are now negative and the heat flows from the air to the walls. The air in proximity of the walls becomes denser and sinks forming a downwards current. The deposition rate is now increased as the negative temperature gradient generates a thermophoretic transport whose effect is added to the contribution of the inertial impaction.
Fig.1.13 Air temperature (~ in a horizontal cross section of the Sistine Chapel when it is opened for cleaning (a) and after the entrance of visitors (b). (7 May 1983, after Camuffo and Bernardi, 1986, reprinted by permission of the Boltettino dei Musei e Gallerie Pontificie).
35 The same method can be applied to investigate the vertical distribution of the air temperature. An example with three different situations found in summer in the Giotto Chapel, Padova, is shown in Fig.1.14 (Camuffo and Schenal, 1982; Camuffo, 1983). In the early morning, when the door is open for cleaning, cold external air enters through the door and fills the lower part of the room up to the height of the door. Above this cold layer, the warm (and less dense) air which was before inside the building remains entrapped there, opposing that new air enters and fills the volume above the height of the door. The isolines are not horizontal, being tilted by the dynamic effect of the external air mass which is entering the room transporting momentum and inducing oscillations in the cold layer. At mid morning, the external air which enters through the door and goes out through some windows in the apse, has a temperature (and a density) which is intermediate between the tongue of cold air which extends from the northern apse as far as the middle nave and the warm air layer which is entrapped below the ceiling. After noon, the solar radiation through the three mullioned window on the facade hits the floor in the front part of the nave, and also heat is released from the hot door. The front part of the nave has the same temperature along the vertical, showing a continuous mixing of the air in the homogeneous region. However, the part of the Chapel near the apse remains unaffected by this perturbation and there the air is thermally stratified (horizontal isotherms), showing a transition zone (curved i s o t h e r m s ) i n the middle of the Chapel. The more vertical the isolines, the more intense the mixing. Sometimes the architectonic features of the rooms are more complicated or the situation is apparently more complex. An interesting example (Fig.1.15) is found in the Cour Marly, Louvre Museum, Paris, which was obtained by closing with a glass roof a courtyard, and the floor is divided into three levels connected with stairs. The top level (on the left) is C shaped and embraces part of the middle level floor; this is Y shaped and surrounds the rectangular bottom level (on the right). Summer air conditioning is accomplished with violent flows of air ejected out of long linear slits sited at the edges of the floor and suction is made with other horizontal slits on walls. The high speed of the airflow facilitates the mixing with the ambient air up to a distance of a few metres from the slits. In addition to the cold air injected by the floor slits, cold air conditioned from some exhibition rooms which face the top level, enters the Cour through open windows and doors. The cold air tends to descend to the lower levels of the Cour flowing along the staircases and jumping over the parapets of the upper floors, and is sucked out by the intake slits. At the bottom level of the Cour, four doors allow free air exchanges between the Cour and the corridor which is connected with the entrance hall. When the corridor is colder, cold air enters
36
24.1
23.7
25.1
26.2
/
/
26.0
Fig.1.14 Vertical cross sections of the Giotto Chapel, in the summertime. (a) In the early morning (8 a.m., the 9 July 1977) cold air penetrates through the door and above the cold layer the warm air remains entrapped. (b) At mid-morning (11.30 a.m., the 8 July 1977) external air penetrates through the door, and has a density intermediate between the cold tongue near the floor on the apse, and the warm air entrapped aloft. (c) In the early afternoon (14.25, the 9 July 1977), the hot floor generates mixing and isothermy in the front part of the nave; after a transition zone in the middle of the Chapel the air in the apse remains unaffected and thermally stratified. (After Camuffo and Schenal, 1982, reprinted by permission of the Bollettino d'Arte).
37 the Cour Marly and forms a cold lake of stable air in the lowest part of the Cour, which is in front of the four doors. When the corridor is warmer (as in this example), the hot air enters, gains buoyancy and rises immediately, forming an uprising flow. This w a r m current rises up to it is stopped at a certain height by w a r m e r air layer stratified below the hot glass roof, or by the roof itself. Whatever is the level aloft where the vertical motion stops, at that level the air flow changes direction and diverges without loosing momentum: it becomes horizontal, crosses the Cour and other colder air sinks, closing the cellar motion. The warmer air found at the bottom layer and the colder one on the top is an index of a very unbalanced situation, and shows that the air is continually moving to reach an equilibrium which is impossible to attain until the forcing factors remain active. In addition, in summer, when the sun is higher on the horizon and solar beams can reach the edge of the floors, hot spots are found which generate a secondary local uprising flow.
21.5
21.9
4-, 21.5
4--
:o' ~ oOoq.
22,3
Fig.1.15 Air temperature (~ measured above each of the three levels of the Cour Marly, Louvre Museum, the 11 August 1993. Hot air enters at the bottom level through the four doors (airflow indicated with arrows) which lead to the entrance hall of the Museum. The hot air rises immediately forming a convective, rotating motion with descent of colder air on the opposite side. Cold air penetrates also through the windows and doors of the exhibition rooms faced to the top floor level, in the opposite side (on the left). The uprising 'bubble' of hot air entering from the four doors (evidenced with arrows) at the bottom level is evidenced with shading.
38 1.9. DRAWING AIR TEMPERATURE AND OTHER ISOLINES Three-dimensional computer graphics give a very elegant visual presentation, but less useful for diagnostic purposes, as several details are masked by the perspective view (Fig.1.16). Two-dimensional maps are much more convenient, as they show with great detail and without distortion the actual distribution and the existing gradients. Computer graphics have been developed to interpolate linearly, quadratically, or with more complex functions, the values between pairs of points.
Fig.1.16 Three-dimensional representation of the temperature distribution at the Sainsbury Centre for Visual Art, Norwich, U.K. (the 9 December 1996 at 16.30, shown in Fig.l.7), and projection of the contour levels in a horizontal plane, which furnishes the two-dimensional diagram. Several details of the 3-D representation are masked by the perspective view. However, this software can be satisfactorily used for a single room with a simple geometry, e.g. a rectangle, but is still unable to well represent the temperature distribution in a complex array of rooms which constitute the floor of a building. In fact, all the data are interpolated in the same way either in the free air or across walls, so that the interpolation is exactly the same for areas in the same room or including walls and different rooms, without considering that the heat flow by advection through an open door is different from the conductive flow across a wall. Computer graphics have not yet reached the level of sophistication which is necessary to equalise the quality of hand drawn isolines in complex architectonic systems. The reason is that this is not only a problem of mathematical interpolation, but of a
39 correct physical interpretation of the data. In the case of building temperature or humidity maps, the distribution is complicated by the presence of sources or sinks of heat or moisture, horizontal advective transports, vertical convective movements, irregular geometry of architectural structures and other perturbation factors. Careful reasoning and experience constitute the best guideline, but some basic directives can be here summarised. A beginner can proceed with successive elementary steps. The first step is to write, on the side of each grid point Ox,y the observed values V(Ox,y). After, one starts by choosing an arbitrary point Ox,y (it is convenient, however, to choose a maximum or a minimum) and drawing the segments which join this point with all the neighbouring points, e.g. the 8 points Ox-l,y-1, Ox-l,y, Ox-l,y+l, Ox,y-1, Ox,y+l, Ox+l,y-1, Ox+l,y, Ox+l,y+l in the case of a regular squared or rectangular grid. Once chosen the map resolution, i.e. the unit step from isoline to isoline (e.g. 0.1~ for air temperature T or dew point spread DPS, 1% for relative humidity RH, 0.1 g kg -1 for specific humidity SH or mixing ratio MR, 0.1 g m -3 for absolute humidity AH) all these segments are divided in equal parts which are determined by the number of times the unit step is included in the difference between the numeric values of the correspondent grid points V(Ox,y) - V(Ox-l,y-1), V(Ox,y) - V(Ox-l,y+l), and so on. For example, if V(Ox,y) = 18.3 and V(Ox-l,y-1) -- 18.7, AV=0.4 and the segment Ox,y Ox-l,y1 is divided into 4 sub-segments which are divided by the equally spaced points 18.4, 18.5 and 18.6. In this way it is possible to note at the extremes of each sub-segment all the values which have been obtained by interpolation. Continuing with this method, it is possible to interpolate the space between all the pairs of points in the grid. Joining by a line all the points having the same value, observed or interpolated, a map is obtained which corresponds to a linear interpolation. All the isolines are closed or end on the walls. This is done in a very short time by several computer programs. However, hand drawn isolines may take into account several other factors. It is possible to distribute more gradually the gradients from flat zones to more perturbed ones instead of using a rude linear interpolation. It is also possible to take into account the presence and location of heat or moisture sources or sinks (e.g. diffusion intakes or suction outlets for hot, cold, humid or dry air) and improve the detail. Even more important is to consider the dynamics of the room, with advective transport from doors or windows, and vertical convection. The dynamics is well represented with analogy to the weather maps and the representation of fronts. In the weather maps a continuity is assumed not only on the values of the parameter, but also in its first and second space derivative. This means that all the isolines and
40 their curvatures (i.e. concavity and convexity) present a progressive and coherent increase or decrease, and that all the points of greatest curvatures are distributed along a line, that in a weather map may represent a front and that has a physical meaning also in a thermal or hygrometric map. In the actual case, when external air masses with different characteristics from the inside air, can penetrate through a door and flow horizontally for a certain path, several successive isolines start from the door, and protrude inside having the m a x i m u m curvature lying on an imaginary line which is the core of the air stream. Two methods are possible: the line oriented point of view, i.e. connecting with an isoline all points having the same value, which is common in topography, and the area oriented criterion, i.e. including between two isolines the belt which has the same
values V(Ox,y) or values which fall within the upper and the lower limit represented by the two contiguous isolines. The field variability obliges to prefer the first or second criterion: line oriented is necessary with a wide range of parameter variability, e.g. climatological maps; the area oriented in the case of a little variability. For instance, if in a room the observed values range in a span of a few tenths of degree, or one degree, the area oriented method is appropriate with resolution 0.1~
if the
span is several degrees, it is practically impossible to keep the same resolution and draw so m a n y lines, and is convenient to choose a larger resolution, e.g. 0.5 ~ or 1~ In this case m a n y data fall within each class and it is preferable to use the line oriented method. The area oriented method is necessary when there are several scattered points having the same value and determining homogeneous areas: e.g. in the case of two contiguous zones characterised by the values 18.3 and 18.4, the band 18.3 includes all the points from 18.30 to 18.39 but not distinguishable because of the truncation at the first decimal, and the separation line ideally joins all the points between 18.39 and 18.40, e.g. 18.399 which of course do not appear in the graph. If we use an accurate psychrometer, whose resolution is 0.1~
but only because the display is truncated
after the first decimal digit, the precision of the transducer being of the order of 0.01~
then the number 18.3 represents any figure from 18.30 and 18.39. This shows
that all the data having the same figures on the display are only apparently identical, being truncated and being directly classified within a class of values. In any case, when a map is drawn, all the space is subdivided with vertical steps and horizontal belts. The line oriented method joins with the vertical steps the few identical values which can determine a line and leaves on the belt the m a n y values between an isoline and the next; the area oriented method groups on the same belt all the m a n y identical values which are scattered over a wider area, where the values are apparently identical, being the result of a truncation, or only slightly
41 different, but fall within the values of two contiguous isolines. The two methods are conceptually the same, if one considers that in the area criterion an isoline instead of separating two areas, ideally connects all the non existing points having a value between the two contiguous classes, as in the example of the truncation. A very practical method for beginners is to facilitate drawing with colours that evidence the maxima and the minima in the map. For example, all the maxima can be evidenced with red, and the minima with blue. All around the maxima the red colour is attenuated (i.e. the saturation of the colour is reduced) as the observed values V(Ox,y) decrease, forming concentric coloured areas with the same pencil but less and less marked. The same can be made with blue, starting from the minima, and leaving untouched the intermediate values. Drawing isolines in a coloured map becomes m u c h easier. After having sketched the first coloured draft, a better and more detailed map can be drawn with a pencil on a new paper sheet. In particular, when all the isolines have been drawn, a very good practice is to colour again the belts, using two different colours for each parameter, one for the upper part of the span of values and one for the lower, and with colour saturation decreasing from the extreme to intermediate levels. The intermediate values can remain white. The visual effect is more immediate making better understandable the microclimate, the forcing factors and the dynamics of the air masses. Finally, it might be useful to compare the practice of the rounding off of a number with that of truncating it, i.e. 16.6 becomes 17 in the first case and 16 in the second one. It is merely illusory to think that the former is more precise, as the figure 17 is in reality 17+0.5, and may indicate any number from 16.5 to 17.4, so that the span of uncertainty is 1. This is exactly the same in the case of truncation, as 16 represents any value from 16.0 to 16.9. The main consequence is that the average of a large population of r a n d o m numbers is different if the numbers are truncated or rounded off, being 0.5 lower for truncated numbers; i.e. truncation makes level to the lowest value of the last digit and rounding off makes level to the middle value of it. In the case of a map of isolines drawn following the former or the latter criterion, the distribution is absolutely the same, but the values (and the isolines) being displaced by 0.5 of the last digit.
42
CHAPTER 2
Humidity
2.1. PARTIAL PRESSURE OF THE WATER VAPOUR The popular term humidity is often used when speaking of the moisture present in the atmosphere; however it is an ambiguous, generic word. Several specific terms exist, each of them represents a different parameter useful to describe a peculiar property. The first hygrometric parameter is the partial pressure of water vapour, conventionally indicated with the letter e. Evaporating new water molecules this pressure increases to a certain limit; when reached, the n u m b e r of molecules escaping from the liquid water is equal to those returning to it from the atmosphere, establishing a dynamic equilibrium between evaporation and condensation. This limit condition is determined by the temperature T, but is irrespective of the dry air pressure according to the Dalton law of the independence of the partial pressures, i.e. the behaviour of any gas in a mechanical mixture is independent of the presence of other gasses and the total pressure is equal to the sum of the partial pressures. The state of being saturated is a characteristic of the vapour, not of the air. The saturation
pressure, also called vapour tension, esat(t), is computed by means of the empirical formula attributed to Magnus or Tetens esat(t) = esat(O) xlOat/(b+t )
(2.1)
where esat(O) = 6.11 hPa (note that in meteorology the mbar unit is more common, and 1 mbar = 1 hPa), a = 7.5, b = 237.3~
The graphical representation of this
equation is shown in Fig.2.1. In the presence of ice, the tension must be calculated with reference to the solid phase with a = 9.5, b = 265.5~
As the tension for ice is
lower than for liquid water, if the two phases coexist, the water molecules will progressively evaporate from the liquid and sublimate on the ice. This equation gives very accurate values at the usual atmospheric temperatures, but is less accurate near the boiling point, where esat(lO0) = 1013 hPa.
43 100 908070c~ v
6050403020100_~, -20
-10
0
10
20
30
40
30
40
Temperature (~ 100
10 c~
0,1 -20
-10
0
10
20
Temperature (~ Fig.2.1 Saturation pressure (esat) of the water vapour (thick line) and partial pressure (e) of the water vapour at different values of relative humidity (RH), i.e. at R H = 90, 80, 70 .... 10%. Of course the thick line is for RH = 100%. The first graph is with linear scales in order to be more immediate to non specialists and present a better resolution of the ordinary vapour partial pressures. The second graph can be better appreciated by specialists: it has the ordinate with logarithmic scale and represents more clearly the physical relationship between vapour partial pressure and air temperature. The lines are not exactly straight, and the departure shows how much the Magnus equation departs from a purely exponential function, giving a clear idea of the approximation made using a such simplified formula.
44 It can be noted that eq.(2.1) is independent of V, so every isothermal compression causes a faster condensation rate until the dynamic equilibrium is established; in the case of an isothermal expansion the evaporation continues until equilibrium; only when all the liquid is evaporated does the water partial pressure decrease, according to eq.(1.2).
2.2. DERIVATION OF THE LATENT HEATS The first law of the thermodynamics states that the increase of the specific energy U of a system that undergoes a change is equal to the mechanical equivalent of the heat absorbed Q plus the work W expended in producing the change.
(Uv-UI ) = Q + W
(2.2)
Gas
P Liq
D A
C B
i i i | |
i
i i t |
gli q
gva p
W
Fig.2.2 Thermodynamic cycle to derive the Clausius Clapeyron equation. Let us consider a liquid in equilibrium with its vapour; Vv is the specific volume V/M of the saturated vapour and Vl the specific volume of the liquid; Pv - Pl
45 are the pressures of the vapour and the liquid (please note that Pv
has been
previously indicated as esat(t), but in this context the new symbol has been introduced for uniformity with the liquid phase, and to make possible the following mathematical treatement); Uv and UI are the two specific energies U/M of the two phases. All these quantities are only functions of the temperature T of the system. In a p versus V diagram, a reversible evaporation-condensation cycle (Fig.2.2) close to the Carnot one can be applied to a sample of water. The cycle is as follows: first the system undergoes an isothermal and isobaric evaporation with increase of V, from A to B; then a little adiabatic heating by compression from T to T + dT from B to C; then an isothermal and isobaric condensation with decrease of V from C to D; finally a cooling by adiabatic expansion to the original state. During the vaporization, the variation of the specific energy of the system is (Uv - UI ) and the external work, negative, is W = Pv (Vv-VI ); the heat Q absorbed in this phase is the latent heat of vaporisation Lv of the liquid, i.e. Q = Lv = (Uv- UI ) + Pv (Vv-V! ).
