2006 International Plumbing Code?
First Pr...
932 downloads
8180 Views
9MB Size
Report
This content was uploaded by our users and we assume good faith they have the permission to share this book. If you own the copyright to this book and it is wrongfully on our website, we offer a simple DMCA procedure to remove your content from our site. Start by pressing the button below!
Report copyright / DMCA form
sib,
A Member of the International Code Familya
NTERNAT 0N AL
$:E;T;L:
2006 International Plumbing Code?
First Printing: January 2006 Second Plintilig: March 2006
ISBN-1 3: 978- 1-58001-259-1 (soft-cover) ISBN- I 0: 1-58001 -259-0 (soft-cover) ISBN- 13: 978- 158001-258-4 (loose-leal) ISBN- 10: 1-58001-258-2 (loose-leaf] ISBN-] 3: 978- 1-58001-307-9 (e-document) ISBN- 10: 1-58001-307-4 (e-document)
COPYRIGHT6 2006 by
INTERNATJOYAL CODE COUNCIL, INC.
ALL RIGHTS RESERVED. This 2006 6zto-1~atioizalPluuzbitzg Codeo is a copyrighted work owncd by the International Code Council, Inc. Without advance wrjtten permission from the copyright owner, no part of this book rliay be rcprocluccd, distributed, or transmitted inany formorby any means, including, without limitation, electronic, opticalor mccha~licalmcans (by way ofexamplc, and not limitation2photocopying, or recording by or in an information storage retrieval system). For information on permission to use, please contact: Publications, 4051 West Flossmoor Road, Country Club Hills, LL 60478-5795. copy rnatcrial cxccecling Pho~lc1-888-LCC-SAFE (432-7233). 'li-ade~narlia:"International Code Council," the "Tnternational Code Council" logo and the "lntcrnational P1~111lblngCodc" arc trademark3 of the Intcmatlonal Code Council. tnc.
PRINTED IN THE U.S.A
PREFACE Introduction Internationally, codc officials recognize the need for a modern, up-to-date plumbing code addressing tlie design and installation of plumbing systctns thnjugh requirements emphasizing performance. The Ir'ten7ationc~lPlr~mbirigCoclele",in this 2006 edition. is designed to meet thcse nccds through ~nodclcodc regulations that safeguard the public health and safcty in all conlmunitics. large and small.. 'l'his comprchensivc plumbing code establishes minimum regulations for plumbing systems using prcscriptive and performancc-relatcd provisions, It is founded on broad-based principles that makc possible the use of new tnatcrials and ncw plumbing dcsigns. This 2006 edition is fully compatible with all the 11itenzci.tioilal code.^'" (I-Codes") published by the 1nternation;ll Codc Buildirzg CodeG),ICC Electriccrl Codecn,Irzter-riutionnl Erzer
Development The first cdition of the lr~ter-rlationulPlct~rzhi~~g Colf~(1995) was the culmination of an effort initiated in I994 by a dcvcloplncnt coiil~nittccappointcd by the ICC and consisting of representatives of the three statutory members of the International Cotic Council at that time, including: Building Officials and Codc Administrators International, Inc. (BOCA), International Co~lfercnceof Building Officials (1CB0) and Southcm Building Codc Congress International (SBCCI). Thc intcnt was to draft a comprchensivc set of regulations for plurnbing systenls consistent with and inclusive of thc scope of the existing n~odelcodes. Technical content of thc latest ]nodel codes pronlulgated by BOCA, ICBO and SBCCl was utilized as tlie basis for thc devclopnicnt. This 2006 edition prcscnts the code as origi~lallyissued, with changes as reflected i n the subsequent editions through 2003 ane with changes approved through the ICC Codc Development Proccss through 2005. A new edition such as this is promulgated every three years. 'l'his codc is foundcd on principles intcnded to establish provisions consistent with the scope of a plumbing code that adcc]uately protccts public hcalth. safety and welfare; provisions that do not unnecessarily increasc constluction costs; provisions that do not rcstrict thc usc of new materials, products or methods of construction; and provisions that do not give preferential trcatnlcnt to particular typcs or classes of materials, products or methods of construction.
Adoption Thc Irzrer~rz~~tio~~al Pl~inlhirigCmle is available for adoptio~rand use by jurisdictions internationally. Its use within a go\!ernmcntal jurisdiction is intcndctl to be acco~nplishcdthrough adoption by reference in accordance with proceedings cstablisliing the jurisdiction's laws. At thc time of adoption, jurisdictions sho~rldinsert the appropriate inforniation in provisions requiring specific local c hthc name of thc adopting jurisdictioi~.These locations arc shown in braclcctcd words in small capital lcttcrs in information, s ~ ~ as the cotlc and in the sample ordinancc. The sample adoption ordinance on page v addresses several licy elements of a code adoption ordinance. including the information rcttuired for insertion into thc codc text.