(2.3)
For the entire cycle, the work is given by the area ABCD between the two isobaric and the two adiabatic transformations, and in the first approximation by the rectangle d W = (Vv -VI) d p . However, the Carnot efficiency is 7/= dT/T = dQ/Q = dW/Q, so that dW = Q dT/T and, combining this with the above equations dT d W - (Vv-Vl ) dp - Q T
(2.4)
i.e.
dp Q = T (Vv-VI) dT
(2.5)
By equating the two values of Q we get dpv (Uv- Ul ) + pv (Vv-VI ) = T (Vv-VI ) dT"
(2.6)
Remembering that Q = Lv the following equation is obtained: dpv Lv = T (Vv-Vl ) dT
(2.7)
46 which was deduced by Clapeyron from Carnot's theory (for this reason it is also called the Clapeyron equation) and proved by Clausius. This equation allows the computation of the value of Lv for every T when the specific volumes are k n o w n as well as the relationship between the increase of saturation pressure and T. For example, for pure water at boiling point T = 373 K and standard pressure Pv = 1013 hPa, Vv = 1674 cm 3, V1 = 1 cm 3, dpv/dT = 36.15 hPa K -1 = 3.62x104 dyne cm -2 K -1 , one obtains Lv = 2260x107 erg gq. The Clapeyron equation shows that the latent heat of vaporisation is due partly to the increase of specific energy and partly to the external work. In order to find a relationship between these two quantities it is necessary to find the ratio between W and Lv
W Pv (Vv- V1)_ P___cvdT Lv Lv - T dpv
(2.8)
and in the above conditions W / L v = 0.075. This means that the external work forms only a small part of the latent heat of vaporisation. A simple approximation of the Clapeyron formula (Fermi, 1958) is obtained by neglecting VI in comparison with Vv (the ratio of the volumes of a molar mass of water in the liquid to the gaseous state is 18:24,000 = 0.75x10 -3) and assuming t h a t the state equation (1.1) for perfect gases is still valid. Under these reasonable assumptions, the formula becomes
Lv = .Jd~vT2 dpv Pv dT
(2.9)
and in the critical case of boiling water the computed value of Lv is Lv = 547.5 cal g-l, slightly greater than the observed value Lv = 538.7 cal g-1. This difference is due to the fact that the specific volume of the saturated vapour at 100~
is less than the
value computed by means of the equation for perfect gases. For usual atmospheric temperatures this approximation is good. The above equation can be rewritten dlnpv Lv dT - . ~ v T2
(2.10)
and, if we assume Lv is constant over a wide temperature interval, this equation can
47 be solved:
Cv
(2.11)
Pv = A e x p ( - . ~ v T)
and this gives the exponential relationship between the saturation pressure and the temperature, theoretically derived. Another approximated formula (Plank, 1926) can be obtained by substituting in eq. (2.6) the formula for the specific energy, Uv = Cv T + constv where Cv is the specific heat at constant volume, which holds for perfect gases in the isothermal processes, when Q +W = 0 and is Cv = 3.~/~v = 0.331 cal g-1 K-1. If for the liquid the specific heat at constant pressure, c! = 1 cal g-1 K-l, is assumed to be constant and the external work is neglected, one gets U! = cl T +constl similar to before, and (Uv - U! ) = (Cv- c! )T. In addition, if the the specific volume of the liquid V! is neglected in comparison with that of the vapour, V v , with the help of the equation for perfect gases (1.1), the following approximations Pv ( V v - V ! ) = ,~/gv T and ( V v - V ! ) = , ~ v T/pv. can be found. By substituting these finding into eq.(2.6), it follows that
(Cv- cl )T + , ~ v
9~ v T2 dpv T +ocnst = - Pv dT
(2.12)
Multiplying both sides by dT/T 2, this equation can be integrated and one obtains Pv = A ' T (Cp-ci ) / . ~ v
A" ) exp(--T-
(2.13)
where A' and A" are positive constants, and Cp = 0.441 cal g-1 K-1 is the specific heat of the vapour at constant pressure. The exponent of T has been obtained considering that . ~ v
Cv - Cl
=
(Cp- Cv ) and, consequently, 1 + .~v
-
Cp - Cv + Cv - Cl
.JZ~v
Cp - Cl
= .~v " This is
another theoretically derived expression. Equation (2.11) can be rewritten in other forms, of wide use, as follows. 9 Lv
esat(T) = e s a t ( ( 2 7 3 K ) e x p ( ~
1
1
( 273 - T- ))
Lv
esat(T) = esat((273K) e x p ( ~ v 2732 (T- 273))
(2.14)
(2,15)
48 0.0318t
esat(T) -~ 6.11x10
(hPa)
(2.16)
where 0.0318 = (Lv/.J?~v 2732) loge (e is the Neper number 2.71828182845904...). From the above formulae the latent heats of vaporisation (or condensation) L v, fusion (or
melting) Lf, and sublimation Ls, can be derived, as follows Lv = 597.3 - 0.57 t,
Lf = 79.7 + 0.52 t,
Ls = 677- 0.05 t
(2.17)
with all the units in cal g-1. Naturally Lv + Lf = Ls.
2.3. MIXING RATIO OF DRY AIR AND WATER VAPOUR The mixing ratio w of moist air (i.e. dry air and water vapour) is the (dimensionless)
ratio of the mass of water vapour mv to the mass of dry air ma, and this ratio represents the ponderal mixture of these two gaseous substances, i.e. mv
w -ma
(g/g)
(2.18)
If e is the partial pressure of water vapour and p the atmospheric pressure, then the partial pressure of dry air is Pa = P - e, and substituting this in the equation of state for perfect gases in the form (1.2), the previous equation can be written in terms of pressure:
w
"
-
-
e .~a p-e.~v
m
e e 0.622 P - e ~0"622p
(2.19)
where 0.622 equals the ratio between the molar masses of the water and the air and, consequently, also .~/~a/.~v. It is e v i d e n t that w is i n d e p e n d e n t of the t e m p e r a t u r e T, v o l u m e V and a t m o s p h e r i c p r e s s u r e of the air parcel and r e m a i n s constant except w h e n condensation, evaporation or mixing with other air masses occur. As a consequence, w can be considered as a characteristic value, which is useful to recognise an air mass and its h y g r o m e t r i c exchanges with the environment, being invariable to either adiabatic (i.e. w i t h o u t exchange of heat) or diabatic (i.e. with exchange of heat), isobaric or non isobaric heating or cooling. For example, in the elevated air masses a
49 decrease of w gives an indication of the amount of water which has been precipitated as rainfall. This parameter, is adimensional as the natural unit is g g-l, representing the fraction of gram of vapour mixed with one gram of dry air, and might also be expressed in percent; however, as the numeric value of w is very small, it is common to multiply this number by 1000 and use the practical unit M R = 1000 w, expressed in g kg -1, which represents the number of grams of vapour mixed with one kilogram of dry air. A plot of this parameter is shown in Fig.2.3. As the atmospheric pressure p is fairly constant (i.e. +4%), a common approximation is to write 1000 hPa instead of p, which simplifies the calculations. At every environmental temperature T the M R increases proportionally to the mass of vapour that is emitted into the atmosphere, until the saturation limit is reached, i.e. when the vapour pressure e equals the upper value esat(t), given by the Magnus eq.(2.1), and the relative humidity RH = 100%. Under saturation conditions, the M R is indicated by MRsat and is computed by means of eq.(2.14), using esat(t) instead of e (for a quantitative evaluation of the error, see the psychrometric chart). Again, as for every T, e is proportional to RH, measuring RH it is possible to calculate MR., i.e. w h e n esat(t) is computed, the saturation value M Rsat is obtained using
eq.(2.14), and the actual M R is: M R = RH x MRsat. By dividing the graph of MRsat versus temperature into fractional parts, one obtains graphically the values of M R at different values of RH. The parameter MRsat is an increasing function of T, with a trend similar to that of esat(t). At usual meteorological conditions, M R <_30 g kg -1. When two different air masses mix together, the final value of the M R depends upon the relative proportion of mixing, and it can be calculated as a weighted mean, i.e. mixing x grams of air having mixing ratio MRx with y grams of air having mixing ratio MRy the resulting M R is
MR =
x MRx +y MRy 9 x +y
(2.20)
In meteorology, this parameter is used to distinguish different air masses, e.g. to evidence the change between the land (dryer) or sea (moister) breeze, or to monitor the evapotranspiration of the soil, or the evaporation over large water bodies. A quantitative evaluation can be made by measuring the vertical gradient of this p a r a m e t e r and the exchange coefficient for the vertical transport in the atmosphere. Similarly, in the conservation science, this parameter can be used to recognise a number of important features and interactions.
50 80 70 60 bO
50
bib "~
40
"~
30 20 10
O-l~ -10
-20
0
10
20
30
40
50
Temperature (~ 1 O0
10bO b~
0,1
/ -20
,
!
-10
|
!
0
|
!
10
~
i
20
|
!
30
|
!
40
|
50
Temperature (~ Fig.2.3 Saturation mixing ratio (MR, thick line) of the vapour in air and actual value of the mixing ratio at different values of relative h u m i d i t y (RH), i.e. at RH = 90, 80, 70 .... 10%. Of course the thick line is for RH = 100%. As in Fig.2.1, the first g r a p h is with linear scales and the second has the ordinate with logarithmic scale.
51 2.4. M O N I T O R I N G MIXING RATIO TO STUDY AIR-SURFACE INTERACTIONS A N D FOR ENVIRONMENTAL DIAGNOSTICS This p a r a m e t e r is very useful for diagnostic purposes, to provide evidence of the action of HVAC systems or air-surface interactions. By m e a s u r i n g this p a r a m e t e r along a horizontal cross section of a room, it is possible to see the advection of external air p e n e t r a t i n g t h r o u g h open (or t h r o u g h fissures of) doors or w i n d o w s (Fig.2.4), or the moisture released by visitors, or where the walls are evaporating or adsorbing moisture. The effects of humidifiers are also pointed out, as they do not generate a h o m o g e n e o u s increase of v a p o u r content, but a cloud of moist air which m a y d a m a g e objects in proximity, or moves into the room along the advective currents b e t w e e n adjacent rooms. A very common, but inappropriate position for a humidifier is near corners or walls where works of art are placed.
5,
,6
Fig.2.4 Mixing ratio (g/kg) in a horizontal cross section of the Giotto Room in the Uffizi Gallery, Florence, showing the penetration of external air masses evidenced with shading (1 February 1993, 4 p.m.). Sometimes the air coming from elsewhere is only a bit different and can be observed as a useful tracer of different air masses. In this case, the emission of moisture in the different rooms is not balanced in comparison with the size and needs of each room. Therefore, the air coming through doors or the vertical slits which have been opened for the passage of paintings, has very different hygrometric characteristics and may perturb the exhibits causing internal stresses. H u m i d i f i e r s generate clouds of moisture which grow in this sheltered space (Fig.2.5). Then these clouds diffuse into the room, or are displaced by local air currents, or are b r o k e n and t r a n s p o r t e d in several directions by the turbulence generated by the motion of visitors. Works of art are alternatively i m m e r s e d into, or emerge from these clouds, or portions of them. The result is a continuous stress and
52
"~ . . . . . . . . 51.7
""~"ii'~i'~i~..!::!ii'..i.i~i."~
53.8
~
9 @
~
~
~
16
~ . ~
8.4
Fig.2.5 Micro-mapping in a horizontal cross section of the Salon CarrY, Louvre Museum, Paris, showing clouds of moisture (evidenced with shading) diffusing into the room, which are generated by humidifiers. Four active humidifiers are placed in corners of the room. Others are in stand-by position. This situation is here described by means of three parameters, in order to gain familiarity with different representations, i.e.: (a) relative humidity (RH, %); (b) mixing ratio (MR, g/kg); (c) dew point spread (DPS, ~ The clouds of moisture appear as local maxima of RH or MR, and minima of DPS. (21 February 1995).
53 fatigue which leads to weakening, microfessuring and flaking the outermost layer or the colour coating. A more appropriate position is far from the exhibits, in the central part of the room, either on the floor (e.g. Kunsthistorishes Museum, Vienna or Uffizi Gallery, Botticelli room) or the ceiling, although the latter position presents a further problem: the suction outlets placed on the lower part of walls d e t e r m i n e a preferential p a t h of the m o i s t u r e into the room, and a non h o m o g e n e o u s distribution. Gradients of the M R close to a surface show that the surface is exchanging vapour with the atmosphere. If the surface is evaporating, the air is locally enriched with water molecules and the M R locally increases; on the other hand, if the surface is adsorbing water molecules or is condensing, the air in proximity to it is depleted of water molecules and the M R locally decreases. Monitoring this parameter near walls directly lighted by solar radiation or artificial lamps, a release of moisture can be seen for a short time during heating, and it stops w h e n the plaster becomes in equilibrium with the hot spots (Fig.2.6).
11,8
11.6
Fig.2.6 Mixing ratio (g/kg) in a vertical cross section in front of the Leonard's Last Supper (Milan) showing the local release of vapour from the area hit by direct artificial lighting (29 July 1982, after Camuffo and Bernardi, 1991). The vapour which is escaped from the wall causes a local enrichment of MR in the air nearby, i.e. the maximum found in the upper part of the wall, on the left. This evaporation is forced by the switching on of the lamps. The radiant energy warms the surface and forces the evaporation. When the equilibrium is reached in the micropores, the evaporation stops and the maximum disappears after a short time.
54 The opposite occurs when the wall cools again after the input of radiant energy has stopped. Daily cycles of direct lighting, which always repeat the same effect on the same areas, may cause severe damages on delicate objects able to adsorb water and change their dimension accordingly. If a cold surface is put in contact with the environmental atmosphere, initially the air in contact with the surface decreases its temperature T, and the M R remains unchanged. This leads RH to rise. As soon as the condensation begins, the M R starts to decrease, and this tends to invert the trend of RH. After some time, the air in the proximity of the surface will be characterised by AMR < 0, and nothing can be said about the final value of RH, which is subjected to two counteracting effects due to T and MR. In general, the thermal effect prevails and ARH > 0. When a wall is hit by direct solar radiation it warms (AT > 0), evaporates (zkMR > 0) and the opposite situation occurs. These obvious facts appear as a paradox w h e n i m p r o p e r l y described: the air is dryer in proximity of a surface where condensation is occurring and more moist near an evaporating surface. This paradox derives from the fact that 'more dry' or 'more moist' are not specified in terms of MR, and people generally associate the concept of dry and moist with that of relative humidity RH which will be analysed later. From the definition, the air is dry or humid in terms of MR as a consequence of its water vapour content only, independently of the temperature T of the system; in terms of R H it means how close the vapour is to saturation, and this depends upon two factors: T and MR. A 'dry' air parcel in terms of MR becomes 'humid' in terms of RH when it is sufficiently cooled; one 'moist' in terms of MR becomes 'dry' in terms of RH when sufficiently warmed.
2.5. SPECIFIC HUMIDITY The specific humidity s of moist air is the (dimensionless) ratio of the mass of water vapour mv to the mass of moist air ma+mv, and this ratio represents the ponderal dilution of the vapour in the atmosphere, i.e. my
s - ma+m--------~
(g/g)
(2.21)
It is also called mass concentration or moisture content of moist air. Substituting eq. (2.21) into (2.18),
55 W S
1+w
t"."z)
and, operating similarly to (2.19)" e
S
0.622 p - 0.378 e
e
0.622 p
w-.~oj
Like the mixing ratio, this parameter is adimensional, the natural unit being g g-1. It might also be expressed in percent; however, in order to avoid the use of small decimal numbers, the practical unit S H = 1000 s, expressed in g kg -1, has been introduced. This represents the n u m b e r of grams of v a p o u r dispersed in one kilogram of moist air. In practice, it can be observed that in the d e n o m i n a t o r of eq.(2.22) w < < l and is therefore negligible; similarly in eq.(2.23) 0.378e can be neglected in comparison with p. As a consequence, the values of w and M R are very similar to s and SH respectively, with differences of the order of 1%. The same properties of the M R can be extended to the SH and the saturation specific humidity
SHsat; also the same graphical representation can be used in a first approximation. Both M R and SH are conservative for adiabatic or diabatic changes of temperature, pressure or volume but are not conservative for evaporation or condensation, as changes of mv are involved.
2.6. ABSOLUTE HUMIDITY The equation of state (1.1) for the water vapour can be written in the form mv~
e = V .... v T = a . J 2 ~ v T
(2.24)
by defining absolute h u m i d i t y a the density of the water vapour, i.e. the mass of vapour contained in the unit volume of moist air mv
a = -~-
(2.25)
From this definition it follows that a is variable with m v, i.e. condensation, evaporation, mixing with other air masses, as well as V, i.e. compression or
56 expansion, d u e to e.g. changing atmospheric pressure or height; from eq. (2.24) it is also e v i d e n t that a is directly p r o p o r t i o n a l to e and inversely p r o p o r t i o n a l to air temperature. Of course, a is e x p r e s s e d in g cm -3, but in o r d e r to avoid the use of small d e c i m a l n u m b e r s , the practical unit A H = 106 a, e x p r e s s e d in g m -3, has b e e n introduced. A H represents the mass of v a p o u r contained in 1 m 3 of moist air. As at s t a n d a r d p r e s s u r e and t e m p e r a t u r e , 1 m 3 of a t m o s p h e r e contains the mass of 1.255 kg of air, the values of A H are numerically similar, but always greater than those of M R or SH. In fact, M R and S H represent the mass of v a p o u r contained in I kg of dry
or moist air, which occupies some 80% of I m 3. The absolute h u m i d i t y can be c o m p u t e d by means of the equation of state (2.24) by considering that the v a p o u r density is the inverse of the specific v o l u m e Vv, i.e. 1
1
e
1
e
a - V v - .~/~v T -.~/?~v 273 (1+ at )
w h e r e the last term comes from the transformation from K to ~
(2.26) i.e. T = 273 (l+c~t)
w h e r e c~ = 1/273 - 0.00366. D e p e n d i n g u p o n the units in which e is expressed, the formula to c o m p u t e A H a s s u m e s one of the following forms. If e is in hPa or mbar (more usual), e
e
1
1+o~t
A H = 220 ; = 0.806 ~ =
0.806e
(2.27)
If e is in d y n e cm-2: e
e
1
l+ott
A H '-- 0.22 ; = 0.806x10 - 3 ~
= 0.806x10 -3 e
(2.28)
or, if e is in m m Hg: e
e
1
1 +o~t
A H = 290 ~ = 1.062 - - =
e
(2.29)
The latter s h o w s that at t = 16.4~ the A H is numerically equal to e m e a s u r e d in m m Hg; at usual meteorological values of t, these two parameters (in the above units) are numerically similar. Using the saturation value esat(t) instead of e, the saturation absolute h u m i d i t y
5? 100
80
~E~
60
,<
40
20
0-~" -20
-10
0
10
20
30
40
50
30
40
50
T e m p e r a t u r e (~
100
10 b~
1
0,1 -20
-10
0
10
20
T e m p e r a t u r e (~
Fig.2.7 Saturation absolute humidity (AH, thick line) and actual values of A H at different levels of relative humidity (RH), i.e. R H = 90, 80, 70 .... 10%. Of course the thick line is for R H = 100%.
58
AHsat is obtained (Fig.2.7). This represents the maximum quantity of vapour that the unit volume of atmosphere can deliver under specified temperature conditions; for this reason it is also called (moisture) capacity. From the above formulae it appears that AHsat is a function of air temperature but not of pressure; in the case of adiabatic compression or expansion the change of AHsat is governed by the change of t (although induced by the change of p), according to the Poisson equation. The value of AHsat allows the computation of the quantity of the liquid that may evaporate or the quantity of vapour which condenses during an adiabatic transformation. As in the previous cases, and the actual AH is: AH = RH x AHsat. By dividing the graph of AHsat versus temperature in fractional parts, the values of AH at different values of RH are graphically obtained.