Maintenance The I~zt~rr~c~tiorral Pl1~1rzbir1g Code is kept up to date through thc review of proposed changcs submitted by codc enSo~-cingofficials, industry rcprescntatives, design professionals and other interested parties. Proposed changes are carefully cvnsidcrcrt through an open codc dcvelopnient proccss in which all interested and affected parties may participate. The content.; of this work are subject to change both through the Code Development Cycles and the governmc~ltalbotly that enact.; the code into law. For nlorc information regal-ding ~ h code c dcvelopnient process. contact the Code and Standard Devclopmcnt Departnlent of the International Code Council. While the dcvelopmcnt proccdurc of the lrlfer.tzatiolla1Pl~nnbingCode ensurcs thc highest ckgrec of care, ICC and ICC's Incmbers and those participating in the de\.elopment of this code do not accept any liability resulting from compliance or nonconipliancc with thc pl-cwisions,since ICC and its members do not have the power or authority to police or enforce compliance with the contents of this codc. Only the goverriniental body that enacts thc code into law has such authority. 2006 INTERNATIONAL PLUMBING CODE@
Letter Designations in Front sf Section Numbers In cach codc dcveloprrlent cycle, proposed changes to the code arc considered at the Code Developmen1 Hearings by the ICC Plu~nbingCodc Developnient Committee, whose action constitutcs arecommendation to the voting ruelllbership for final action on the proposed change. Proposcd changes to acode section that has a nunher beginning with a letter in brackcts are considered by a diffcrcnt code dcvclopment committee. For example, proposcd changes tc~code sections that have [B] in front of them (c.g. IB] 300.1,) are considered by thc ICC Building Code Development Committee at the code development hearings. are maintained by another codc developnicnt commitlec in The content of sections in this code that bcgin with a letterdesig~~ation accordance with thc following:
IB] [El (FI IM I
= International Building Code Development Committee;
= I~~tcrrlatiol~al Energy Conservation Code Development Committee: = International Fire Code Development Committee: = International Mechanical Code Dc\eloptnent Committee.
Marginal Markings Solid vcr~icallincs in thc margins within thc body of the code indicate a technical change from the requirements of the 2003 cdition. Deletion indicators in the form of an arrow ( I)) areprovidcd in the margin whcre an entire section, paragraph. cxccption or table has been delctcd or an item in a list of items or a table has been deleted.
2006 lNTERNATlONAL PLUMBING CODE@
ORDINANCE 'The I~~ter-rrcrtiotlal C'oclc..~arc dcsigncd and pr~u~n~~lgated to be adopted by refercnce by ordinancc. Jurisdictions wishing to adopt the 2006 hitc.rrtatio~tulPI~rnzOir~g Code as an enforceable regulation governing plumbing systems s h o ~ ~ensure ld that ccrtain factual ir~formationis included in the adopting ordinancc at the time adoption is being considered by the appropriale govcrnmcntal body. Thc following sample adoption ordinancc addresse,~several key elements of a codc adoption ordinancc. including the ir~fornlation rcquircd tor insertion into the code text.
SAMPLE ORDINANCE FOR ADOPTION OF THE INTERNABlONAL PLUMBING CODE ORDlNANCE NO. An ordinance of the [JURISDICTION1adopting the 2006 cdition of thc Iirler~zarionulPlrlr~zOirlgCode. regulating and governing thc design, construction. quality of materials, erection, installation, alteration, rcpair, location. relocation, rcplaccmcnt. addition to, use or niaintcnancc of plumbing systc~i~s in the [JURISDICTION]: providing for the issaancc of permits and collection of fees therefor; of the [JURISDICTION]and all other ordinances a n d p m s of the ordinances in conflict therewith. repealing Ordinance No. 7'hc [GOVERNING BODY] of the [JURISDICTION] does ordain as follows: Scction I .That a certain document, three (3) copies of which are on file in the office of the [TITLE OF JURISDICTION'S KEEPER OF RECORDS] of [NAME OF JURISDICTION]. being marked and designated as the Internotioilc~lPl~triibitzgCode, 2006 cdition, including .4ppcndix Chapters [FILL IN THE APPENDIX CHAPTERS BEING ADOPTED], as p~iblishedby the international Code Council, be and is the design, conlicreby adoptedas the Plumbing Code of the [JURISDICTION], in the State of [STATENAME] rcgulating and govcr~~ing struction. quality of materials, crcction, installation, alteration, repair, location, relocation, replaccmcnt, addition to, usc or maintcnancc of plumbing systems as hcrein provided: providing for-the issuance of pernlits and collection of fecs thcrcfor; and cach and all of the regulations, provisions, penalties, conditions and tcmis of said Plumbing Code on file in the office of the [JURISDICTION] :Ire hcrcby rcfcrrcd to, adopted, and made a part hereof, as if Sully sct out in this ordinance, with ihcadditions. insertions, clelctions and changes. if any, prescribed in Section 2 of this ordinance.
Section 2. The following sections arc hereby rcvised: Section 10 1.1. insert: [NAME OF JURISDICTION] Scction 106.6.2. Insert: [APPROPRIATE SCHEDULE] Section 106.6.3. Insert: [PERCENTAGES IN TWO LOCATIONS] Section 108.4. Insert: [OFFENSE, DOLLAR AMOUNT, NUMBER OF DAYS] Scction 108.5. Insert: [DOLLAR AMOUNT IN TWO LOCATIONS] Section 305.6.1. Inscrt: [NUMBER OF INCHES IN TWO LOCATIONS] Scction 904.1. Insert: [NUMBER OF INCHES]
Section 3. That Ordinancc No. of [JURISDICTION] entitled [FILL IN HERE THE COMPLETE TITLE OF THE ORDINANCE OR ORDINANCES IN EFFECT AT THE PRESENTTIME SO THATTHEY WILL BE REPEALED BY DEFINITE MENTION] and all othcr ordi~lances or parts of ordinances in conflict herewith are hereby repealed.
Section 4. 'That if any section, subsection, sentence, clause or phrase of this ordinance is. for any reason, held to be unconstitutional, such decision shall not affcct the validity of the remaining portions of this ordinance. The [GOVERNING BODY] hcreby dcclarcs that it would havepasscd this ordinance, and each scction. subsection, clause or phrase thereof, irrespective of the Pact that any one or morc sections, subsections. sentences, clauscs and phrascs be dcclared ~~nconstitutional. Section 5. That nothing in this ordinancc or in tile Plumbing Code hcreby adopted shall be constn~cdto affcct any suit or-proceeding impending in any court, or auy rights acquired, or liability incurred, or any cause or causes of action acquired orcxistinp, under any act or ordinancc hcrehy 1.epea1'd as cited in Section 3 ofthis ordinancc; nor sliall any j u a ~or legal right or rerncdy of ally character be lost, impaircd or affected by this ordinance. Section 6. That the [JURISDICTION'S KEEPER OF RECORDS] is hereby ordercd and directed to cause this o~dinancclo bc published. arid to specify that it is to bc (An additional provision may be required to dircct the number of times the ordinancc is to bc p~~blishctL in a ncwspapcr in gcncral circulation. Posting may also be rcquircd.) Section 7. That this ordinancc and thc rules, regulations, provisions, rcquirc~~ients, orders and matters cstablishcd and acloptcd hcreby shall take effcct and be in full force and effect [TIME PERIOD] from and after the date of its final passage and adoption. 2006 INTERNATIONAL PLUMBING CODE@
v
2006 INTERNATIONAL PLUMBING CODE@
TABLE OF CONTENTS CHAPTEIP 1 Section
ADMINISTRATION
...............1
405
Installation of Fixtures . . . . . . . . . . . . . . . . . . . . . 118
406
Automatic Clothes Washers . . . . . . . . . . . . . . . . .29
101
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
407
Bathtubs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
102
Applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
408
Bidets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
103 104
I>eparttnent of IJlunibing Inspection . . . . . . . . . . . . 2 Dutics and Powers of the Code Official . . . . . . . . . 2
409 410
Dishwashing hlachincs . . . . . . . . . . . . . . . . . . . . .30 Drinking Fountains . . . . . . . . . . . . . . . . . . . . . . . .?O Emergency Showers and Eyewash Stations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Pcrmits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Inspections and Testing . . . . . . . . . . . . . . . . . . . . . . 5
Floor and Trench Drains
Food Waste Grinder Units . . . . . . . . . . . . . . . . . . . Garbage Can Washcrs . . . . . . . . . . . . . . . . . . . . . . Lau11cl1-yTrays . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Violations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Mcails of Appeal . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
....................