2.7. RELATIVE HUMIDITY It is useful to state beforehand that in meteorology, for practical purposes, the convention is used of attributing all the properties of the atmosphere to one fictitious gas, called 'air' which behaves as the mixture of the gases and vapours which form the atmosphere. In order to describe particular phenomena, a distinction is made between dry air and moist air. The adjective dry may have two meanings, which are clarified by the context: the former is literal, i.e. without vapour, the latter without
condensation, i.e. the mixture behaves as an ideal gas, without changes of phase; similarly, moist indicates the opposite of these two situations. Under this point of view, the vapour component is formally ignored and it is improperly expressed in terms of relative humidity of the air or degree of saturation of the air instead of the correct form: relative humidity and degree of saturation of the vapour. From the physical point of view, it is meaningless to speak in terms of saturation in the case of a mixing of two (or more) gases, as they are absolutely miscible from 0 to 100%, according to the Dalton law. The saturation arises because one of the components is not a gas but a vapour, and all vapours become saturated when their partial pressure reaches the limiting value determined by the ambient temperature, called saturation tension. In the case of water vapour, this is given by the Magnus formula. It is independent of the presence of other gases and their pressure, and the definition of relative humidity is the same in the presence of air or in absence of it (e.g. for some vapour in a vessel deprived of air). The relative humidity u (popularly termed humidity) was originally defined
59
u =~ esat(t)
(2.30)
i.e. the (non-dimensional) ratio between the actual partial pressure of the vapour and its
saturation vapour pressure. Below 0~
the saturation value esat(t) is c o n v e n t i o n a l l y
c o m p u t e d w i t h refernce to s u p e r c o o l e d water, or to ice if the t e m p e r a t u r e is far below 0~
and this fact introduces ambiguity. The above definition is not any more
rigorous w h e n the s a t u r a t i o n is a p p r o a c h e d . In fact, in this condition the v a p o u r d e p a r t s from the b e h a v i o u r of a perfect gas, in that s o m e m o l e c u l e s a g g r e g a t e f o r m i n g small clusters; the actual n u m b e r of free particles n w h i c h describe the e q u a t i o n of state decreases as well as the partial p r e s s u r e e. N e a r saturation, the partial pressure of a v a p o u r departs from the ideal condition and another unaffected p r o p e r t y should be used. In order to avoid the above problem, the definition of u has been reformulated in t e r m s of the mass mv of the v a p o u r c o n t a i n e d in the air parcel, w h i c h is a conservative property, by substituting e = ( m v / V ) . ~ v T and esat(t) = (mv, sat/V).~/~v T, w h e r e mv, sat is the mass of w a t e r v a p o u r p r e s e n t u n d e r saturation. The relative
h u m i d i t y u is then defined as the (non-dimensional) ratio between the mass of vapour mv actually present in whatever volume of atmosphere, to the greatest amount possible at the same temperature mv, sat, i.e. my
u =~ mv, sat
(2.31)
a n d p h y s i c a l l y r e p r e s e n t s the degree of saturation of the vapour. F r o m the a b o v e definitions it is easy to recognise that
mv mv mv e mv Wv ma av W Sv ma +my u - - - - -esat(t) mv,sat Wv,sat my, sat av,sat my, sat Sv,sat mv, sat ma V ma+ mv,sat
(2.32)
a n d it d e p e n d s u p o n both the a m o u n t of m o i s t u r e w h i c h is actually p r e s e n t mv (to w h i c h it is p r o p o r t i o n a l ) a n d the t e m p e r a t u r e t, w h i c h acts e x p o n e n t i a l l y in the d e n o m i n a t o r mv,sat. The d e p e n d e n c e of u on t is very strong, and at the first sight the d i a g r a m s of u and t seem to be nearly symmetric, as reflecting in a mirror. As u varies b e t w e e n 0 and 1, in order to avoid the use of decimal n u m b e r s , the practical unit R H in p e r c e n t a g e form is used, i.e. RH = 100u. W i t h the help of
60 eq.(2.19), eq.(2.32) and the Magnus equation, it is possible to obtain practical formulae to compute the M R or SH from measurements of t and RH: M R ~-SH ~ 37.95 R H xlO at/'b+t~ P
e = 0.0611RH xlO at/(b+t )
AH =
13.44RH xlO at/(b+t ) 273.3 + t
) 0.03795RH xlO "t/(b+7t'
)
(g/kg)
(2.33)
(hPa)
(2.34)
(g/m3)
(2.35)
The R H can be measured directly (e.g. hair hygrometer) or indirectly. In the following, a very accurate method for the determination of the RH will be described, based on the measure of T and the wet bulb depression; by substituting R H in the above formulae, the values of M R , e and A H can be calculated. It is customary to compute eq.(2.33), eq.(2.34), and eq.(2.35) with the Magnus coefficients a = 7.5 and b = 237.3~ referred to (supercooled) water also when t < 0~ This convention is partially justified as, in mild climates and daytime, ice is covered with a film of liquid water. However, when the wet bulb temperature is below the freezing point, and the sensor is covered with ice, the appropriate coefficient for ice should be used. Climatology requires average values. It might be useful to underline that relative humidity is a parameter derived from other elementary physical variables, e.g. mixing ratio or vapour pressure which is proportional to it, and air temperature. The equations that link the R H to the basic parameters are not linear, and for this reason a mean value obtained as the arithmetic average of a set of R H observations is not physically correct. Mixing two air masses with different R H values, the R H of the final mixture is not the arithmetic average of the two initial R H values, but is determined by the final temperature and mixing ratio. The 24-hour or the monthly averages should be computed after the averages of mixing ratio (or vapour pressure) and air temperature. The common use is to sacrifice correctness to convenience and data are handled in terms of averages; however, in this field the most correct statistical form is to abandon averages and to present data in term of percentiles, which are based on frequency distribution. This parameter constitutes a very useful tool for environmental diagnostic and risk assessment, and the methodology is the same that has been already described for air temperature and mixing ratio.
61
2.8. THE EQUILIBRIUM MOISTURE CONTENT Several materials (e.g. wood, paper, parchment, leather, ivory, bone, paintings, plaster, stucco, stones containing abundant clay minerals) are very sensitive to their water content, and this is in equilibrium with the RH. In materials science a concept similar to the mixing ratio is used in defining the equilibrium moisture content, EMC, i.e. the mass of water per unit mass of anhydrous material. The water molecules can be adsorbed, as in m a n y organic (e.g. wood, paper, parchment, soap) and some inorganic materials, or can be transformed into hydration or crystallisation water, as in some inorganic salts (e.g. sodium sulphate, copper sulphate, barium chloride). The EMC is generally expressed in percent and varies with ambient temperature and relative humidity. It is nearly zero for non porous, non hygroscopic materials; for other materials it vanishes only at zero relative humidity. In some inorganic (e.g. clay minerals) and m a n y natural organic materials, microclimate changes lead to vary the EMC and, consequently, the size of the object. W h e n the deformation is not isotropic, three deformations should be considered. In the case of wood which is characterised by a fibrous structure, the three key directions are: (i) tangent to the tree growing rings, (ii) radial i.e. from the centre of a cross section of a trunk to the exterior, (iii) longitudinal, or parallel to the grain, i.e. along the direction of the trunk. Anisotropic deformations generated by changes of temperature and humidity result in strain and strain-induced stresses. They force internal tensions, deformation, fatigue and often fractures. C o m m o n effects are configurational strain (warping, cupping, bowing etc. or fracture (checking, splitting). The EMC of fresh wood is 30% or more, and for well seasoned wood at ordinary temperature and humidity falls to values typically ranging between 7 and 20%, although important departures can be found for changes of RH. The dependence of wood EMC upon temperature and relative humidity is shown in Fig.2.8, where it is evident that wood is weakly sensitive to a temperature change, but very sensible to humidity changes, especially in moist environments, i.e. for RH > 80%. In the humidity range 10% < RH <70% the plot is a straight line, and at room temperature (i.e. T = 20~
the EMC of the experimental values found by Giordano
(1993) for Italy obey in average to the equation EMC = 5.9 R H - 4.7
(2.36)
but the coefficients may vary with the wood species, seasoning and temperature.
62 35 ,.~
30
o
25
~
20
T = 20~
o
0~
T =
9~
]0
.~..i
T= 40~
.v,=l
~
5 i
a
I
I
l
I
I
I
I
I
0
10
20
30
40
50
60
70
80
90
100
Relative H u m i d i t y (%)
Fig.2.8 Dependence of w o o d equilibrium moisture content (EMC) u p o n ambient temperature (T) and relative humidity (RH). It is evident that wood is very sensible to humidity changes, especially in moist environments. 7 6
5 ~
o r~
r,j
4-
"-,
3
o o
|
0
,
,
|
i
5
,
',
|
,
!
10
,
|
,
|
I
15
,
|
|
|
20
E q u i l i b r i u m M o i s t u r e C o n t e n t (%)
Fig.2.9 Wood size change, expressed as percent of the reference size at EMC = 20%, for oak (thick line) and pine (thin line), and for the two main axes, i.e. the tangential (continuous line) and the radial (broken line) ones. The tangential change is about twice the radial one.
63 When the ambient relative humidity falls, also the EMC drops and the wood shrinks, or vice-versa, with important deformations. For practical purposes, in the EMC range between 0 and 20%, the relationship may be assumed to be linear
(Summit and Slicker, 1980). The shrinkage, expressed as percent of the reference size at EMC = 20%, is shown in Fig.2.9 for two wood species, i.e. oak and pine, and for the two main shrinkage axes: the direction tangent to the tree rings and the radial one. These two figures can be combined in order to express the wood contraction (or expansion) versus the equilibrium relative humidity, and Fig.2.10 shows the response of an aged wood (with initial EMC = 20%) to ambient humidity changes: the w o o d expands in d a m p environments, but severely contracts in drying, especially w h e n this happens with abrupt changes, e.g. originated by s u d d e n warming of hot air heating systems. They may lead to dramatic results in only one or a few cold seasons.
Oak tang
Pine tang ,~-
4
Oak rad 0 r~
I=
3
Pine r a ~ 2
o
1
o
0
0
-1 -2 -8 -4
0
20
40
60
80
100
Relative Humidity (%) Fig.2.10 Wood size change, expressed as percent versus the equilibrium relative humidity (RH). Initial conditions at EMC = 20%. Lines refer to oak (thick line) and pine (thin line), and for the two main axes, i.e. the tangential (continuous line) and the radial ones (broken line). The tangential change is about twice the radial one.
64 From the above figures it is evident that the tangential change is greater than the radial one, and both are greater than the longitudinal one. These coefficients often follow the proportion 1: 1/2: 1/3. The most important expansion or contraction of roof timbers is the longitudinal one, which fortunately is also the smallest one, but the considerable length of the timbers may induce large changes of size. It should be noted that any rise of temperature induces a thermal expansion but also a drop in RH and, consequently, a drop in the EMC and a wood contraction, and vice-versa. By the way, the thermal expansion and the EMC contraction are opposed, so that the shrinkage is partially mitigated by the expansion. However, the shrinkage due to RH changes is largely dominant. Any unbalance caused by the heating, the air conditioning system, or the humidifiers generates severe damage in panels, frames, furniture and so on. Also gradients may generate diffrential expansions in wood structures, which can undergo severe stress and damage (Fig.2.11).
51
56
~
~:
::
...... .~.~i!i~i~i~~il ~i!i~-i-.--i~l~ .~ .t~ . -.~ .....
Fig.2.11 Relative humidity (RH, %) in a horizontal cross section of the Historic Anatomy Theatre of the University of Padova (3 July 1992, 5 p.m.). The most humid corner has been shaded.
2.9. MECHANISMS OF HUMIDITY DEGRADATION It is well known that high humidity levels increase the deterioration rates in several ways. A list of some of the most important phenomena recurrent in conservation has been reported by Thomson (1986), or can be found in special
65 studies. In order to clarify the action operated by moisture, it is useful to summarise some key mechanisms of water into a material; others will be seen in the following. The presence of liquid water favour chemical reactions: the transformation of marble or limestone into gypsum is probably the most popular example (for an extensive discussion of this mechanism see Laurenzi Tabasso and Marabelli, 1992). Gypsum is mainly formed in heterogeneous phase on the monument surface when, in the presence of a film of liquid water, the absorbed sulphur dioxide (SO2) as a primary pollutant is first converted into sulphurous acid (H2SO3) a n d / o r sulphuric acid (H2SO4). The oxidation of S(4) into S(5) is favoured by the presrence of 03, NOx and catalysts such as metals or soot; the reaction with the calcium carbonate (i.e. calcite, CaCO3) forms directly, or as a final product, the hydrated crystal of calcium sulphate, i.e. gypsum (CaSO4-2H20). The chemical reaction is more straight when atmospheric SO2 is dissolved and oxidised to suphuric acid into rain droplets (acid rain), or sulphate aerosols deposit on the marble or limestone surface and, in the presence of water, they are transformed into sulphuric acid and gypsum. Stones, bricks, pottery, plasters, frescoes and other materials having water soluble salts in the pores are sensitive to microclimate changes. Environmental conditions leading to cycles of RH may generate crystallisation and dissolution of salts by means of two key mechanisms: (i) the water evaporation, which is controlled by ambient RH, causes a concentration of the solute, supersaturation and precipitation of salt crystals; (ii) hygroscopic salts, which are in crystalline form only in a dry environment, become deliquescent or precipitate following the ambient RH cycles. These mechanisms generate cumulative mechanical damage, efflorescences, subflorescences, delamination, spalling, flaking etc. Corrosion (Jones, 1996) is the destructive result of a chemical reaction between a metal and its environment, and therefore includes also oxidation which is the first form of metal decay. Metallic corrosion involves transfer of electronic charges in aqueous solutions. For this reason, in presence of water, metals tend to combine with other chemical compounds, and return in a form similar to the natural minerals from which they are extracted, making free the energy required for their extraction. For glass (Newton and Davison, 1989) the situation is complex, as there are several types of glass and deterioration mechanisms. Chemical solutions (and the pH of the attacking solution) may provoke chemical changes on the surface, which may then spread to the whole of the glass. Water originated by condensation or arrived with rainfall, or simply by vapour adsorption, is necessary for the replacement by protons of the diffusing alkali ions and subsequent hydration of the silica network. Water molecules may diffuse inside the glass leaching tiny cracks by acting on
66 sodium and potassium carbonates which are deliquescent and causing ion exchange and alkali extraction. In dry condition, or under the action of solar radiation, the loss of the water absorbed causes dehydration. For this reason humidity cycles are dangerous, also in the absence of pollution. Wood and paper microfibrils (Coped6, 1991; Richardson, 1993) are mainly composed of cellulose chains which are formed from glucose molecules. Each glucose unit possesses three hydroxyl groups which have an affinity for water. When water is absorbed, it will retained between the cellulose chains, displacing them with the first consequence of increasing the size of the material and decreasing its strength for the attenuation of the hydrogen bounds and van der Waals intermolecular forces. The second consequence is that a slow but progressive hydrolysis of cellulose is produced, which breaks the bounds between the glucose units, breaking the cellulose chain into a number of shorter and weaker chains, with a depolymerisation mechanism. The third consequence is oxidation, or chemical degradation, especially in modern paper (i.e. after mid 19th century) which is made from wood pulp and contains several acidic elements. The damage is particularly severe in the presence of atmospheric pollutants and especially ozone. In addition, when paper is stored in a humid environment, it releases sulphuric acid that accelerates the deterioration. The last, but not least, consequence of dampness is biodeterioration. Not only dampness, but also dryness affects the molecular structure. Paper has a structure which is weaker compared to wood and is more sensitive to humidity changes. Moderate cold and dry is better for storage and conservation, but makes paper brittle. Moderate humidity causes the absorption of a number of water molecules which ensure mobility to the cellulose chains, increasing flexibility and this environmental condition is better for use. Therefore, when a book is consulted, it should pass from a cold, dry storage, to an intermediate transition climate, and then to the reading room which should be moister to made paper more elastic and warmer, and to be more comfortable for the reader. For this reason, the choice of the R H may change according to the use. Different humidity limits can be found
suggested in literature, e.g. the interval 45 to 65% RH. Similarly, also the collagen in parchment is arranged with chains of molecules with problems similar to those discussed for cellulose in paper, and extreme dry or wet may irreversibly alter the structural composition. Water can also be absorbed by textiles (cotton, linens, wool and silk) weakening the material and fading their colours. For all materials the microclimate should be especially chosen in order to reduce or eliminate the risk of biologic attack by fungi, bacteria or other parasites.
67 For example, algae and cyanobacteria need high RH, fungi generally prefer RH > 65%, but in already contaminated materials it should be considered that, due to the humidity conserving biofilm, the microorganisms will survive or even act at humidity levels > 50%. High levels of RH, especially when associated with T > 20~ favour biological rotting especially in the case of organic materials whose composition is appreciated by parasites or may offer a good substratum for the development of microbiological life. Besides RH and T, the intensity of microbial attack is basically controlled by the structure and chemistry of the respective substrate (e.g. porosity, inner surface, biosusceptibility of the material) and is secondly determined by air pollution levels (e.g. salts and organic materials) as well as further environmental conditions (e.g. ventilation, light, pH and redoxpotential) (Warscheid and Kuroczkin, 1997). It is should be considered that microflora lives at the interface between a solid substrate and the air: these two media may have a different temperature and moisture content, e.g. with water being adsorbed or trapped into pores. In certain cases, the dynamic situation generated by daily cycles which are transmitted with a phase delay in the two media, may lead to the fortunate circumstance that microorganisms may benefit alternatively from one or the other medium, so that considering only the physical characteristics of the air is analysing only a part of the problem. As far as the atmospheric part is concerned, the appropriate environmental conditions should be carefully chosen as a whole, including not only RH and T, but also ventilation and turbulence (which regulate the deposition and removal of spores), light, pH, air pollution levels, and the relevance of each of these factors may change in the case of indoor or outdoor environments. For instance, in the past when the air pollution was modest, lichens colonised many monuments especially in the Mediterranean belt, where solar radiation and rainfall were most appropriate and many lichens can still found in rather unpolluted zones of Portugal, Spain, Italy, Greece and so on. Later, when the SO2 and sulphates reached elevated levels, the atmosphere became toxic for them, and they disappeared from most cities, leaving on stone monuments typical signs of their past presence, e.g. pitting, oxalates. However, the microflora of stones represents a complex and highly adaptable ecosystem, metabolising inorganic and organic substrates from natural or anthropogenic sources. Because of their metabolic flexibility and remarkable tolerance against osmotic stress (e.g. salts) or toxic compounds, air pollution might cause considerable shifts in the composition of the stone colonising microflora, but will hardly control or stop biodeterioration processes.