Lavatories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Showers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
CIIAPTEH 2 DEFINITIONS 9 Scctioii 201 Gencral . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 102 General Definitions . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sinks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Urinals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Water Closets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
.......
CMAPTEK 3 GENERAL. REGULATIONS 17 Section 301 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 302 Exclusio~lof Materials Dctrilr~cntal to the Scwcr System . . . . . . . . . . . . . . . . . . . . . 17 303 Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 305
Rodcntproofing . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Prolcction of Pipes and I'lunlbing Systc~iiComponents . . . . . . . . . . . . . . . . . . . . .18
306
Trenching. Excavation 2nd R;~ckfill. . . . . . . . . . . 1S
307 308
Structllral Safety . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Piping Support . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
309
Flood Hazard Resistance . . . . . . . . . . . . . . . . . . . . 20
3 10 3 11 3 12 3 13
and Toilet Room Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Toilet Facilities for Workers . . . . . . . . . . . . . . . . . 21 Tests and Inspections . . . . . . . . . . . . . . . . . . . . . . . 21 7 -I Equipinent Efficiencies . . . . . . . . . . . . . . . . . . . . . --
3 14
Condcnsatc Disposal . . . . . . . . . . . . . . . . . . . . . . . 22
303
CtlAP'SEP< 4 FIX'I'UREY. FAUCETS AND FTX'FURE FITTINGS .............25 Scction 401 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 402 Fixture Materials . . . . . . . . . . . . . . . . . . . . . . . . . . 25 403 Minimllrn Plulnbing Facilities . . . . . . . . . . . . . . . 25 404 Accessible Plumbing Facilities . . . . . . . . . . . . . . . 28 2006 INTERNATIONAL PLUMBING CODE@
....................
Whirlpool Bathtubs . . . . . . . . . . . . . . . . . . . . . . . . 32 Health Care Fixtures and 13yuipme11t. . . . . . . . . . 32 Specialty Plumbing Fixturcs . . . . . . . . . . . . . . . . . 33 Faucets and Other Fixturc Fittings . . . . . . . . . . . .33 Flushing Devices for Watcr Closets and Urinals . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34 Manual Food and Beverage Dispensing Equipinelit . . . . . . . . . . . . . . . . . . . 34 Floor Siriks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
CHAPTER 5 WATER HEATERS ...............35 Section 501 Gcneral . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35 502 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 503 504 505
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Safety Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
CHAPTER 6
WXCEK SUPPLY A h U 1)ISTRIIRUTION ..................37
Section 601 Gcneral . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37 602
Water Required . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
603 604
Water Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Design of Building Watcr Distribution Systein . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Mntcrials, Joints and Conncctioiis . . . . . . . . . . . . 39
605
TABLE OF CONTENTS
lnstallntion of thc Building Water Distribution System . . . . . . . . . . . . . . . . . . . . . . 44
Com~llonVcnt . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Hot Water Supply System . . . . . . . . . . . . . . . . . . . 45
Waste Slack Vent . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Protection of Potable Water Supply . . . . . . . . . . . 46 Health Care Plumbing . . . . . . . . . . . . . . . . . . . . . . 50 Disinfccliorr of Potable Watcr System
. . . . . . . . . 51
Drinking Watcr Trcatrnent Urlits . . . . . . . . . . . . .51 Solar Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1 Temperature Control Devices and Valvcs . . . . . . 5 1 CHAPTER 7
SANITARY DKAINAGE ........... 53
Scction 701
Gcneral . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
702
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
703
Building Sewcr . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
704 705
Drainagc Piping Installation . . . . . . . . . . . . . . . . . 55 Joints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
706
Conncctions Between Drainage Piping and Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
707
Prohibited Joints and Connections . . . . . . . . . . . . 59
708 709
Cleanouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59 Fixture Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
7 10
Drainage System Sizing . . . . . . . . . . . . . . . . . . . . 60 Oft-sets in Drainage Piping in Buildings of Fivc Stories or More . . . . . . . . . . . . . . . . . . .60
711
Wet Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 Circuit Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Comhinntion Drain And Vent System . . . . . . . . . 72 Island Fixturc Ventiilg . . . . . . . . . . . . . . . . . . . . . . 72 Relief Vents-Stacks of More Than 10 Branch Intcrvals . . . . . . . . . . . . . . . . . . . . . .72 Vents for Stack Offsets . . . . . . . . . . . . . . . . . . . . . 73 Vent Pipc Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 Air Admittance Valves . . . . . . . . . . . . . . . . . . . . . 74 Engineered Vent Systcins . . . . . . . . . . . . . . . . . . . 75 Colnputcrized Vent Design . . . . . . . . . . . . . . . . . . 75
CHAPTER 10 TRAPS. INTEIZCEPTOKS AND SEPARATORS
................... 77
Section I001 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
1002 Trap Requirements . . . . . . . . . . . . . . . . . . . . . . . . .77 1003 Interceptors and Separators . . . . . . . . . . . . . . . . . . 77 1004 Materials. Joints and Connections . . . . . . . . . . . . 79
CHAPTER 11 STORM DRAINAGE
..............81
Section
7 12 7 13
Sumps and E-jectors . . . . . . . . . . . . . . . . . . . . . . . . 63
I101 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Mcalth Carc Plumbing . . . . . . . . . . . . . . . . . . . . . . 64
1 102 Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
7 14 7 15
Computcrizcd Drainage Design . . . . . . . . . . . . . . 65
1103 Traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82
Backwater Valves . . . . . . . . . . . . . . . . . . . . . . . . . .65
CHAPTER 8 Scction
INUIKEGT/SPECIAL WASTE
.....67
1104 Conductors and Connections . . . . . . . . . . . . . . . . X2 1105 Roof Drains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82 1106 Size of Conductors. Leaders and Storm Drains . . . . . . . . . . . . . . . . . . . . . . . . . . .82
801
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
1107 Secondary (Emergency) RooT Drains . . . . . . . . . . 89
$02
Indirect Wastes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Spccial Wastes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Materials. J o ~ n t sand Conncctions . . . . . . . . . . . . 68
1108 Combined Sanitary and Storm Systcrn . . . . . . . . . 00
803
804
..........................
CIIAVTEK 9 VENTS 69 Section 901 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 002 R/laterials. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69 ?03 Oucdoor Vent Extension . . . . . . . . . . . . . . . . . . . . 69 904 Vcnt Tcr~liinals. . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 905 Vent Co~lncctioncand Gradcs . . . . . . . . . . . . . . . . 70 906 Fixlure Vcnts . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70 007 Individual Vcnt . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
1109 Valucs for Continuous Flow . . . . . . . . . . . . . . . . . 90 1 110 Controlled Flow Roof Drain Systcn~s. . . . . . . . . 90 11 1 1 Subsoil Drains . . . . . . . . . . . . . . . . . . . . . . . . . . . .90 11 12 Building Subdrains . . . . . . . . . . . . . . . . . . . . . . . . 90 1 1 13 Sumps arrd Pumping Systems . . . . . . . . . . . . . . . .00
CHAPTER 12 SPECIAI, PIPING AN11 STORAGE SYSTEMS ............. 91 Section 1201 Gencr-al. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 1202 Medical Gases . . . . . . . . . . . . . . . . . . . . . . . . . . . .91 1203 Oxygen Systcins . . . . . . . . . . . . . . . . . . . . . . . . . . 01 2006 INTERNATIONAL PLUMBING CODE@
TABLE OF CONTENTS
CHAPTISR 13 REFERENCED STANDARDS
......93
APPEKDIX A PCliiMBING PEIZMIT FEE SCI-IEDULE 101 Permit Issunticc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 Unit Fcc Schcdulc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 Othcr Inspections and Fees . . . . . . . . . . . . . . . . . . . . . . . 101
.....................
APPENIIIX B RATES OF WAINF'A1.I. FOR \'AKIOUS CITIES
...............103
APPENDIX C GRAY WATER KECYCI. ING SYSTEMS 105 Scc~ion C101 Cicncrnl . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 C 102 Systems for Flushing Water Closets and Urinals . . . . . . . . . . . . . . . . . . . . . . . . . . . .105 C103 Subsurface Land\cape Irrigation Systems . . . . 106
......................
APPENDIX D DEGREE DAY AND DESIGN TEhlPER.4TURES
............... 111
APPKNDIX E SIZING OF WATER PIPING SYSTEM
.......................117
Section El01 Gcncral . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
El 0 2 Information Required . . . . . . . . . . . . . . . . . . . . . 117 E l 0 3 Selection of Pipe Slzc . . . . . . . . . . . . . . . . . . . . . 117 E201 Selection of Pipe Si7e . . . . . . . . . . . . . . . . . . . . 134
.........