68 2.10. WHAT IS THE BEST TYPE OF MICROCLIMATE FOR CONSERVATION? It has been clearly seen that some humidity levels are often associated with specific deterioration mechanisms, or may accelerate them. The water molecules which are absorbed into the material may determine internal stress a n d some deformation to the structure; the amount of absorbed water (and therefore internal stress and deformation) is in equilibrium with the RH and also, to a lesser extent, with T. These deformations tend to be reversible in plastic, new materials, but irreversible and extremely dangerous in aged materials. This is a good reason for suggesting some allowed or non-allowed microclimate conditions. For the materials most frequently used in creating works of art, some recommended values (or spans) of T and RH can be found in the literature, with the aim of determining the conditions of physical well-being, suitable for an appropriate conservation. These values are recommended with the aim of taking advantage from experience, or avoiding the repetition of errors already made by other colleagues, or keeping off from dangerous situations discovered with laboratory tests. However, a fundamental question arises: are microclimate norms and guidelines always useful and should they be always followed? It is useful to underline that recommended values of T and RH which are in principle suitable for materials are not always appropriate for individual artefacts. In fact, specific artefacts which have been kept for centuries under determined T and
RH, have been subjected to internal stresses and eventually have reached a new equilibrium of internal tensions with possible (permanent) deformation of their structure. Now, an old artefact, which has adapted to its environment according to the past internal system of tensions, and has lost its initial elasticity, is unable to adapt again to a new microclimate, and any change is very dangerous. This is a well known problem for wood conservation and when archaeological terracotta or glass is dug up to light. For this reason, an accurate knowledge of the past conditions is needed, and the previous microclimate should be kept untouched, or modified towards a new equilibrium very slowly and with extreme care, only in the case of real need. In addition, once these objects have adapted to some specific values of RH and T, they need very steady conditions as every fluctuation of these parameters works against the durability of the object. For this reason, all the abrupt changes are dangerous (it is common that archaeological pottery breaks when removed from u n d e r g r o u n d due to environmental shock) as well as the daily cycles of these microclimatic parameters. The daily cycles are repetitive and the effect of the stress is
69 of cumulative nature, and soon or later causes mechanical damage (fatigue failure). Seasonal changes, although they have a wider span, are less dangerous, as they occur more slowly, in a time much longer than the relaxation time of the object and with a rate slower than the penetration of heat and moisture in the material, so that there is no significant stress between the external layer and the interior. However, also these changes may be dangerous in the case of non homogeneous materials. It is evident that a furniture, or also a panel built with wood slabs constrained between them and having grains differently oriented, will undergo important internal stress when an element shrinks in a different way. It is obvious that for 'rigid' hygroscopic materials, e.g. aged wood or ivory, need a very constant microclimate, and the risk associated with a rapid change of the physical environment is greater than for more elastic or deformable materials, e.g. paper, parchment, tissues. However, the difference between materials and objects is often substantial: e.g. an old book with paper sheets and parchment cover, bound together with wire, is composed of parts that cannot expand or contract freely, so that microclimate cycles that are harmless to the individual components, may lead rapidly to severe damage of the object. When an object is not irreversibly conditioned by its past microclimate, and it is possible to choose the most appropriate conditions for preservation, these can be found by means of its adsorption isotherm (see Chapter 5). The goal is to avoid the intervals of RH where a small change of RH causes a great change of adsorbed water and to keep the object in one of the intervals where changes of RH do not affect (too much) the amount of adsorbed water and do not provoke new internal tensions. However, it is not always true that the best choice is the one indicated by the physical analysis of the material. In fact, if the experimentally determined 'best' interval is far from the natural local conditions, it might be better to choose a naturally stable microclimate than an artificial one, which is conditioned by the good functioning of complex devices. On this ground, Thomson (1986) suggested 60% RH for m u s e u m in Great Britain, and this value was deduced from the mean natural climatic values of that country. Similarly, in order to avoid shocks to the objects, the National Gallery, London, for reasons of continuity kept the standard 55%, which was the RH value in equilibrium with the moisture content in wood preserved in the Gallery prior the installation of an air conditioning (Padfield, 1994). These values have been acritically transferred to other natural climatic contexts. It is not common to find papers w h o criticise (as Padfield correctly did) the acritical use of microclimate normative or standards, some of them are widely used in everyday practice although without having been scientifically demonstrated.
?0 2.11.
KEEPING
CONSTANT
RELATIVE
HUMIDITY
IN
ROOMS
AND
SHOWCASES Relative humidity is of primary importance in the problem of conservation of works of art, and in exhibition rooms should be kept both homogeneous in space and constant in time. However, in practice several variations exist and dramatic changes occur, especially in the morning when windows and doors are opened d u r i n g cleaning, or when the heating system is switched on. In several cases humidifiers are introduced to mitigate or compensate the effect of the temperature change, but this system is never well balanced and hardly successful (Fig.2.12). Air conditioning systems and humidifiers cause repetitive 'ocal variations which are very dangerous. Active devices which create artificial microclimates are unable to ensure a very homogeneous distribution of the moisture and are very dangerous especially when bad functioning or power supply interruptions cause failure of the system. It is evident that the clouds of moisture generated by humidifiers displaced in rooms produce local perturbations also in terms of RH, with the effects that have been previously discussed.
80
-
t
RH(1)
"~" 7 0 RH(3)
.
~
60
~
50
40 0
3
6
9
12 Time
15
18
21
24
(hr)
Fig.2.12 Change in relative humidity at 1 and 3 m above the floor, i.e. RH(1) and RH(3), when the heating system and the compensating humidifiers are operating during the visiting time (for the temperature change see Fig. 1.13a). The humidifiers are too much powerful and, instead of mitigating the dry air, the net result is a moistening. The Pollaiolo room, Uffizi Gallery, Florence, 18 Febuary 1997.
71 Different systems to control the relative humidity are popularly used. For instance, in the Uffizi Gallery, Florence, a number of different systems can be found and they give the opportunity of very interesting comparisons, as follows. The Giotto room has a system which is based on controlled air introduced from grille diffusers sited in the ceiling above the Madonna d'Ognissanti by Giotto; as an equal flow is removed by intake slits on the wall near the floor level, this system generates a preferential path for the controlled air masses which cross the room and partially mix with the room air. For this reason this system is integrated with some traditional box humidifiers close to the walls. The result is a non homogeneous distribution of the humidity inside the room, and in particular in the summertime the cold flow of air conditioned falls just on the Giotto's painting (Fig.2.13). The Leonard room has a more sophisticated system which is based on the emission aloft of treated air released from line sources, i.e. four pipes hung to the ceiling, which lie parallel to the walls, but at a certain distance, so that the cold air falls far from paintings. In principle, this system is preferable, as the emission is not from a few points but is distributed from lines, and far from the exhibits. However, the treated air is transported by the depression generated by intake slits on the wall near the floor level, and by air currents exixting between a room and another. Although the system is good in principle for a single room, the overall result in the context of a buildings, where rooms are interconnected and air masses are transported from a room to another by internal temperature or pressure differences, the result (Fig.2.14) is not very satisfactory and practically not better than the simpler system in the Giotto room (Bernardi and Camuffo, 1995a). A number of rooms has box humidifiers sited close to walls and paintings, following an incorrect, dangerous practice very frequently found in museums and galleries. More appropriately, the Botticelli room has some humidifiers located in the centre of the room, far from paintings. Also very sophisticated automatic systems which control the ambient relative humidity keeping it in a span between two determined, relatively close, levels, cause continuous fluctuations between the lower and the upper levels (Fig.2.15). Although the range of variability lies within a few percent and the period is relatively short, so that the wave of the hygric perturbation cannot reach deep layers on artefacts, all of these repeated cycles have a very negative impact, especially on objects with small thickness, e.g. canvas paintings. It is easy to imagine the tremendous consequences that hot air heating systems have in churches heated once a week. In the example shown before for the church at Rocca Pietore, Italian Alps (Fig.1.11), the rise of temperature found at I m height, i.e. AT = 7~
causes a humidity drop ARH = 10%; the temperature rise found at 3 and 4
72
~///////////~'////////////////A
~
~'/////////~
5 8______ . 57
Fig.2.13 Relative humidity in the Giotto Room, Uffizi Gallery, Florence. In the hot season, the cold air conditioned released through diffusers in the ceiling, falls generating a perturbed zone. 12 August 1992 at 12.00. 'G' shows where the Giotto's panel is located.
~ ~ / /// / / / / / / / / / / / / / / ~ 62
I, 63
8
~////////////////////~
Fig.2.14 Relative humidity in the.Leonard Room, Uffizi Gallery, Florence. In the hot season, the sophisticated air conditioning system releases treated air from an extended source below the ceiling, but also this system is unable to guarantee ideal conditions. 13 August 1992 at 18.20. 'L' shows where the Leonard's panel is located.
73 m, i.e. AT = 20~
causes a dramatic humidity drop A R H = 50%, so that canvas
paintings, tablets and wood artefacts will contract and shrink, as we have already discussed.
In the long run, the repetition of these cycles has t r e m e n d o u s
consequences. 50 48 46
44 42 40
!
0
I
2
!
I
4
!
I
6
!
I
8
!
I
10
!
I
!
12
I
14
!
I
16
!
I
18
!
I
20
!
I
22
i
24
Time (h)
Fig.2.15. Fluctuations in relative humidity (RH) generated by a sophisticated controlling system, which controls this variable within two stated limits, i.e. the span 45 < RH < 50%. (Private Gallery of Modern Paintings, Parma, February 1996).
Some porous or fibrous materials characterised by large heat capacity maintain constant both T and RH: e.g. a thick wall tends to keep a constant microclimate in its proximity, and paintings hung to it or statues in niches benefit from these conditions; wooden boxes protect small objects against sudden changes of RH. One of the most effective materials, widely used in showcases, is the silica gel, characterised by many fine pores and therefore extremely adsorbent. This material smoothes out abrupt changes of RH, but does not ensure steady, pre-determined conditions. Silica gel is often pre-conditioned at some desired R H levels by keeping it for a sufficient long time at a determined humidity level until equilibrium is reached. At this point the silica gel behaves as a buffering agent, i.e. if the R H drops it will desorb moisture, and if R H rises it will absorb moisture in order to offset changes. However, the silica gel slowly adapts to the new average environmental conditions and the buffering level changes in a rather incontrolled way, so that it is necessary to change often the silica gel in the case with other silica gel, just conditioned at the desired level. This makes complex the management of the case. In addition, the amount of silica gel necessary for good conservation of exhibits in show cases has been calculated to be
74
25 kg per m 3 of air to control (Thomson, 1986). This figure shows clearly that it is e x t r e m e l y difficult to preserve objects at constant R H avoiding fluctuations, disturbances or slow changes. Whenever possible, it is advisable to improve the natural microclimate with the help of all the passive systems which ensure the best stability and reliability. A good method to maintain constant the RH at a desired level inside an airtight case, is to place in the bottom of the case a vessel containing a super-saturated solution of pure water with an excess of a certain solid substance which is in equilibrium with a specific value of RH, a number of these substances being listed in Chapter 11. These super-saturated solutions are characterised by a constant, typical vapour pressure and, consequently, by a constant value of RH. If the R H inside the case lowers, some water evaporates from the vessel to re-establish the equilibrium and, vice-versa, some vapour condenses in the solution if the inside R H increases. The choice can be extended to a large number of buffered RH levels, of course by choosing chemical substances that are not noxious to the exhibits. Sometimes showcases have a humidity level which is controlled by a micro climate generator which adjusts the RH by adding or removing moisture as required. The treated air is continually circulated between the case and the m o i s t u r e controlling unit. The RH sensor which is in the case drives in the control unit a feedback of moisture exchanges and the treatment stops when the desired RH level is reached. If the whole system, i.e. the case and the control unit have exactly the same temperature, there is a good probability that the desired RH is reached in average, i.e. w i t h several dangerous fluctuations around the mean level. H o w e v e r , if temperature differences are found in the system, although the mixing ratio is exactly the same, the relative h u m i d i t y will present d e p a r t u r e s and the r e q u i r e d homogeneity is lost. This happens normally for several reasons, e.g. the case and the control unit m a y have a different temperature, or the exhibit is heated by the lighting system, or the case has not exactly the same temperature everywhere because the most lighted panes w a r m the air near to them or the hot air accumulates in the top part of the box leading to an internal temperature stratification. These active systems are not fully reliable, need continuous control, are rather expensive and expose the works to the risk of dangerous departures in the case of bad control or work.
2.12. DEW POINT: THE TEMPERATURE OF CONDENSATION The dew point temperature, commonly termed dew point, DP is the temperature
75 to which a parcel of moist air must be cooled at constant pressure and constant water vapour content in order for saturation to occur. It can be alternatively defined as the temperature at which the actual pressure of the vapour contained in an air parcel equals the saturation pressure, under constant pressure and mixing ratio. Although it is popularly called dew point of the 'air', it is a property of the vapour that might be extended to the 'air parcel', i.e. the little mass of mixture of dry air and vapour taken into consideration.
From the definition it is a conservative property of the air parcel with respect to isobaric heating or cooling without addition or subtraction of vapour. It is non conservative with respect to adiabatic expansion or compression. Of course, in a completely dry atmosphere there is no any temperature at which water can condense and this parameter does not make sense. This parameter can be easily computed from the relative humidity and air temperature, starting from the consideration that the dew point is reached with an isobaric process, so that the vapour pressure at the original dry bulb temperature equals the saturation pressure at dew point, i.e. e(T) = esat(DP). By substituting this finding in the formula (2.20), one obtains with the help of the Magnus formula: aDP/(b+DP) e(t) esat(DP) esat(O)xl0 [aDP/(b+DP)] - [at/(b+t)] u - esat(t) - esat(t) = at/(b+t ) = 10 esat(O) xl0
(2.37)
hence aDP at logu = b + DP" b + t
(2.38)
and
DP-
b + DP
a
b + DP at b +t logu + ----a--- b +------t--~ logu + t
(2.39)
where the last approximate finding has been obtained substituting t to DP in the right hand side of the first identity. Of course, the first term is negative as u < 1 and logu < 0. Another formula can be deduced considering an air mass over an evaporating surface. The air temperature lowers, while the increase of mixing ratio raises the DP. The air temperature t continues to drop to the temperature of the evaporating surface, called wet bulb temperature, tw, is reached. When the vapour evaporated causes saturation, t = tw. Starting from the Clapeyron equation and the definition of
76 w, and always considering the difference D P - t w , after some laborious steps and approximations the following formula is obtained:
b logu+t logu+at D P = b -al~ - -b l o g u - t ~ gu
(2.40)
where a and b are the Magnus coefficients for vapour in equilibrium with the liquid phase. The eq.(2.39) is a better approximation. The above formulae can be used once the R H is known, and obviously logu = log(RH/lO0) = logRH- 2. The D P < T and D P = T only when R H = 100%. The D P is determined once the air temperature T and the R H are both known, or also when only the M R (or S H or A H ) is known. In particular, maxima of M R correspond to minima of D P and vice-
versa, so that the D P can be used for diagnostic purposes instead of the MR. The d e w p o i n t s p r e a d (also called spread), i.e. the difference A D P = T - D P basically depends upon both the actual air temperature T and the M R . Following the approximation (2.39) it can be expressed as a function of air temperature and relative humidity b+t A D P -- - ----a- logu.
(2.41)
It physically shows how much the air temperature is close to, or far from, the DP. The zones having the smaller A D P are more prone to form condensation and to allow micro biological life and weathering to occur. Useful maps of this parameter can be easily done for diagnostic purposes. However, although the R H is a very different, but related parameter, the areas with maximum R H are the same as those in which the A D P is minimum, and if the critical cooling is not requested, maps of R H are sufficient to give a qualitative description of these micro climatic problems. The d e w has the typical form of droplets and especially forms on leaves during the nocturnal cooling due to the IR emission. The formation of dew on leaves is favoured by the local excess of moisture due to the stomatal transpiration. The surface tension of water tends to displace the larger droplets on the edges of the leaves and in particular on the points of leaves, especially the lance-shaped ones. The u p w a r d IR loss during clear nights is a very effective cooling mechanism. The surfaces on which dew forms are free from any upper shield, and in practice are the same as those which are wet by rainfall. This is the reason that people often believe that dew falls similarly to the drizzle. If a non porous surface cools until it reaches the DP, the environmental vapour
77 begins to condense onto it, forming films of liquid water or droplets. A well known example is the condensation on the window panes during winter, especially in rooms with an elevated M R due to the presence of people, w h e n the glass conductivity cools below the DP the pane surface. Another important example of the same principle, is the condensation which typically occurs in spring in the Mediterranean region, when the air becomes mild and rich of moisture (i.e. with an elevated DP), and especially when the w a r m and humid Sirocco wind blows. Historic buildings have thick walls with high heat capacity and a large thermal inertia, whose temperature keeps a memory of the past cold season. The contrast between the elevated DP of the air, and the low temperature of the thick walls which remain below the DP, causes heavy condensation on the surface (Fig.2.16). If the surface is porous, the effects of the surface tension can favour condensation in the micropores also at temperatures above the DP, as we will see in Chapter 5. For this reason, in spring, thick walls of non heated buildings are very frequently damp. As the dew forms on all the surfaces whose temperature drops below the DP, irrespective of the environmental value of the RH, it is completely useless to insufflate the surface of cold walls or monuments with heated air, which has a lower RH but the same MR and, therefore, the same DP. Due to the large thermal inertia of these structures, the ventilation brings in contact with the cold surface a greater amount of air and vapour, thus increasing the condensation rate. This method was originally proposed by Massari (1959; 1971; 1977) as the windscreen effect, considering the analogy with the method used by cars to remove the misting of the windscreen. However, the vapour mists over the windscreen when the pane temperature T is T < DP of the air, irrespective of the RH of the airflow, but eventually the internal surface of the pane, which is poorly conductive and needs a relatively little amount of heat to warm, rises its temperature above the DP. At this point condensation stops and the misting evaporates. A nice example that the surface condensation is independent of the air temperature is given by a stainless steel pot, half filled with cold water, when this is put over the methane fire. Although the flames lick the pot, the cold pot is immediately covered with dew. A few seconds later, the droplets disappear from the upper half of the pot (i.e. the part which is empty and has a lower thermal capacity) when it is warmed above the DP. The droplets in the lower half of the pot, which is filled of water and has a greater heat capacity, disappear simultaneously several seconds later, when also the water inside the pot is warmed over the DP. For this reason, in some specific cases, condensation on limited surfaces can be eliminated either increasing the surface temperature, e.g. with IR radiation or direct warming, or diminishing the environmental MR. Some results can be also reached by
"/8
Fig.2.16 In spring, the contrast between the air rich of moisture (i.e. with an elevated DP), and the low temperature (below the DP) of the thick walls, causes heavy condensation on the surface, which is damp and fully covered with droplets. In this picture, taken in a room of Castel del Monte (Southern Italy), the 27 March 1996, when the surface is perpendicular to the flash light, the light crosses the droplets which are transparent and invisible, but when the surface is nearly parallel, the light undergoes a multiple reflection inside droplets which appear brilliant, with a silver like appearance. The red colour on the white part of the marble columns is a biopatina.
79 impregnating the surface with hydrorepellent substances which increase the contact angle 0 of the water droplets, as we will see in Chapter 5.
2.13. FROST POINT: THE TEMPERATURE OF FREEZING The frost point FP is defined in the same way as the dew point, but reference is made to ice and in the eq.s (2.39) and (2.40) the Magnus coefficients are a = 9.5 and b = 265.5~
From these equations it follows that FP < T and FP = T only when RH =
100%. In addition, FP - 0~ only in the case that at this temperature RH = 100%. In general, the frost forms at a temperature below 0~
which depends u p o n the
moisture content of the air. The frost (also called hoar, hoar frost, crystalline frost, white frost) is generated by the direct sublimation of the vapour, which forms needle-shaped crystals of ice. It is different from the frozen dew (also called white dew, silver frost) which has the appearance of ice spherules. Similarly to dew, the frost also prevalently covers the horizontal surfaces that loose heat by IR radiation toward the clear sky. Different is soft rime, which is due to the rapid freezing of very small supercooled water droplets in fog or cloud when they impact on (prevalently) vertical surfaces with temperature below 0~
In this way windborne droplets stick
forming a dendritic accretion, and all the trees are white on the side facing the wind, and iceless on the opposite side. The ice is white, porous, and is constituted of very small granules separated by few or many air inclusions. Similar to soft rime, but formed with drizzle droplets of micronic size, is hard rime. In the case that the concretion of ice has been generated by ice needles already formed in the atmosphere, this phenomenon is known as advection hoar frost (or also ice fog, frozen fog, frost fog, air hoar, rime fog). If the drops splashing on the cold surface are even larger, i.e. rain drops, the coating is more homogeneous and translucent, known as glaze (or also glazed frost, clear ice or ground ice for the soil). The windborne droplets and the splashing from them may cover surfaces differently oriented and the branches of trees may break due to excessive weight of the ice.