APPENDIX F STKIJCTCWAI. SAFETY 137 Section FIOI Culting . Notching and Boring in Wood Mcinbcrs . . . . . . . . . . . . . . . . . . . . . . . . 137 APPENIlIX G VACIJIJMDRAINAGE SYSTERI INDEX
..139
.......................................141
2006 lNTERMATlONAL PLUMBING CODE@
2006 INTERNATIONAL PLUMBING
CODE^
CHAPTER 4
ADMINIISBRATION SECTION 101 GENERAL
The owncr or the owncr's dcsignatcd agent shall be responsible for ~naintcnanccof plumbing systcms. To clctcrminc con>101.1 Title. These regulations shall be known as thc h~trr-r~o- pliance with this provision. the code official shall h a w the authority to rcquire any plumbing systc~nto bc rcinspccted. tiolzal Phlrnhing Code of [ N A h E OF SURISDICTIOh] hereinafter refcrrcd to as "this codc." 102.4 Additions, alterations or repairs. Additions, altcrations, renovations or repairs to any plumbing system shall 101.2 Scope. The provisions of this code shall apply to the confonn to that requircd for a ncw plumbing system without erection, installation. alteration, rcpitirs, relocation, replacerequiring the cxis~ingplumbing systcm to coinply with all thc ment, addition to, use or ~iiaintenanccof plu~nbingsystcms requirements of this code. Additions. alterations or repairs within this jurisdiction. This codc shall also regulate nonflamshall not cause an existing system to become unsafe, illsanitary lnablc medical gas, inhalation anesthetic. vacuum piping, or overloaded. nonmedical oxygen systems and sanitary and condensate vacuum collection systcms. 7'he installation of fucl gas distribuMinor additions, alterations. renovations and repairs to tion piping and ecluipment. fuel-gas-fircd water heaters ant1 water hcater venting systems shall be regulated by thc I~zter~iu- existing pluinbing systems shall be pcrmittcd in the same manncr and arrangement as in the cxisting SYS~CITI, ~ J I - O Y that ~ ~ C rio~iulF~1c.lC;o.s Code. Provisions in the ztppcndiccs shall not such rcpairs or rcplacenicnt are not hazardous and are apply unless specifically adopted. approved. Exception: Detached onc- and two-family dwellings and 102.5 Chailge in occupancy. It shall be unlawful to make any multiple single-family dwellings (townhouses) not morc change in the occupancy of any structure that will subjcct the than thrcc stories high with separate means of egress and shall corr~plywith the 111rm1n- structure to any special provision of this codc witho~itapproval their accessory struct~~rcs of thc codc official. Thc code official shall certify that such iio~lalReside~ziiulCode'. e meets the intent OF the provisions of law govcrninp structure 101.3 Intent. Thc DurDose of t h ~ code s is to ~ r o v i d eminiinurn building construction for thc proposed ncw occupancy and that standartls to safegllarcl lifc or limb, health, pl-uperty and public such changc of occupancy does not rcsult in any hazard to thc wclfr~rcby regulating and controlling the design, construction, public health. safcty or welfare. inslallation, quality of materials, location, operation and maintenance or LISC of plumbing ccluiyment and systcms. 102.6 Historic buildings. The provisions of this code relating to the constn~ction.alteration, repair. enlargc~ncnt,restoration, 101.4 Severability.If any section, subsection, sentence, clause relocation or moving of buildings or structurcs shall not he or phi-asc of this codc is for any rcason held to be unconstitumandatory for existing buildings or structurcs idcntificd and tional, such decision shall not affect the validity of the remainclassified by the state or local jurisdiction as historic buildings ing portions of this codc. when such buildings or structures are judgcd by thc codc official to be safe and in the public interest of health, safety and welfare regarding any proposed construction, alteration, SECTION 102 repairi enlargement. restoration. relocation or moving of buildAPPLICABILITY ings. 102.1 Ccneral. The provisions of this codc shall apply to all
.
&
niattcrs affecting or relating to structures, as set forth in Section 101. Wherc, in any specific case, diffrrcnt sections of this code specify Jiffcrcnt materials, methods of co~~struction or othcr rcq~~ircinents, the most restrictive shall govern.