2.14. WET BULB TEMPERATURE: THE TEMPERATURE OF EVAPORATION The w e t bulb temperature Tw (or tw) or isobaric wet bulb temperature, is the
80
temperature an air parcel would have if cooled adiabatically to saturation at constant pressure by evaporation of water into it, all latent heat being supplied by the parcel. This temperature is directly measured by the wet bulb of a psychrometer, or can be obtained indirectly by means of a psychrometric diagram or formulae, after the dry bulb temperature and one hygrometric value (i.e. e, MR, SH, AH, RH, DP) are known. From the thermodynamic point of view, Tw is the temperature that an air parcel would have when some liquid water is supplied gradually, in very small quantities and at the same temperature as the environmental air, and then this water is evaporated into the air adiabatically (i.e. the latent heat being supplied by the air) at constant pressure, until the saturation is reached. The saturation is reached for the combined action of two factors due to the evaporation: the increase in MR and the drop in T. Consequently, Tw is the lowest temperature that an air parcel would have by evaporating water, the latent heat being subtracted to the air and utilised for the change of state of water from liquid to vapour, until saturation is reached. Tw is also the equilibrium temperature of an evaporating surface of water. Applying the first law of the thermodynamics to an air parcel formed by 1 g of dry air with a mass of vapour mv, i.e. with mixing ratio w = mv, and experiencing the above process, Tz0
mw
f Cpm (l+ mv) d T : T
f Lvdmv
(2.42)
my
where
Cpm
is the isobaric specific heat of the moist air that can be expressed in terms
of isobaric specific heat of dry air Cpd (Cpd = 0.240 cal g-l K-1 = 1.003 Joule g-l K-l), i.e. Cpm = (1+0.8 mv)Cpd and Lv is the latent heat. After integration, by dividing both sides by (Cpd + <w> Cpv), the wet bulb depression ATw = T- Tw is obtained
ATw
(msat,w - m v) Lv =
(2.43)
Cpd + < w > Cpv
where <w> is the average mixing ratio during this process, msat,w is the saturation mixing ratio at the temperature Tw a n d Cpv is the isobaric specific heat for the water vapour (Cpv = 1.81 Joule g-1 K-l). A further approximation of the wet bulb depression is obtained by using the formula (2.19) for w and considering that Cpd + <w> Cpv = Cpd (i.e. <w> <<1), so that the wet bulb depression becomes
81
ZlTw ~-
0.622 Lv (ew - e) Cpd P
(2.44)
where ew is the vapour pressure at Tw. This equation can be solved with successive approximations for every initial set of T, p and e. Graphic solutions are popularly used. Saturation occurs at temperature Tw for the dynamic equilibrium which follows the increase of M R due to the addition of water to the system. From the definition, Tw is conservative with reference to the evaporation of falling rain drops. In the case
of an evaporating porous surface, the evaporation rate is generally modest, so that T tends towards Tw but may not reach it, and the M R increases at the interface, generating a negative gradient of M R (i.e. M R decreasing coming away from the surface) and a positive gradient of T in the air close to the evaporating surface. In the opposite case of evaporation occurring in the internal pores of a wall, the latent heat is supplied by the wall and the air temperature remains unchanged, but the evaporation is still evidenced by the negative gradient of MR. There is an analogy between DP and Tw: both are based on isobaric cooling until saturation is reached, but the DP is reached without changing the MR. On the contrary the Tw is reached with the addition of external water which raises the M R of the air parcel, favouring saturation; for this reason the DP cannot be reached with evaporation forced by ventilation. The DP is the temperature for condensation and the Tw for evaporation and DP < Tw < T
and
ADP >_ATw > 0
(2.45)
where the identity holds only for RH = 100% when DP = Tw = T. It might be noted that in the atmosphere the saturation is usually found on foggy days, especially during night-time. In general, during fog, the RH is 95 < RH <_ 100%. During short rainfalls and showers saturation is not often reached. Summer showers may occur with very low RH, and the fallen water then evaporates in a short time. The Tw can be easily measured by means of a psychrometer, which is constituted by a couple of ventilated thermometers, i.e. a normal one (i.e. the dry bulb) and another having the bulb (i.e. the wet bulb) covered with muslin which supplies water adsorbed for capillarity from a reservoir. The air speed of the ventilation is generally between 3 and 5 m s -1 as will be discussed in Chapter 11. It is evident that, for a given temperature, the greater the M R , the greater the D P as the vapour is less
82 further from saturation. The same can be said for Tw which lies between T and DP. It is also obvious that Tw is also related to the degree of saturation of the air, in that the higher the R H the smaller the amount of water that should be evaporated to reach saturation and, consequently, the cooling ATw caused by the absorption of the latent heat for vaporisation. When the wet bulb is ventilated, it drops in temperature, and the cooling stops at the equilibrium, which is reached when the heat Qv lost by evaporation from the wet bulb e w
Qv = C Lv S ~
- e
(2.46)
P
(where C is a proportionality coefficient, Lv the latent heat of vaporisation, S the surface area of the evaporating surface, e the actual vapour pressure, ew = esat(tw) the saturation vapour pressure at the temperature of the evaporating surface and p the atmospheric pressure) equals the sensible heat Qs transferred from the ambient air to the colder wet bulb (2.47)
Qs = B S ( T - Tw)
where B is another proportionality coefficient and Tw is the wet bulb temperature. By the way, equation (2.46) is the Dalton law of evaporation. Equalling the two previous equations for the heat exchanges equilibrium, the basic psychrometric formula is obtained (2.48)
e = esat - A p ( T - Tw).
where A = ( B / C Lv) is the so-called psychrometer coefficient which is not really a constant and depends, inter alia, on the ventilation rate (see Chapter 11). Substituting in the definition (2.30) of relative humidity, e with the psychrometric formula, esat with the Magnus formula (2.1), and A = 6.667x10 -4 K -1, and dividing numerator and denominator by esat(O) = 6.11 hPa, the very useful equation is derived atw/ (b+tw) 10 - 1.09x10 -4 p (t -tw) R H = 100
at/(b+t)
(2.49)
10 which allows a precise determination of R H after measurements of t and tw and,
83 consequently, precise calculations of M R (eq.(2.33)), e (eq.(2.34)), A H (eq.(2.35)) and DP (eq.(2.28)). This equation has been reported in the form RH vs. ATw in Fig.2.17 for
some values of T. The depression ATw can be also calculated after the readings of T and DP with the following empirical formula ATw = ADP (-1.281x10 -4 t 2 + 0.01786 t + 0.3682) - 0.00889 ADP 2
(2.50)
where the dew point spread can be calculated with the eq. (2.41) in the case of known RH instead of DP. This formula is not commonly used because it obtains values that
are generally measured directly. However, meteorological services furnish the DP instead of the ATw or the RH and for this reason it is useful to calculate from the DP the basic parameters which are then used as input for other formulae.
2.15. THE PSYCHROMETRIC CHART Several thermo-hygrometric parameters can be graphically computed with the help of the psychrometric chart (Fig.2.18) as follows. 9
The abscissa is the actual air temperature T (i.e. the dry bulb temperature) and the
ordinate the MR (or the SH). 9
The vertical lines are isotherms. Ascending, the M R increases (e.g. addition of
external water, e.g. by evaporation); descending, it decreases (e.g. condensation, absorption or adsorption of vapour which is subtracted from the atmosphere; the term 'adsorption' implies the condensation of the vapour on the surface of solids). 9
The horizontal lines are isohume in terms of constant MR:. A displacement to the
right indicates a warming of the system without change in MR, a displacement to the left, a cooling, and according to our previous definition, the final point of this cooling is the DP. 9
The near exponential curve on the left is the saturation curve, and represents
simultaneously the MRsat, the RH = 100%, the DP and the Tw. 9
The (vertical) distance between each point of the saturation curve RH = 100% and
the abscissa can be divided into 100 parts. Each of them, by definition, shows the percentage of MRsat. This is the actual value of the RH of the air parcel characterised by the values of T and M R which are the co-ordinates of that point. The nearly exponential curves with RH = 10, 20, 30..., 100% are generally evidenced. These are isohumes in terms of RH.
84
i
o
o
I
.........----"""""" i
i
i
o
(%) ~4!pImnH aAIlelaX,I
.._
i
_...
--,-
0
0
|
o
o .....-
I
o
--.
o
co
CM
o
o4
o
o
~
0
.~.,~
~:~
~ 0 ~ .,--i
9,4
0
o
0 II
I
f',l
9
~ 0 0 u
~.~ ,.~
m
9 ....i
m
~.~
~
~ >
9 ..-t
~
o
r,.'~ ~ ~.
Relative H u m i d i t y (%) 100 90 80 '
'
'
I
'
I
'
J
/
Wet Bulb Temperature ( ~
/L~/
9
,,",~ / /~r / 2~.
20 !
/
/ ",~/
.,(/'/N.z" i/%d ./ ~
_
-10
0 ~ % < ! ~ X ~ ~ , / ~
_~_~~~,~---"
0
~
10
,<
X/
l O i
/
/ / T M ' 4
Dew Point (~
.
30
'' 30
"~--4 ~ ,, '/ / /' "/ A . ~'~/
t
/ -,~
z-
7'
7"_
%/ i /
/ , / /'~~<,.
-
70
'
i>~
j-~,t.~--
~,~
/'
- 20
/ /~ <.. / I'~,1"-.2 ~ / .7".,.
/- ~
/
j 4./' ,,
/~
/
,><.,,.
25
o~
=
15
~
"~ .-/
o~ ow~l
10
.~ ~-~
20
30
40
Dry Bulb T e m p e r a t u r e (~ Fig.2.18 Psychrometric chart
O0
86
9
The tilted lines, where both the T decreases and the MR increases, are
characterised by Tw = constant and are nearly isenthalpic. In fact, there is a small departure, being d r a w n for a non perfect gas. The value of T w of each thermodynamic point can be read on the saturation curve. Sometimes, the scale for enthalpy of the system is also added. It can be recalled that the enthalpy,,~ of a system in equilibrium at pressure p and temperature T is defined as
~ ( p , T)= U + pV
(2.51)
where U is the internal energy of the system and V its volume. Therefore, 4 , ~ = dQ + p dV
(2.52)
where dQ is the amount of heat gained or lost. For a process which is isobaric and
reversible = dQ;
(2.53)
and for a perfect gas (i.e. no change of state)
= Cp dT
(2.54)
the enthalpy is a function of T only, i.e. the change in enthalpy measures the heat imparted to the system. In meteorology the enthalpy is considered a synonymous of sensible heat (i.e. heat, in opposition to latent heat) as exchanges of enthalpy coincide with exchanges of heat. Indicating ~ m v the enthalpy per mole of pure water in the vapour phase, and ~ m c in the condensed phase, then
,~mv - ,.~mc = Lv
(2.55)
i.e. the molar heat of evaporation denoting the latent heat of vaporisation for one mole of the associated condensed phase. Therefore, changes of enthalpy always represent transfer of heat, either in the sensible or in the latent form. For an isolated air parcel all the processes that are simultaneously adiabatic and
isobaric are also isenthalpic. A process which is isenthalpic is also adiabatic, as well as isentropic, as the entropy 50 is thermodynamically defined as
81
.5~= ; d ~ 9
(2.56)
In fact, all these processes are characterised by dQ = 0. A process which is adiabatic but not isobaric (e.g. the upward rise of an air parcel) is by definition isentropic (i.e. dQ = 0) but not isenthalpic, due to the work done against the external pressure during the variation of the volume of the air parcel. The sum of enthalpies of the phases of a closed system is conserved in an adiabatic isobaric process. Sometimes, the isochoric lines i.e. the lines with equal specific volume are also reported, expressed in m 3 kg -1. Each point in the chart shows directly, or by interpolation, the complete thermodynamic state of the air parcel: the T, by following d o w n w a r d s the isotherm to the abscissas; the MR, by following the horizontal isohume to the ordinate; the DP, by following the same isohume to the saturation curve; the Tw, by following the iso wet-bulb line (i.e. the isenthalpic) to the saturation curve: the RH, considering on the same vertical the distance between the thermodynamic point and the abscissa and expressing it as a percentage of the whole distance between the abscissa and the saturation curve, or interpolating with the nearly exponential curves with RH = const passing close to the point. A few examples may be useful to clarify the method, first of all becoming familiar with the chart. 1) Let us consider the thermodynamic point (Fig.2.19a) characterised by t = 25~ and RH = 70%; the vertical isotherm and the curve of equal saturation 70% meet at a point where the horizontal isohume shows on the right MR = 14 g kg -1 and on the left DP = 19~
Moisture can be added isothermally to MRsat = 20 g kg -1, or
isenthalpically to MRsat = 15.75 g kg -1, and the corresponding temperature is Tw = 21~ 2) In this example (Fig.2.19b), we want to change the temperature of the air in a room, initially at t = 30~ and RH = 60% in order to arrive at 25~
but with the same
RH. A subtraction of both heat and moisture are necessary, and the moisture can be removed by condensation. The air conditioning system will cool the air; initially the cooling will occur with u n c h a n g e d M R
(i.e. 16.3 g kg -1, with a horizontal
displacement along the isohume to left); at around 21~ the DP will be reached. A further cooling will cause the thermodynamic system to follow the saturation curve RH = 100% with condensation on the refrigerating surface and subtraction of vapour from the air. The system will condense water until the moist air will reach 17~ and the M Rsat = 12 g kg -1. Removing the fraction of liquid water which has been
88 ....
I
....
I
....
I
....
I ~
~
v13o
# I I I~l.,~I 11 l 3 0 [ II ~ -
I1 'I'KI
,,4
I 25
'~' ' ~ X ~
# t / l"KJ T/Y Y lY'~/I r'/'3 .t. . K.) . / I .4 A~ . 4 12%L . 4 / J "~ on A I,a"-/4 I Z I,.,N[/I ~JAM /["4/I X lbl T /l_.,[-'~. I / ) / I " , 4 , / i 14~ ,r -II ~ 2 0 Awi zi ~. .' A % l ~ I / I ~ ? tv- . . lI/ I X " ~ I.,"-I~ Dp ~ l/ I It'.,.I I I I',1-"-'
Wet Bulb Temperature Dew Point
0 .
.
.
~
(~
.LV'-.k'P'P/-J X I",A; I IY-,I I 1 10./'I><J/I-'~I~ ~ X I'~I T ~ L _ ~ 10 E . , ' ~ > < ' v p < J . - ~ ~,<1 X ' - k [--'1 ~ I ~ . , ~ ' [ ~ v t > < l . . . - 1 - ' - > ~ l ...T<,.I ]..xl,. I I ~ t < L I ] _~L-.-"I",>2r ~ 1>4U i /I><1 i ~ I 'l'~,,,-i ~ _c><3 i>~Vl b . - e q " k / 1 q
.
~
0
0
. . . .
10
1
i
I ""-t.,.. I 3-,-.,. I 20
'
,
,
i
,
'~ 1)~
"" .~
1""--4..i
30
,
o "-
40
~-N
3O
/
301/~Z i?<-~
# , Wet Bulb Temperature
,
" /
.< Dew
y.. /
'
~
,-.
7.,
~l
(~
><(
/ K/" ~//' ,'-i J / "" AK~Z i ;.. / i~.. / .,~ I ")%.I /" N./ ><,,
Point (~
2~
~.~/x
"
"~"
x
~.
"~
/
.
_
141 15
..~~
~z(
~o
"~
[
--~ ~
. . . . . . -10
0
~
"-4
10
~,..
20
~.!
30
,
....
40
i/~.~./, 30
/ ,/
/ / ' Y K /
-_.'
/ , P
25
, 20
Wet Bulb Temperature
(~
Dew Point (~
I 'I~A"K/ / N / / . . . / . ~o% .,r...i It, ~ c... i ,"~k ,' 2( / / " M I I ? ~ I ,I" ,.. i ~'~,~'I" ~ ~< / / ~ " y.~ ,~ .~-./ /
/
,,.#'.,J" j ",..Y
~ /
/ ~
~i/ /•
.o
N. "', / N
lo 1(~><'/><./
.~.~<.-q~"
0
0
10
./"--...-"
"<"
>, "
~. "'<
20
/--,,~.. " ><-C
30
"~
o~
.~.
i~,
40
Dry Bulb Temperature (~
Fig.2.19 E x a m p l e s cited in the text. (a): Characteristics of a air parcel w i t h t = 25~ a n d RH = 70%. (b)" Thermo, d y n a m i c t r a n s f o r m a t i o n n e e d e d to cool an air m a s s initially at t = 30~ and RH = 60% to t = 25~ but w i t h the s a m e RH. (c): D r y i n g cloths in a b a t h r o o m .
89 condensed and heating the air parcel to 25~
with a horizontal displacement, the
desired temperature and humidity will be reached. 3) Suppose (Fig.2.19c) to hang out the washing in a bathroom, w h e n the external conditions are characterised by t = 0~ and fog, i.e. RH = 100%; consequently, the MR is M R = 3.8 g kg -1. The volume of the bathroom is 25 m 3 and contains the total mass 25 m3x1.255 kg m -3 = 31.4 kg of air. The external air which is penetrated into the house was heated to t = 20~
as there is no subtraction or addition of moisture, the
indoor R H is R H = 25%, i.e. very dry. At this indoor temperature the m a x i m u m allowable M R is MRsat = 14.8 g kg -1, and the amount of water that can evaporate is given by the number of kilograms of air contained in the bathroom, multiplied by the moisture capacity of each air kilogram, minus the initial moisture content, i.e. 31.4 kgx(14.8-3.8) g kg -1 = 345 g, which is a very little amount, corresponding e.g. to one sock. Heating the bathroom to 25~
the MRsat is risen to MRsat = 20 g kg -1, which
allows a further evaporation of 31.4 kgx(20-14.8) g kg q = 163 g, i.e. half a sock. This shows that the critical factor for indoor evaporation is the limited ambient volume, and little help is obtained by overheating. The washing can dry only with the windows open and exchange of the air.
9!
CHAPTER 3
Parameters for Describing Air Masses and Vertical Motions
So far we have observed the air from the Eulerian point of view, i.e. stating a stationary coordinate system linked to the soil or the architecture of a room, where the same air undergoes temperature or humidity changes, or is substituted by other air masses, and we have looked at the variation of a number of parameters in some stated points, isolated or forming a horizontal grid or a vertical profile. It is also useful to consider the thermodynamic transformation of the air masses from a mobile reference frame, which has been linked to the air mass itself, so that the fixed subject is the air, and the changing parts are the locations where the air moves. This is the Lagrangian point of view. Each of these systems presents advantages and disadvantages, and the choice of the more appropriate system depends on the specific problem. However, whatever will be the reference system, it is obvious that, when we are willing to apply a wider analysis, it is always useful to introduce new variables which are better representative of the thermodynamic state of an air mass. In fact, when an air mass is considered not only in a specific location, but in its three dimensional displacement in the atmosphere, it may adiabatically expand or compress, changing in temperature. A temperature drop may lead to saturation and condensation of the vapour, with the release of the latent heat, and vice versa. In addition, also precipitation may occur, which removes liquid water and the possibility of utilising again the latent heat associated to it. All these thermodynamic situations can be appropriately described with new parameters that should be introduced at this point. Although they may seem complex at a first sight, they have the great advantage of being unaffected by some specific thermodynamic processes, so that they may characterise an air mass before and after the happening of the specific transformation to which they are invariable. All of these parameters are well familiar to people working in meteorology and transport of pollutants, and are useful to interpret a specific environmental condition in its more general meteorological context. In addition, they can be applied to better understand the
92 interactions that are happening on a monument surface.
3.1. EQUIVALENT TEMPERATURE The e q u i v a l e n t temperature Te (or te) or isobaric equivalent temperature is the temperature that a moist air parcel would have if all water vapour in it were condensed out at constant pressure and adiabatically, i.e. all the latent heat released in the condensation being used to heat the air. The adjective equivalent implies the sum of the latent and sensible
heat contained in the air parcel. It represents the molecular temperature that would be attained by an air parcel if all the latent heat Lv w potentially present in the parcel were transformed into kinetic energy of the air molecules, and liquid water were removed by the system, e.g. by precipitation. This process is only speculative, as all the forms of condensations that occur in nature do not involve the total a m o u n t of the moisture actually present. This parameter is given by the equation
Lv
Te = T + ~ w Cpd
~ T + 2.5 M R
(3.1)
where the right hand approximation (with constant Lv) shows that 1 g of water vapour raises the temperature of I kg of air by some 2.5~ From this definition this parameter is a conservative property of the air with respect to isenthalpic evaporation or condensation of droplets in the air, e.g. the formation or dissipation of fog or clouds, or condensation or evaporation of water in micropores of non conductive materials. At ground level, considering that at standard conditions, i.e. p = 1013 hPa and t = 0~
1 m 3 of air has the mass of 1.275 kg, and remembering the eq.(2.28), the
previous equation can be approximated also as Te ~ T + 1.95 A H - - T + 2 A H
(3.2)
w h e r e 1.95 = 2.5/1.275. This equation shows that 1 g of v a p o u r raises the temperature of I m 3 of air by some 2~ This parameter, which is a function of both T and M R shows w h e n and where the air exchanges heat (also called sensible heat) or moisture (i.e. latent heat) with an evaporating or absorbing surface, or when two different air masses meet and mix
93 together. In the case of microclimatic studies, this parameter is useful to individuate exchanges between air and surfaces or the penetration and path of external air. When no interactions have occurred, this parameter is the same indoors and outdoors. However, it remains unchanged also if condensation, or evaporation, occurs in micropores of a non conductive material, the heat being supplied or absorbed by the air. If the walls have a low conductivity and a very large heat capacity and all the heat is supplied or absorbed by them, the condensation in the micropores does not affect the room temperature but lowers the room MR and, consequently, the Te; the opposite occurs in the case of evaporation from the micropores. Although this parameter does not describe a realistic process, it presents several diagnostic advantages, and is the first step to arrive to define another parameter, namely the equivalent potential temperature, that is conservative with reference to both adiabatic and non isobaric processes. For instance, the formation or dissipation of a fog (or a cloud) cannot only occur with an isobaric and adiabatic process, and it is necessary to introduce other parameters, which will be conservative before, during and after uplift adiabatic expansions, cloud condensation and precipitation. The next step is to find invariance with respect to adiabatic vertical displacements in the atmosphere.
3.2. ADIABATIC GRADIENT IN THE TROPOSPHERE Following the path and the destiny of an air mass and its moisture in the lower atmosphere is not only of interest for the weather forecast, but also for the transport and dispersion of airborne pollutants. This implies to know how the energy is distributed and transformed within an air mass, its temperature and density. When in the path of an air mass important changes of height are involved, the ambient pressure changes, and the work done to expand an air mass is made with part of the thermal energy of the air molecules, so that the process causes a cooling of the air. This is an example of adiabatic expansion (i.e. without exchange of energy with the external system), and the temperature change which is regulated by this mechanism can be computed with the Poisson equation, as we will see in the following. The convective mixing of the lower atmosphere is the reason why the air temperature is lowering with increasing height in the first 1 0 - 15 km of atmosphere, called
troposphere. Above this layer, up to some 25 km, the air temperature increases again because in this second layer, called stratosphere, the dominant mechanism is the absorption of ultraviolet radiation by oxygen and ozone.
94 In a transformation which is reversible and slow, the internal pressure of an air parcel equals the external one and (3.3)
~)W= p d V .
The condition of reversibility gives (3.4)
5Q=pdV+dU
where the internal energy U = U(T) is a function of T only, as well known for an ideal gas. If an amount of heat 8Q is supplied to the sample of gas having mass m, all the heat is transformed into intcrnal energy and the increase is (3.5)
d U = m Cv d T
and this equation is valid also if the volume is not kept constant. The first principle of thermodynamics can be then written (3.6)
8 Q = p d V + m Cv d T
The equation of state is preferably written in terms of p and T only, as they are easy measurable parameters. The equation of state becomes (3.7)
p dV +V dp = m .J?~a dT.
By definition, for a thermodynamic transformation X the specific heat Cx is given by (SQ)x
mcv
Cx - m d T -
dT+p(dV)x m aT
p dV =Cv+m (d-T-)x
(3.8)
In the case of an isobaric transformation dp = 0 and the (3.7) becomes p dV = m .~a dT and
(3.9)
95
p m,ff/~a Cp = Cv + m
p
(3.10)
- Cv + . ~ a
Substituting this result in the (3.6): 5Q = m Cv d T - V dp + m , ~ a d T = m Cp d T - V
dp
(3.11)
and a further substitution in the equation of the state gives for the unit mass
( S Q )m = 1 = Cp d T - . ~ a T
dp --. P
(3.12)
For an adiabatic process 5Q = 0; if it is also reversible, then
Cp d T = . ~ a T dp P
(3.13)
or
dT = k T
dp P
(3.14)
where k = (Cp- Cv )/Cp = , ~ a / C p = 287/1003 = 0.286, which is valid for small variations of p. By integration the P o i s s o n equation is found for adiabatic and reversible processes, i.e.
T2 (p2k T1 - " ~ - ' "
(3.15)
The atmosphere is called adiabatic when vertical motions occur without any external work, and this happens when the density of the air parcels is always in equilibrium with the ambient air. The atmosphere is characterised by a neutral equilibrium making reference to the vertical adiabatic motions of dry air. It is possible to compute the vertical thermal gradient during neutrality. From the hypsometric equation of the hydrostatics dp = - p g dz where p is the barometric pressure, p the density, g the acceleration of gravity and z
96 the vertical coordinate, remembering that from the equation of the state for perfect gases .~/2~ap T / p = 1, eq.(3.13) can be written dT ,~a P g T g 9.8 d---~- Cp p = - Cp - - 100---3-~ 0.01
(K m -1)
(3.17)
which in practice corresponds to the cooling of 1~ per 100 m of adiabatic uplift. The vertical gradient dT/dz = 1~
m is therefore called adiabatic and is represented
with the symbol 7 (especially in the mathematical formulae) or F (especially for the graphical representation).
3.3. POTENTIAL TEMPERATURE We have seen that the temperature is representative of the average kinetic energy of the molecules in an air parcel, but that this value changes with vertical displacements of the parcel. It is useful to find a parameter which allows for a comparison between the average kinetic energy of the molecules in two air masses, independently of their height, i.e. referring them to a standard level. The p o t e n t i a l temperature 0 is the temperature a parcel of air would have if brought dry adiabatically from its initial state to the standard pressure of 1000 hPa. Note that the round number
1000 is used instead of 1013, in order to make easier calculations. At sea level the potential temperature is very close to the actual air temperature and it is exactly O = T when p = 1000 hPa. The potential temperature of an air parcel is independent of the height, similarly to the temperature of mixed, incompressible liquids. The O is computed with the help of the Poisson equation utilising the initial values of T and p, i.e.
O=T.p.
(1000~ k
(3.18)
where it is clearly shown that O is directly proportional to T. A region of the atmosphere in which O is constant on the vertical is said to be dry adiabatic. A representation in terms of O shows immediately where the
atmosphere is adiabatic, i.e. d O / d z = 0, as there the isotherms are vertical; where d O / d z > 0 the isolines are tilted towards left; where d O /dz < 0 the isolines are tilted towards right (Fig.3.1). Further details will be given in Chapter 7.
97 700 T
//
O
600
500
E~
400
9 ~,,,i
200
100
20
22
24
26
28
30
Temperature (~ Fig.3.1 Vertical profile of the air temperature T (thick line) and potential temperature O (thin line) in the Venice hinterland, the 25 June 1979 at 10 a.m. The first 150 m show a profile superadiabatic, i.e. with a gradient greater (in the absolute value) than the adiabatic one (O profile tilted towards left); from 150 to 280 m substantially adiabatic (O profile vertical); above the air is stable (O profile tilted towards right). In meteorology, weather prediction and pollution transport, the basic equations can be solved more easily if appropriate co-ordinates are used. For this reason, the geopotential, the pressure, the entropy and the potential temperature can be used as a vertical co-ordinate instead of the geometric height (for a discussion see Kasahara, 1974). Potential temperature or isentropic coordinates are especially convenient for description of adiabatic motions. As in the definition of O the a t m o s p h e r e is characterised by adiabatic displacements, in the whole region where O - const, also 5Q = 0 and displacements are isentropic. Therefore, all the surfaces with the same 0 are isentropic and an air parcel having a given value of O will remain within the same
surface of equal potential t e m p e r a t u r e , unless external w o r k is s u p p l i e d to it. Therefore, the isentropic representation of the atmosphere is a very practical tool to forecast where a pollutant can or cannot be transported; whether it will be able to cross m o u n t a i n chains or not (Fig.3.2). In fact, except near the soil w h e r e heat is
98 exchanged and in absence of condensation, an air parcel tends to maintain the same entropy and potential temperature.
Fig.3.2 Surfaces having the same potential temperature are also isoentropes. The vertical cross section of potential temperature shows an example. It is also possible to find a relationship between potential temperature and entropy. Dividing by T both members of eq.(3.12) and integrating, one obtains the
entropy function of the air: dQ = f Cp --~-dT f. ~a --~ dp = Cp lnT-.J?~a lnp .}/~=f --~
(3.19)
This equation holds for unsaturated air, assuming the air and vapour mixture behaves as an ideal gas (unsaturated vapour), but for saturated vapour the equation is identical, but for an additive constant (Goody, 1995). The relationship is easily obtained substituting in the previous equation the definition of O in eq.(3.18) in logarithmic form, i.e. lnO= lnT + -~p (lnl000- lnp)
(3.20)
so that the entropy is immediately found, .~= cp lnO
(3.21)
99 where the additive arbitrary reference constant has been omitted. The Poisson equation can be compared with the assumption that the vertical temperature gradient is constant and given by the eq.(3.17), i.e. dT/dz = y, so that T = To + 7 z
(3.22)
Dividing the hydrostatic equation (3.16) by the equation of state for perfect gases (1.2), and using the previous equation for T, dp
P
.
g dz . . . . . ~ a (To + ~/z )
g d(To + yZ ) - . ~ a 7 To + ~/z
(3.23)
or
dlnp = - g__K__dlnT. 7.~/~a
(3.24)
Integration gives p2 ( ~ ) - g / Y'~-'r Pl -
or
T2 (P2) ~ '~a /g T1 = "P-1-1"
(3.25)
where y. ~Z?a/g = k = 0.286.
3.4. EQUIVALENT-POTENTIAL TEMPERATURE The equivalent-potential temperature Oe is the potential temperature corresponding to the equivalent temperature Te , i.e. (1000}k Lv Oe = T e , p , = O + - -Cpd w
(1000} k , P ,
(3.26)
This p a r a m e t e r is conservative with respect to dry adiabatic processes, e.g. compression or expansion of air parcels due to change of height. The exponent k has been derived for dry air; the moist air, when reduced to the standard pressure of 1000 hPa has a temperature somewhat lower than dry air, and the departure
1 O0
increases with moisture content. However, this departure is in general very small, so that this parameter can be considered quasi-conservative for isenthalpic pseudoadiabatic processes. The adjective 'pseudo-adiabatic' refers to systems in which saturation occurs and the condensed water is removed from the system, e.g. by precipitation. The rising of air masses, which form clouds and rainfall are a meteorological example of a pseudo adiabatic process. Both the dry and the pseudoadiabatic lines are represented in aerological diagrams, e.g. the Strive diagram. This parameter varies for isobaric heating or cooling, or gain of vapour supplied by oceanic waters relatively warmer than the air. The above discussion on the isentropic surfaces can be applied with a wider generality to Oe, as it also includes the possibility of formation of clouds and precipitation. When an air mass is forced to flow over a mountain chain, during the slope rise it may arrive at a height above the cloud condensation level (CCL): the temperature drops below the dew point, the vapour is supersaturated and begins to condense forming cloud droplets and precipitation on the upwind slope. This upslope precipitation is known as stau. This mechanism continues during the cooling associated with the rise and stops when the air is heated by compression when it descends downwards along the other slope. The droplets which remain in the cloud evaporate again. If the equivalent temperature of the uprising and descending streams is measured in the opposite slopes at the same height Zl, the value Te(Zl) is the same for both streams, but is not conservative with changes of level, i.e. Te(Zl) Te(z2). The equivalent-potential temperature Oe of an air parcel which moves adiabatically is independent of the height, and is the same everywhere, so that an air mass can be always individuated by this parameter; when the parcel undergoes non adiabatic transformation, the change AOe gives the gain (or loss) of the thermal energy expressed as the sum of sensible plus latent heat. In the previous example, the temperature T of the air has undergone important changes. During the upwind condensation, the latent heat has warmed the air mass and most of the liquid water has been removed from the system by precipitation. During the descent, the cloud droplets evaporate re-absorbing the heat that they have previously released during the condensation phase, so that this part of the process is reversible; however, the heat supplied by the precipitated water remains in the air, which arrives hotter. This is the well known warm foen wind downslope. In all the stages of upslope cooling and precipitating and downslope warming the equipotential temperature remains unchanged or quasi-unchanged.
101 3.5. VIRTUAL TEMPERATURE A smoke plume, a meteorological balloon, or a cumulus cloud rise whenever their density is lower than the ambient air. However, the density of moist air is determined by two factors: the air temperature, and the moisture content. The molecular weight of water vapour is 18, whereas the average molecular weight of dry air is 28.96. For this reason, the density of a moist air parcel at a given temperature and pressure is equalised by a hotter parcel of dry air at the same pressure. In order to simplify the description atmospheric processes, it is convenient to ignore the presence of moisture and make reference to an ideal dry air with an effective temperature which simulates the effects of moisture in terms of density. The
virtual temperature Tv (or tv) of a parcel of moist air is that temperature at which completely dry air would have the same density and pressure as moist air. Also this parameter is speculative, but is very practical, as it allows to apply to the moist air the equation of state for dry air. This parameter is used w h e n c o m p a r i n g the buoyancy of two different air masses which come into contact, or the vertical uplift of a puff smoke or a meteorological balloon. Using the Dalton law the pressure of the moist air is p = Pa + e where Pa represents the partial pressure of dry air, and the mass is m = ma + mv where the labels 'a' and 'v' are still used to distinguish between dry air and vapour. The equation of state for the moist air becomes:
pV
.161 )
.~v. ~ - + mVm.j?~a ! T = m . ~ a (1 _ _m_Vm (ma.~/P~a+mv.~v) T = m . ~ a ( -ma m
: m . ~ a (1+ 0.61 - ~ ) T-- m.~a (1+ 0.61 m~aaV ) T : m , ~ a (1+ 0.61w)T
= m .~aZv
(3.27)
where Tv is defined as Tv = (1+ 0.61w) T but it is also often expressed as
(3.28)
102 (--,1 TT~
+~3p) T--
T3-------e _
(3.29)
_
8p The derivation of this formula is simple. When w is small, as it is, the reciprocal of (1+0.61w) is to a close approximation (1- 0.61w); substituting to w the approximation (2.19) and considering that 0.61x0.622 = 0.379 -~ 3/8, the latter equation is found. From the formulae it follows that T < T v < Te. Under usual meteorological conditions, the virtual temperature increment is Tv - T < 5~
103
CHAPTER
4
Radiation and Light
4.1. THE EMISSION OF RADIATION FROM BODIES AND THE EFFECTS OF THE ABSORBED ENERGY Each body emits electromagnetic radiation, which propagates in the space in the form of waves of electric and magnetic fields, according to the classic Maxwell's theory of radiation. The radiation frequency v is given by the ratio between the velocity of light c and the wavelength ~ of the radiation, i.e. c V
=
-.
c4.~
X
The intensity I of the flux of energy emitted from a blackbody per unit time, unit wavelength and unit solid angle, depends upon v and the absolute temperature T, according to the P l a n k ' s formula
I(v,T) =
2h
V 3 C2
exp(h vc / KT) - 1
(4.2)
where h = 6.626x10 -27 erg s = 6.626x10 -34 J s is the Plank's constant and K the Boltzman's constant K = 1.3806x10 -16 erg K -1. The same p h e n o m e n o n can be also described in terms of a corpuscular emission (Einstein, 1905), where the radiant energy is transported by photons having the individual energy E = h v,
(4.3)
the intensity of a spectral component being given by the n u m b e r of photons having a given wavelength. Although the two theories are equivalent in several cases, the classical wave representation is more suitable to describe some
104 p h e n o m e n a , e.g. diffraction, interference, polarisation; the q u a n t u m theory for other p h e n o m e n a , e.g. photoelectric effect, emission of cathode rays, gas ionisation by means of ultraviolet radiation. A synthesis of the two points of v i e w has been m a d e to associate with light the dual nature of w a v e and corpuscle. According to the Einstein's theory, w h e n a p h o t o n is absorbed by a molecule, the molecule absorbs its energy and excites, and this provokes a change of the energetic state of its electrons, with a n u m b e r of possible consequences. If the energy hv exceeds the bound energy of an electron, the latter m a y escape (photoelectric effect), or the exited molecule m a y dissociate, or isomerise, or transfer energy to another molecule, or change into a different c o m p o u n d with a photochemical reaction, or undergo other causes of degradation (Wypych, 1995). Ionisation in the u p p e r atmosphere, ozone formation in the stratosphere, and molecular excitation of atmospheric H20, CO2, 03 are well k n o w n mechanisms which absorb some spectral bands of the solar radiation. The solar radiation which arrives at the earth surface is classified as reported in Table 4.1. TABLE 4.1 Wavelength of the solar radiation crossing the atmosphere wavelength
radiation
wavelength
radiation
<10 A 10 A - 0.2 lzm 0.2 - 0.315 ~tm 0.315 - 0.38 ~tm 0.38 - 0.72 ~tm
T rays and X rays far ultraviolet middle ultraviolet near ultraviolet visible
0.72 - 1.5 ~tm 1.5 - 5.6 ~tm 5.6 - 1000 ~tm >1000 ~tm
near infrared middle infrared far infrared micro & radio-waves
The shortest w a v e l e n g t h s are mainly absorbed by the ion- and ozonosphere; the longest ones by atmospheric water vapour and carbon dioxide. The Sun, whose photosphere is at some 5,800 K, emits 99.9 % of its energy within the wavelength interval 0.15 to 40 ~tm, with a peak intensity in the visible, near 0.47 ~tm. A l t h o u g h the ultraviolet (UV) radiation is the most energetic one, it is composed of a small flux of photons and the power emitted is very low; about half of the power lies in the visible light and most of the second half in the near infrared. All bodies can absorb and emit radiation at all w a v e l e n g t h s , and the
'colour', i.e. the distribution of intensity of the spectral lines of the light, depends
105 upon the temperature of the body. This effect is quantitatively described by the
Wien's displacement law, which states that the spectral distribution of the energy density varies with the temperature of the hot body, the peak value being attenuated and displaced towards the infrared with decreasing blackbody temperature. More precisely, the wavelength ~p of the peak intensity for blackbody radiation is inversely proportional to the absolute temperature, i.e.