102.2 Existing installatio~ls.Plumbing systems Iawf~illyin existence nt thc tilnc of the adoption1 of this codc shall be pernlittcd to havc thcir use and maintenance continucd if the use, mainrcnnncc or rcpnir is in accordance with the original design and no hazard to life. health or property is created by snch plumbing S Y S ~ C I T ~ . 102.3 blaintenance. All plumbing systems. materials and appurtcnanccs, both existing and new, and all parts thereof, shall bc maintained in proper operating condition in accortl;~nccwith the original design in n safe and sanitary condition. All dcviccs or safeguards rcquired by this code shall be nuaintained in conipli~uicewith thc code editior~under which they M I C ~ Cinstalled. 2006 INTERNATIONAL PLUMBING CODE@
102.7 Moved buildings. Exccpt as dctermincd by Section 102.2, plumbing systems that arc a part of buildings 01- structures moved into or within the jurisdiction shall co~nplywith the provisions of this code for new installations. 102,8 Referenced codes and standards. The codcs and standards referenced in this codc shall hc thosc that arc listed in Chapter 13 and such codes and standards shall bc considcrcd as part of the requirements of this codc to the prescribed cxtcnl of each such reeference. Whcre the diffcrcnces occur between provisions of this code and the rcfcrcnccd standards, tlic provisions of this code shall be the ~ninimumrequircmcnts.
102.9 Requirements not covered by codc. Any rcq uircmcnts necessary fol- thc strength, stability or propcr operation of an cxistingor proposcd plumbing systcnl, or for the public snfcty, hcalth and gencral welfarc. not specifically covcrcd by this code shall be detern~inedby the code official.
~
SECTION 103 DEPARTMENT OF PLUMBING INSPECTION
permits have bcen issued. and enforce conipliancc with [he provisioris of this code.
103.1 General. Thc tlcpartrnent of plumbing inspection is hcreby creatcd and thc executive official in ctiargc thcreof shall be I C ~ O W I Ias the code official.
104.4 Inspections. The code official shall makc all the requircd inspections, or shall accept reports of inspcctioll by approvcd agencies or individuals. All reports of such inspcctions ahall be in writing and be certified by a responsible officcr of such approved agency or by the responsible individual. The code official is authorized to engage such expert opinion as deer~iednecessaql to report on unusual technical issucs that arise, subject to the approv;~lof the appointing authority.
103.2 Appointment. Thc code official shall be appointed by the chicf appointing authority of the jurisdiction, and thc code official shall not bc removed from office except for cause and aftel fill1 opportunity to be heard on specific and relevant charges by and before the appointing authority. 103.3 Deputies. In accordance with the prescribed procedures of this jur~sdictionand with the concumcnce of the appointing autho~itq,~ h codc c official shall have the authority to appoint a deputy codc official, other related technical officers, inspcctors and other etnployees.
103.4 Liability. The code oflicial, officcr or employee charged will1 the enforcement of this code, while acting for the jurisdiction. shall not thereby he rendered liable personally, and is hcrcby rclievcd from all personal liability for any damage accruing to pcrsons or property as a result of any actrequired or pcrnmitted in the discharge of ofticial tiuties. Any suit instituted against any officer or employee because of an act pel-formcd by that officcr or employee in the lawful discharge of dutics and under the provisions of this code shall bc defended by the legal representative of the jurisdiction until thc final termination of thc proceedings. The code official or any subordinate shall not be liable for costs in any action, suit or proceeding that is instituted in pursuance of the provisions of this code. and any officer of the department of plumbing inspection, acting in good faith and without malice, shall be frce from liability for acts performed i~nderany of its provisions or by reason of any act or omission in the performance of official duties in connection therewith.
1.04.5 Right of entry. Whenever it is ncccssary to makc an inspection to enforce the provisions of this code, or whenever thc code official has reasonable cause to bclievc that thcre exists in any building or upon any premises any conditions or violations of this code that make the building or premiscs unsafc, insanita~y,dangerous or hazardous. thc code official shall havc the authority to enter the building or prc~nisesat all reasonable times to inspect or to perfom? the duties imposcd upon the codc ofticial by this code. Jf such building or premises is occupied, the code official shall prcsent crctlentials to the occupant and request entry. If such building or prcinises is unoccupied, the codc official shall first makc a reasonable effort to locate the owner or other person having charge or control of the building or prerliises and request cl~try.If entry is refused. the code official shall havc rccoursc to every rcmcdy provided by Jaw to secure entry. When the code official shall have first obtaincd a propcr inspection warrant or other remedy provided by law to secure or entry, no owner or occupant or person having charge. ~211-e control of any building or prcrnises shall fail or ncglcct. after proper request is made as herein providcd. to PI-0111ptlypermit entry therein by the code official for the purpose of inspection and examination pursuant to this code.
104.6 Identificalion. The codc official shall carry propcr identification when inspecting structures or premiscs in thc performance of duties under this code.