~P-
const
T
(4.4)
where the proportionality constant is 2897 gm K (Born, 1952). Of course, this finding has been obtained by differentiating the Planck function with respect to the wavelength, and equalising the derivative to zero, i.e. 3I(v,T) /3~ = 0. The highest the body temperature, the shortest the peak wavelength, and the lower the temperature, the longest the peak wavelength. The tungsten filament of a incandescence lamp has a temperature (or, better, the colour temperature i.e. the temperature of a black body having the same strength of colour) around 2800 K; its spectrum falls within the solar spectrum, with a lower spectral radiance, but with the maximum shifted to around 1 gm, in the near IR region. The candle flame has some 1700 K, its spectrum has a lower spectral radiance, begins in the visible and extends into the IR region where the peak value is found at 1.7 gm. At 800 K hot bodies are faint red and below this temperature they emit only invisible radiation in the IR region, with a lower power; at 800 K the peak is at 3.6 gm. At room temperature the spectrum has a still lower power, ranges between 3 and 100 gm, and the peak is near 10 gm. As the power emitted by a body depends upon T, a remote measure of this power can be used to detect the body temperature, which is for this reason called the radiometric temperature,.
4.2. RADIOMETRIC TEMPERATURE The radiometric
temperature Trad is the temperature deduced from the flux of radiant energy, per unit surface and unit time, spontaneously emitted by a body with temperature T by means of the infrared emission, according to the Stefan-Boltzmann law which states that the flux density emitted by a blackbody is proportional to the fourth power of the absolute temperature, i.e.
106 q~ = ~ T 4 where T
(4.5)
=
Zradso
that the temperature can be written in explicit form
Trad = ~ / q)~3
(4.6)
and r~ = 0.286x10 -10 cal cm -2 min -1 K -4 = 5.67 erg cm -2 s -1 K -4 is the Stefan constant. The flux of electromagnetic radiation emitted in the
IR spectral
w i n d o w can
be m e a s u r e d with a radiometer or a bolometer and furnishes an experimental observation of the surface temperature, without mechanical contact with the surface. This aspect is very important especially in the case of delicate surfaces that cannot be touched with contact thermometers (e.g. frescoes, where it is not possible to attach the sensor with glue) or for remote monitoring (e.g. ceilings, vaults) or whenever the contact thermometer m a y alter the surface temperature (e.g. w h e n the surface is lighted, the sensor shields the point of contact and measures the temperature of the surface in the shadow, instead of the lighted one) or the observed object is mobile. The radiometric temperature of a body is a function of several variables, some of intrinsic nature, e.g. the albedo and the thermal diffusivity of the body, and some due to atmospheric forcing, e.g. reflection of long wave radiation, air temperature, humidity, aerosols, cloud cover, heat or moisture accumulated or lost d u r i n g past meteorological conditions. This makes it difficult to obtain accurate observations of
Trad. The
radiometer (see Chapter 10) can be usefully
applied to compare relative temperature levels and to diagnose anomalies in the internal
conductivity
(e.g.
detachment
of frescoes
or
the
presence
of
h e t e r o g e n e o u s materials) especially during dynamic changes of t e m p e r a t u r e . Indoor m e a s u r e m e n t s are m u c h more easy and reliable than outdoor infrared observations. The Stefan-Boltzmann's law in the above form is valid for an ideal black body, w h e n both the absorptivity and emissivity are equal to 1. In practice, real bodies have some departures from this theoretical formulation, and a 'grey' correction should be added, which takes into account for the of the bodies; therefore, the grey emissivity r
relative emissivity
should be explicitly written in the
Stefan Boltzmann equation, i.e. = r r~ T 4.
(4.7)
107 The values of e are in general close to unity for most of the natural materials, but much less for polished metals, as we will see in Chapter 10. As E varies with the physical characteristics of the surface, e.g. wet or dry, attention must be paid in order to distinguish apparent variations of T from changes of e. The flux of radiation arriving from a surface can be divided into two components: one is the radiation emitted by the surface, and the other is the reflected, emitted from other bodies, giving rise to an apparent greater value of ~P. Dividing these quantities by the incident flux, the following identity is found a+R=1
(4.8)
where R is the reflectivity of the surface. This equation shows that good reflectors are bad emitters, and vice-versa; e.g. polished metals are good reflectors but bad emitters; candle smoke has an emissivity close to 1 but a very bad reflectivity.
4.3. ANGULAR DISTRIBUTION OF RADIANT EMISSION OF BODIES The radiant intensity I(0) (i.e. the flux per unit solid angle) emitted in any direction from a unit radiating surface varies as the cosine of the angle 0
between
the normal to the surface and the direction of the radiation ( L a m b e r t law), i.e. I(0) = I(0) cosO.
(4.9)
At the same time, the radiometer sees the observed surface under a given solid angle, determined by the diaphragm which characterises the geometry of its optics. When the instrument is normal to an extended surface, it sees the portion So of it; w h e n it is rotated by the angle 0, it sees a greater portion of surface, i.e. S(O) = S o / c o s O , although tilted by the angle 0. As a consequence, the flux of
radiant energy entering through the diaphragm is
(0) = I(0) S(O) = I(0) cos0
So cos0
= I(O) So = 9 (0)
(4.10)
i.e. the luminance (or radiance) of a radiating surface is independent of direction and appears equally bright at all angles. A surface exactly obeying this law is called
108 Lambertian. The ideal black body is Lambertian, and m a n y bodies are Lambertian,
at least in a first approximation. For this reason the Sun and the Moon have the appearance of a flat disk and not of a three-dimensional sphere, and golden or painted domes appear flat. For this reason Vittori and Mestitz (1975) suggested that in the four brass horses of the Basilica of San Marco in Venice, which are plated with gold and present m a n y narrow scratches, the network of scratches was the result of the delicate work of a skilled engraver to gain the third dimension. However, other surfaces may present some departures from this law. The wings of butterflies which change colour with the angle of sight, and Persian carpets with changeable luminance, are well known examples of non-Lambertian surfaces. It might be useful to remember that radiance (W m -2 sr -1) is a radiometric unit which measures the energy emitted in the unit time (Watts) from the unit surface (square meter) in the unit solid angle (steradians, sr) and luminance (lm m -2 sr -1) is a photometric unit which measures the intensity of the light which is sensible to the eye (lumen) emitted from the unit surface in the unit solid angle; both are a measure of the power radiated from t h e u n i t area into the unit solid angle. A n o t h e r consequence of the Lambert law of emission is that surfaces differently exposed, even if in contact with air at the same temperature, assume different temperatures as a result of the radiative balance. In fact, horizontal surfaces facing the clear sky emit IR radiation receiving back only a small portion of the outcome; on the other hand, vertical surfaces see on the horizon an infinite optical air mass, so that the IR outcome equals the income. For this reason dew forms early on the horizontal top of cars, which faces the sky and cools d o w n more rapidly than the vertical broadsides.
4.4. ATTENUATION OF LIGHT IN THE ATMOSPHERE Corrections to the observed q)should be made also to take into account the attenuation of intensity caused by atmospheric absorption, and in particular by the water v'fipour, CO2 and other gases, smokes and atmospheric aerosols. The atmospheric attenuation is exponential and selective for every w a v e l e n g t h k ( B o u g u e r - L a m b e r t law), i.e. I(k) = Io exp(-~z(k)m)
(4.11)
109 where Io is the intensity of incident radiation (out of the atmosphere), I(;~) the intensity after passing through the optical air mass m, and 0~(~) the absorption coefficient. This law can be expressed also in terms of the optical path length x t h r o u g h the absorbing substance, instead of optical air mass m. This formula shows that a white solar beam, when crossing the atmosphere, has its spectral components attenuated in a diffrent way o~(K), and the final mixture of colours d e p e n d s u p o n the optical air mass m, and the latter is a function of the sun height Ho, or its zenith angle Zo = 90 ~ Ho, i.e. m = secZo.
(4.12)
This is the reason w h y the daylight changes continually colour, from sunrise to sunset. When radiation is incident upon the atmosphere, or a liquid or a solid body, part of it transmitted, part absorbed, and part is reflected. The ratio of each of these quantities to the incident flux, which are respectively called transmissivity
Tr, absorptivity A, and reflectivity R, must add up to unity, i.e. Tr + A + R = 1.
(4.13)
This formula holds in average, as well as for the spectral quantities for any value of wavelength K, included the visible or thermal infrared range.
4.5. DAILY AND SEASONAL CYCLES OF SOLAR RADIATION ON A SURFACE Natural
light falls on external
monuments
and p e n e t r a t e s
through
windows: it is composed of direct radiation, which forms the solar beams, and
diffuse radiation, which is scattered by the sky in every direction. The diffuse component ranges from 20-30% of the total income in clear days, to 100% in overcast ones. The scattering is a function of the wavelength (this is the reason w h y the sky appears blue), and the very energetic photons in the ultraviolet band are the most scattered ones, so that they hit also objects not illuminated by direct light. For every latitude q and day of the year, defined by the solar declination 6o, the direct light can be computed by means of the coordinates of the sun: the
II0 altitude over the horizon (i.e. solar height) Ho and the azimuth Ao i.e. the angular
distance b e t w e e n the vertical circles containing the zenith
and,
respectively, the sun and the south point. The astronomical formulae to compute these coordinates are: sinHo = sin6o sin$ + cos6o cosr cost
(4.14)
cos6o sinz
sin Ao = ~
1- (sint~o sinr + cost~o cosr
(4.15)
cosz)2
where the hour angle T = 180 ~ t/12 is computed from the time t, in hours and tenths of hour, from or to the culmination of the sun, i.e. from or to the true mid-day. This means that t is negative in the morning, vanishes at noon and is positive in the afternoon. The solar declination 3o(j) for the j-th day is found in astronomical ephemerides
tables or, for e n v i r o n m e n t a l p u r p o s e s ,
can be
computed with the simple approximation 2~j
3o(j) = So(0) cos 365
(4.16)
where the j-th day is computed after the winter solstice and 3o(0) = -23 ~ 27' is the declination of the winter solstice. In this formula the earth orbit around the sun is supposed circular. The mean of the Earth orbit eccentricity e~ is ee = 0,0167; the eccentricity is found dividing the distance between the foci by the length of the major axis, and a circle is the limiting case as e~ approches zero. The error of this approximation
is small (some primes) and negligible except for precise
astronomical calculations. From the above formulae it follows that: *
at solar noon, when the hour angle ~: is zero, cost = 1 at any latitude, and the
9
zenith angle Zo (defined as Zo =90 ~ Ho) is Zo = ~ - 6o; at sunrise and sunset (i.e. Ho = 0), at any latitude (except the poles), cosZo=0, and 2~: is the daytime length expressed in hour angle;
9
the daylength DL =2~: can be computed under the condition cos~: = -tanq tan6o, i.e. DL = (24/~:) arccos(tanr t a n ~ ) (hr).
Solar beams are represented by straight lines coming from the sun and passing through a window; their intercepts on the opposite wall represent the light spot. The envelope of these spots describes the areas affected by the direct solar income
111
during the course of the day as discussed below.
intensity Ip of the solar radiation (also irradiation) falling on horizontal, vertical, or arbitrarily inclined planes
The flux density per unit time or called
(Robinson, 1966; K o n d r a t y e v , 1969; Bernardi and Vincenzi, 1994) facing the direction
Ap ( c o m p u t e d from the m o m e n t of the true noon, i.e. the south) and
inclined by the angle ]3 with the plane of the horizon, is
Ip = Io {cos// (sin6o sinq + cos6o cosq cos1:) + + sin]3 {cosAp [tanq (sin6o sinq + cos6o cosq cosr
- sin6o secr ] + (4.17)
+ sinAp cos6o sin~: }} where
Io is the intensity of the solar beam (near the surface) and the irradiation
on a h o r i z o n t a l or vertical plane is o b t a i n e d by setting 13 = 0 ~ or ]3 = 90 ~, respectively. An example of the hourly variation of the flux density of the solar radiation on the h o r i z o n t a l
a n d vertical surfaces w i t h v a r i o u s o r i e n t a t i o n s
is here
discussed for the latitude q = 45 ~ In order to show the influence of the absorption due to the optical mass, first let us s u p p o s e that the a t m o s p h e r e is perfectly transparent. At the winter solstice the sun rises at Ao = 124 ~ i.e. close south-east (135 ~ and sets at Ao = 236 ~ i.e. close south-west (225~
and the vertical surfaces
facing these two directions receive the m a x i m u m flux of energy; at noon the solar height is low, i.e. Ho = 90 ~ Zo = 90 ~ - (~ - ~o) = 22~ and the energy income on the vertical surface facing south is greater than that on the horizontal plane. At the equinoxes, sunrise and sunset occur just at east and west, and w i t h a perfectly transparent a t m o s p h e r e the vertical surfaces facing these two directions receive the m a x i m u m flux of radiation. At this particular latitude, at noon the solar height is Ho = 45 ~ so that the solar energy which falls on the vertical surface facing south equals that on the horizontal plane. At the s u m m e r solstice surprise and sunset occur respectively at Ao = 57 ~ i.e. m i d w a y b e t w e e n north-east and east-north-east and Ao = 303 ~ i.e. m i d w a y b e t w e e n north-west and west-northwest; at noon the sun is high, i.e. Ho = 68 ~ so that the solar energy flux which falls on the vertical surface facing south is less that on the horizontal plane, and at this particular latitude the flux on the horizontal equals the flux at the winter solstice on the vertical surface facing south and vice versa. If the same calculations are m a d e taking into account the attenuation of the solar radiation w h e n it passes t h r o u g h the optical air mass which increases with decreasing solar height according to the above formulae, the results are quite
112 10
08
06
.v=,l
I,,. -I
04
02
O0
I
4
'
I
6
'
I
8
'
T
10
"
I
12
"
1
14
'
I
16
18
20
10
08
ESE
SE SSE_ -qSW S W H bv WSW
06 0 .I-i
04
02
O0
|
4
9
6
|
9
I
8
10
10
9
T
9
|--
12
|
9
14
16
18
20
~mmlm~
9
08
E
~l
,"
",
W
w 0,6
"-'
r~ .v..~
0,4 02 O0
9
4
6
8
10
12
i
14
.
r
16
.
i
18
20
T i m e (h) Fig.4.1 Hourly variation of the flux density of the solar irradiation Ip on the horizontal H (dotted line) and vertical surfaces (full lines) with various orientations (principal compass directions, thick lines; secondary, thin lines) for the latitude q~ = 45 ~ (a) Winter solstice; (b) equinoxes; (c) summer solstice.
113 different, as shown in Fig.4.1. At the winter solstice (Fig.4.1a), the declination 3o is at is m i n i m u m and the optical thickness of the atmosphere is so important that w h e n the sun is very low on the horizon (i.e. south-east and south-west), and the light beams perpendicular to the vertical surface, the fraction of energy reaching a vertical surface faced to the sun is less than the energy which arrives at noon, w h e n the beams arrive slant, but after having passed a shorter optical length. The other vertical surfaces receive a smaller flux of energy, which is the combined effect of the atmospheric attenuation and slant incidence of the beam. The vertical surface facing south receives the m a x i m u m flux density, and the horizontal plane a very minor value. At the equinoxes (Fig.4.1b), 3o = 0, and the absorption is less. Near sunrise and sunset the atmosphere causes an important attenuation (but less than in winter) and then the maximum flux density on the vertical surfaces facing the sun remains more or less the same, reaching the m i n i m u m at noon where the geometric effect of the slant beam dominates over the minor atmospheric attenuation. On vertical surfaces not faced to the solar motion (northern sector from west to east) the flux density is much less. The flux density on the vertical surface facing south equals the flux density on the horizontal plane. This is obvious at noon, when the solar altitude is Ho = 45 ~ forming the same angle with the horizontal plane and the vertical surface; on the other hours, for the vertical surface, the advantage of receiving the beam with an angle approaching the normal is substantially compensated for the atmospheric absorption. At the summer solstice (Fig.4.1c), the declination 6o is at is m a x i m u m and the optical thickness of the atmosphere is further reduced. However, the height of the sun over the horizon becomes so important which is the dominant factor, except near sunrise and sunset. In fact, the flux density increases from sunrise as far as east, then decreases and reaches the m i n i m u m at south and continues symmetrically till sunset. The elevated solar altitude makes m a x i m u m the solar income on the horizontal plane. The flux on the south surface is low and at noon is close to the value reached at 6.30 a.m. on the north-north-east or at 17.30 on the north-north-west. A comparison between the plots at the two solstices shows that at noon the summer flux on the vertical south Surface is greater than the winter flux on the horizontal plane at the same hour, and the s u m m e r flux on the horizontal plane at noon is even more greater than the winter flux on the vertical surface facing south. This example shows how the solar income is affected by the atmospheric optical length, although in clear sky. If the atmospheric attenuation originated by the seasonal change of the local climate (e.g. haze persistency, cloud cover) or pollution, the departures are also
114 '~>.~ 35000 30000 ~ , 25000 20000 0
15000
SE,SW
10000 O
["
5000
~2
o
E,W
0
5
10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90
35000
.....
30000 25000
s 20000 0
15000
rW
""q
10000 O
[-'
5000
o 0
5
10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90
35000 30000 25000
SW 20000 0
"-'
15000 10000
,.i..a
O
N
5000 .~
0
[
0
i
i
i
i
i
I
i
i
|
i
i
i
i
i
i
'
i
'
i .......
~
5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 g0
Sloping Angle Fig.4.2 The daily total income It of the solar radiation on a slant surface oriented in the eight cardinal directions is represented against the sloping angle r for the latitude = 45 ~ (a) Winter solstice; (b) equinoxes; (c) summer solstice.
115 greater. It is also possible to integrate over the whole daytime the flux density of solar radiation for a surface arbitrarily oriented or slant (Fig.4.2). At the winter solstice the dominance of the southern sector is evident. At the equinoxes, the m a x i m u m instantaneous values of irradiation shown in Fig.4.1b were similar for the whole southern sector from east-south-east to west-south-west, with a slight m i n i m u m on south, and the surfaces facing east and west having slightly less than south. However, the daily total solar income on these vertical surfaces (i.e./3 = 90 ~ shows a different situation: the south surface receives the m a x i m u m total and the east and west ones half of it. On the other hand, when ]3 tends to zero, all the slant surfaces tend to the horizontal plane and the differences tend to vanish. For slant surfaces facing south and south-east or south-west, the total income reaches the m a x i m u m respectively at the slopes ]J = 45 ~ and ]J = 40 ~ The whole southern sector has convex plots with the m a x i m u m at a sloping angle which tends to vanish at the east and west orientations. The east and west plots are still convex but close to a straight line. The northern sector has concave plots, with the total income decreasing w h e n the slope increases. The surface exposed to north is no more reached by direct solar radiation when ]3 > 45 ~ At the summer solstice all the integral values, except the northern sector, are quite similar.
4.6. WHAT IS THE COLOUR OF NATURAL LIGHT? Sunlight is optically white, as it is composed of a balanced mixture of all the colours, that is all the wavelengths in the spectrum of incident light. However, w h e n the solar r a d i a t i o n p e n e t r a t e s the a t m o s p h e r e , the w a v e l e n g t h s c o r r e s p o n d i n g to violet and blue resonate with the oxygen and n i t r o g e n molecules which disperse them. Looking at the sky on a clear calm day, the characteristic interstellar blackness of empty space can not be seen, but there is, instead, an intense blue, because the h u m a n eye is much more sensitive to this colour than it is to violet. The lighter blue or the whitish colour of the sky depends upon the presence of minute drops of water of various diameters (which are even more evident w h e n there are clouds), given that the dispersion is not selective but distributed over the whole spectrum. The band of solar radiation is initially white, but when part of the blue has been subtracted from direct sunlight and diffused in all directions by the air molecules, colours slightly change and the white objects which are far away, e.g. the snow-caps of distant mountains, slightly
116 take on a complementary yellow, orange or red. This is what happens every day as the sun changes the height and the light beams cross a variable optical thickness of the atmosphere. The colour change is m i n i m u m when the sun is near its zenith (midday, summer solstice) while it is at its m a x i m u m when the sun is near the horizon (sunrise and sunset, winter solstice), given that the rays are at a grazing angle and cross a thicker atmospheric layer. Pollution increases the opacity and the colour change. The sun itself, which is very white, seems to take these colours that correspond to the progressive detraction of the blue varying from brilliant yellow to purple with the time of day and the season. Not only the light changes colour with the day and the season, but also the eye has a perception of the colour which depends upon the light intensity. When the intensity is high, the objects appear lighted with a w a r m e r spectrum, i.e. displaced towards yellow and red; when the intensity is low, the object appear lighted with a colder light, e.g. objects lighted by the moon appear with a bluer colour. This different response of the eye is called Purkinje effect.
4.7. ARTIFICIAL LIGHTING, OPTICAL FILTERS AND OPTICAL FIBRES The variability of the sunlight colour poses a question, which is very i m p o r t a n t w h e n works of art need artificial lighting 'What kind of lamp will give the same light as the sun?' This question is not a realistic one, in that a lamp does not vary during the day, from red at sunrise to the golden white at noon and red again at sunset. A lamp does not take on the light blue of fog, nor does it d a r k e n as the sky darkens with clouds, neither does a lamp take on the transparency of the drops of water when it rains, nor does it change tone with the various seasonal changes in the vegetation, nor does it reflect the white of the snow. Every lamp, characterised by a different shade can only reproduce one of these particular instantaneous colours, b u t a lamp can never reproduce the same dynamic shades of sunlight. However, in front of a fresco, or in an exhibition room, it is necessary to choose the type of illumination to adopt. Would it be better to choose a light giving the same colour of a candle, a torch, the sun at dawn or at another precise time? This is a static sensation that must be chosen, and once realised, it remains unchanged. For illuminated works of art, however, the choice of the appropriate or inappropriate light depends u p o n two requests: (i) a good reproduction of
117 colours, (ii) the minimum damage to artefacts, either directly or indirectly; e. g. avoiding excessive intensity and especially direct exposure to U V or IR radiation which may provoke alteration or discolouring, while the indirect effects are caused when lamps generate convective cells because of the heat they dissipate, thus leading to deposition of particles which stick on the surface of the work of art. All sources of light have their own emission spectrum, including in different proportions the U V band (which should, therefore, be filtered above all for organic material), and the IR that forms a considerable part of the total light spectrum. The harmful effects of U V and IR radiation vary with the type of material sensible to these wavelengths, and it is virtually impossible to make a universally valid quantitative comparison of the damage resulting from the intensity of the illumination. Any effect would be typical for each material and different source of light. In such cases it is necessary to determine whether it is advisable to substitute one source of light with another, and whether, for example, the situation is improved by substituting partially or wholly the sunlight with artificial light. The answer only depends upon how much U V and IR radiation can be filtered. In terms of conservation, the best lamp is the one
with minor U V and IR bands, i.e. the most dangerous wavelengths, and the less heat dissipation. A comparison of the overheating caused by different kinds of lamps is shown in Fig.4.3 which considers only the IR
component.
With
reference to colour, it must be remembered that the human eye can only visually discern a certain spectral distribution of sunlight, so that the same spectrum should be present in the source of artificial light. Incandescent lamps (i.e. traditional tungsten filament ones and halogen lamps) have a continuous spectrum, with an intensity distribution which is different from sunlight because of the lower emission temperature which favours warm tones. Incandescent lamps are often preferred for their continuous spectrum, with a warm tonality midway between the solar light and the candle, although they have an important IR emission. When a spotlight is switched on, the energy transferred to the illuminated area warms the surface of the artefact (Fig.4.4): part of heat penetrates into the artefact warming it, part is returned back to the air, part forces evaporation, according to the energy balance (see Chapter 7). There is, subsequently, a considerable reduction in the relative humidity both in the air enveloping the object, and in the internal pores. A painted wood tablet looses some vapour and curl up in different directions; flakes of colour drop off the surfaces which is experiencing differential expansion; microfractures appear
118
3.5 TIL U.
2.5
~
2
~
1.5
>
1
0
HL
MMH
0.5 0
10
20
30
40
50
60
70
80
Time (min) Fig.4.3 A comparison of the overheating AT caused by different kinds of lamps, lighting with 500 lux a blackened aluminium target. TIL indicates a tungsten incandescence lamp, HL a halogen lamp, MMH a lamp obtained with a mixture of metal halides. The last has been used to illuminate the Giotto and the Sistine Chapels.
16.8
17.5 17.1
Fig.4.4 Hot spot generated by the incandescence lamps that years ago were used to illuminate the Leonard's Last Supper, Milan. Now the lighting system has been changed with a more diffuse and cold light. Measurement taken the 9 May 1982. (after Camuffo and Bernardi, 1991, reprinted by permission of the Bollettino Geoflsico)
119 on the surfaces as the dehydration continues on the objects which are porous or made of organic material such as ivory. The excitation sources such as fluorescent lamps have a low IR dissipation, and for this reason they are said to give cold light. This is a clear advantage; however, they have a discontinuous spectrum, very different from the solar one, with some chromatic lines missing while others may be excessive with some unbalanced effects which alter colours.
Sometimes they are appreciated for the
absence of IR, more often they are rejected for the colour changes. They have a higher UV emission in comparison with incandescent lamps, which may have negative effects in the oxidation, cross linking and fading. However, now some fluorescent lamps with anti-UV filters incorporated are commercially available, so that this problem is eliminated with an appropriate choice of the lamp characteristics. Joining a cold fluorescent light with a warm one does not mean that this combination will give the same spectrum as sunlight, but will only give a light with a superposition of spectral lines giving excessively w a r m or cold tones with some gaps due to missing lines, so that the overall effect is one that might, in the first instance, trick the h u m a n eye but which does not give the full chromatic picture. It is, however, impossible to add a missing line, although it is always possible to balance a spectrum with an excessively dominant line, toning d o w n the d o m i n a n t colour with a complementary colour. For this reason, the high density discontinuous spectra are preferable, while the ones which have too m a n y missing spectral lines should be discarded. A c o m b i n a t i o n of two complementary lights is unadvisable also because it is very difficult to balance two sources, and the balance changes as the lamps age. Such a combination also creates a double shade in two different colours and, also, the IR emitted and the heat dissipated by conductivity and advection are, on the whole, always greater than those from one source of light having the same luminous efficiency. C o n s i d e r i n g the d a m a g e that excessive illumination can cause in an exhibition room, direct sunlight should be avoided. The daily apparent solar motion induces sunlight spots to describe curved bands on the wall opposed to w i n d o w s (or also in the wall p e r p e n d i c u l a r ) a n d these bands move with the season: they are higher in winter and lower in summer (Fig.4.5). A very common m e t h o d used to intercept the light beams is to apply curtains to w i n d o w s . However, when curtains are hit by solar radiation, their temperature rises: the air coming into contact with them w a r m s and a convective motion is generated. This airflow is responsible for soiling the portion of wall above the windows, or
120
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
,
. . . . . . . . . . . . . . . . . . . . .
f
!ii!i!iii!iii
Fig.4.5a Spots of direct light in the Giotto Chapel, Padova, during the winter solstice. The upper band shows the daily displacement of the sunlight spot through the three-mullioned window on the facade and the lower bands the spots through the first, second and last side windows (the others are shielded by trees). The Chapel is oriented with the facade facing 240 ~ The sunlight has been shaded for a long time with curtains, and now the problem has been solved adding an amber glass outside the old windows. The external pane has been applied at a distance of some 10 cm from the window, leaving a free space on the bottom and the top, to allow a free circulation of air and avoid the green-house effect. The external position helps to protect the stained glass against the adverse meteorological factors.
Fig.4.5b Spots of direct sunlight in the Sistine Chapel calculated for December 15. The windows are in stained glass and the light passing through is partially dispersed. However, as the effect of light is cumulative, a second protective pane, or a polyester film optically treated with the inclusion of metals and other pigments should be applied. (After Camuffo and Bernardi, 1986 reprinted by permission of the Boltettino dei Musei e Gallerie Pontificie)
121 also the ceiling. Another problem with curtains is that dust and bacteria deposit on them; bacteria grow, and when curtains are shaken off for closing windows, they form a dangerous clouds of dust and bacteria. The practice of keeping some areas too much illuminated in order to light up the furthermost parts of the room, is imprudent. Diffuse sunlight should be reduced w h e n it is too intense, or integrated with artificial light in the areas where it is too weak. The goal is to reach everywhere a h o m o g e n e o u s , soft lighting. In the sunlight, the harmful (and optically useless) parts of spectrum outside the optical range should be filtered out. This can be easily done by using optically selective glass panes or applying a filtering film over the panes. However, it may also be necessary to dim the visible light, although this is a particularly delicate problem because it means that, in practice, a reflecting or coloured glass must be used. A reflecting glass is in principle similar to a mirror, but one which has a chromatic tone alters, at least slightly, the tone of sunlight, and the same problem applies to coloured glass. Although everybody appreciates the gothic cathedrals which have large stained glass windows to colour the austere interiors, the use of new coloured glasses is not accepted, especially in an ambient decorated with frescoes or pictures. Several colours exist, but in practice the choice of a coloured pane is necessarily limited to two possibilities: grey and amber. Grey is not properly a colour but a balanced toning down of the whole spectrum, so that none of the single colours dominates in that there is only a light, general attenuation; grey is the first step towards black, which is the total absence of all colour. This choice is probably the less popular, but is certainly the most impartial. It does not alter the colours inside the room but only sunlight intensity coming from the exterior, as if it were covered with a dense layer of clouds; almost a psychological trick played on the weather. Using an amber pane of glass might seem, at first sight, absurd, because this really does alter colours, toning down all of them, except those of the same amber tone which are reinforced. However this is, in reality, the same thing that happens, as described earlier, to the sunlight crossing the atmosphere, i.e. light filtered through an amber pane is similar to sunlight a short time after d a w n or before sunset. An amber glass might be considered, therefore, responsible not for falsifying colours, but rather, for falsifying time, so that in the morning the light inside is similar to that outside a few hours earlier and vice versa in the afternoon. It falsifies the time of the day and, if it is raining outside, it falsifies also the weather. The final choice, however, depends on how adequately the artificial
122 light complements the natural light from windows, so that the overall result is the most pleasant one. Lamps placed inside the exhibition cases turn these into small greenhouses because the panes allow the light in the visible range to pass through but not so the infrared, as we have seen in Chapter 1. Given that the IR emission is considerable, even with the so-called cold lights, heat is trapped in the exhibition case and results in overheating the objects and in dropping the relative humidity. A good method, w h e n e v e r possible, is to place lamps outside the case and transport
light inside with optical fibres, which are m a d e of a glass core
s u r r o u n d e d by a cladding having a lower refraction index. A ray will be transmitted only if the glass is transparent to this wavelength and if the fibre is able to trap the light beam in the core by total internal reflection, which is d e t e r m i n e d by the combination of the refractive indexes of the core and the cladding. Most glasses are opaque to the UV region for some strong absorption bands arising from electron excitation of two types: i.e. when electrons are excited from the valence band to unoccupied states in the exciton or the conduction band, or w h e n electrons are transferred from the shells of one ion to the shells of another ion. The absorption in the IR especially occurs as a result of atomic vibrations in a molecule that has a dipole momentum, which has a fundamental vibration mode in the IR spectrum (Varshneya, 1994), as e.g. the H 2 0 molecule. If the optical waveguide is transparent to the optical b a n d w i d t h and is opaque to both the ultraviolet and infrared edges it acts as a filter which supplies light only in the visible spectrum, otherwise the UV and IR bands can be cut out inserting appropriate filters between the light source (e.g. a halogen lamp) and the fibre. Then the light is concentrated with a lens and supplied to the fibre. This beam, c o m p o s e d of pure light in the visible region, will be transported with the w a v e g u l d e into the show case, and then the beam is opened again with another lens in order to illuminate the object within a desired light cone.
4.8. DETERIORATION TO WORKS OF ART CAUSED BY LIGHT Light causes several mechanisms of degradation, e.g. photo oxidation of gaseous pollutants which form a very aggressive environment, chlorophyll synthesis and possible development of algae (especially in prehistoric caves, Etruscan tombs or other dark rooms) and other forms of vegetation, as well as direct damage to objects. Direct damage severity depends upon several factors:
123 photon energy (i.e. the wavelength of the spectral line), total number of photons as well as material response. This changes with the chemical composition and crystalline structure, type and concentration of the molecules, optical properties of the surface and the subsurface layer, penetration depth, interactions with the molecular structure and electronic state. In the simplest case, absorbed light can be transformed into heat, which affects temperature and relative humidity, and may induce internal stress. Paintings are more intensely illuminated and heated; Fig.4.6 shows the heating of the panel 'the Madonna d'Ognissanti' by Giotto (Uffizi Gallery, Florence), compared with the wall and floor temperature. The wall close to the painting and the floor have a gradual rise of temperature AT which reaches some 1.5~ after 6 hours, with an average heating rate equal to 0.25~ lower thermal capacity, is overheated by a AT = 3~
the panel which has a after 4 hr, with 0.75~
heating rate, i.e. tree times faster. 21 Painting
20 ~ o
v
19 =I ^ _
18
Wall
[..., 17
16
0
3
6
9
12 Time
15
18
.21
24
(h)
Fig.4.6 Heating of the panel painting the Madonna d'Ognissanti by Giotto (Uffizi Gallery, Florence) compared with the wall and floor temperature. The 3 February 1993. Light can alter the crystalline or polymeric structure. Many organic molecules are sensible to this form of degradation, and damage occurs when the amount of energy absorbed by a molecule exceeds the bound energy. For this reason, the sensitiveness of a material increases with the p h o t o n energy, suffering the most severe damage with the shortwave U V light. The most evident effects are polymers ageing, reduction of the plastic and elastic properties, colour fading, textiles yellowing, wood degradation. An extensive presentation of
124 the present day knowledge in this matter has been made by Wypych (1995). A change of colour relates to changes in the chemical composition of the material and discolouring is the main problem of water colours, ink drawings, ancient manuscripts, coloured textiles. Oxidation of keratin exposed to U V radiation is responsible for wool yellowing and decrease in tear and tensile strength and abrasion resistance. Wood is very sensible to UV radiation, and the weathered outer layer increases sensitiveness to abrasion, having loosely connected fibres. Although the UV penetration is limited to a depth of 75 ~tm, the damage progresses in depth and after one year exposure degradation can reach 3 mm, but one century is necessary to double the depth of the deteriorated layer. Surface coating may protect wood, and in the case of painted tablets the problems are substantially two: the degradation of dye, and the stress experienced by the wood after the temperature and the equilibrium humidity change. In special exposition rooms, several attempts have been made to evaluate light levels and types, and some authorities have r e c o m m e n d e d lighting standards between 50 and 200 lux to limit fading, yellowing and breaking of mechanical bonds of dyes. However, there is no known level of lighting which has been proven to be safe for colour change. The real problem is that damage progresses with the cumulative number of photons which have reached the surface (and this involves light intensity, lighting duration, number of repeated cycles) and the energy of individual photons. The energy is associated with the wavelength, and the most obvious conclusion is that the whole visible spectrum should be allowed, but harmful UV and IR should be avoided with the use of appropriate filters. In addition, it should be useful to preserve in the dark artwork which suffer fading (e.g. historical robes, tapestry and other coloured tissues, water coloured drawings, gouache painting) and light them only gently, during the visiting time, as for the Leonard's Virgin and Child with S. Anne and St. John the Baptist in the National Gallery, London. This principle can be usefully extended preserving the whole museum or gallery in the dark and lighting exhibits only when people really want to watch them. This goal can be attained by placing in front of each painting or show-case an IR proximity sensor which detects approaching persons and temporarily switches-on a local gentle lighting, so that light follows paths and stops of visitors. The intermittent use of soft light, when necessary, is different from the dangerous practice of lighting panels or paintings for few minutes with powerful lamps which are turned on every time a visitor introduces a coin. Every painting is composed of a number of different layers (i.e. a colour coating, a preparation
125 base, a canvas, or a wood tablet, or a wall) which are bad conductors, so that the energy of the light beam is not transmitted or dissipated at the same rate in all the layers. When the lamp is turned on, the pictorial coating becomes overheated and expands generating mechanical stress with the base which has not yet been w a r m e d up, causing microfractures and partial detachment of the coating, which is transformed in tiny flakes, raised at the edges like the skin of a snake. After some delay, the heat reaches the preparation base and then the underlying frame, causing a dangerous surface stress every time the light is turned on/off, which tends, in the long run, to detach the coating from the support. This fatigue and ageing are important for painted tablets, paintings on canvas, frescoes, wood, ivory etc., where the mechanical stress is much more dangerous than fading. Flash light is usually forbidden in museums. The principle is theoretically sound, but in practice each flash has a very short duration so that the energy transferred to the objects is so small that its contribution is substantially negligible. For instance, considering that flash light may reach the intensity of daylight and usually has a duration from 1/1000 s to 1/50,000 s, then respectively 1000 or 50,000 flash pictures are equivalent to one second solar lighting as far as photon accumulation is concerned. Regarding heating, their cumulative effect is absolutely negligible, the energy being supplied by means of several very small contributions provided after time intervals which are extremely long compared with the short flashlight duration; consequently, the heat transferred is easily dissipated and never overheating is reached. Flashlight is much more dangerous for the guardians' eyes, and might constitute a real risk only for extremely delicate objects. If some paintings suffer for light accumulation, a much more substantial advantage can be achieved closing curtains and w i n d o w shutters as soon as visiting time is up. The position of the sources of artificial light is very important. In a closed environment the air is naturally stratified into layers with different densities, corresponding to the temperature increase from the ground up to the ceiling. The air heated by lamps starts to rise, forming a convective vertical cell, which develops u p w a r d s up to the warm air reaches the ceiling or another air layer with a lower d