SECTION 104 DUTIES AND POWERS OF THE CODE OFFICIAL
104.7 Notices and orders. Thc code official shall issue all nccessary notices or orders to cnsure compliance with this codc.
104.1 General. The code ofticial shall enforce all of the provisions of this code and shall act on any question relative to the installation, altclxtio~l,repair. lnaintcnancc or operation of all plunlbing systems, devices and equipment except as otherwise specifically provided for by statuto~-yrequirements or as provitled for in Sections 103.2 tllrough 104.8.
104.8 Department records. The code official shall Bcep official records of applications received, permits and certificates issued, fees collected, reports of inspections, and noticcs and orders issucd. Such records shall be retained in thc official records as long as the building or structure to which such records relate remains in existence unlcss othcrwisc providcd for by other regulations.
104.2 Rule-making authority. The code ofticid shall have authority 21s neccssarjl in the interest of public health, safety and gcncral wclfare to ~itloptand promulgate rules and rcgulations to interpret and in~plemcntthe provisions of this codc to secure the intent thereof and to designate requirements applicable because of local climatic or other conditions. Such rules shall not ha1,e thc cffcct of waiving structural or fire performance requirements specifically provided for in this code, orof violating accepted engineering practice involving public safety. 104.3 Applirations and permits. The code official shall receive applications and issue permits for the installation and alteration of plu~nbing.inspcct thc premises for which such
SECTION 105 APPROVAL
105.1 Modifications. Whenever there are practical difficulties involvcd in carrying out the provisions of this code, the cotfc official shall have the authority to grant modifications for individual cases. provided the code ofticial shall first find that special individual reason makes the strict letter of this codc impractical and the motlification is in confornrity with the intent and purpose of this code and that such modification tlocs not lessen health, life and fire safety requircmcnts. The derails 2006 INTERNATIONAL PLUMBING CODE@
ADMINISTRATION
of action granting modifications shall be recorded and entered 111 Ilic tiles of the plumbing inspection dcpartnle:~t.
cate the direction of fionl. a11 pipe s i ~ c sp, a d c of horizontal piprng, loading, and location of fixtures and appliances.
105.2 Alteinative materials, methods and equipment. The provisions of this codc arc not intended to prevent thc installation of any ntaterial or to prohibit any method of construction not specifically prescribed by this code. provided that any such alternativc has becn approved. An alternative material or method of consti-uction shall he approved where the codc official finds that the proposed design is satisfactory and complies with the intent of the provisions of this codc, and that thc rnaterial, method or work offered is, for the purpose intended. at least the equivalent of that prescribed in this code in cluality. strength, effectiveness, fire resistance, durability and safety.
105.4.5 Design approval. Where the code official dctcrmines that thc alternative engineercd design confor~iisto the s the plumbing system shall be approvcd. intent of t h ~ codc, If the alternative enginccrcd design 1s not appro~cd,the code official shall notify thc registered design professional in writing, stating the reasons thereof.
105.3 Required testing. Whenever there is insufficient cvidcncc of compliance with the provisions of this codc, or evidencc that a inaterial or method does not conform to the rcquiremcnts of this codc, or inol-der lo substantiate claims for altcrnatc materials or methods, the code official shall have the autliority to r e q ~ ~ itcsts r e as evidenceof conlpliance to be made at IIO cxpcnse to the jurisdiction. 105.3.1 Test methods. Test methods shall be as specified in this codc or by other recognized test standards. In the absence of recognized and accepted test methods, the code official shall approve thc testing procedures. 105.3.2 Testing agency. All tests shall bc performed by arl approved agcncy. 105.3.3 Tcst reports. Rcports of tests shall be rctaincd by the code offic~alfor the period required for rctcntlon of public records. 105.4.4ltcrnatiue engineered dcsign. The design, documentation. inspection, testing and approval of an alternative enginccred design plun~bingsystem shall comply with Sections 105.4.1 through 105.4.6. 105.4.1 Design criteria. An alternativc engineercd design shall conform to the intent of the provisions of this codc and shall provide an equivalent level of quality. $trength, cffectivencss, fire resistancc, durability and safety. Material, equipment or components shall be designed and installed in accordance with thc manufacturer's installation instructions. 105.4.2Submittal.The registered design professional shall indicate on the permit application that the plumbing system is an alternative cngineercd design. The permit and permanent pcrmit records shall indicate that an alternative engineered dcsign was part of the approvcd installation. 105.4.3 'Fechnical data. The registered design professional shall subiiiit sufficient technical data to s~tbstantiatethe proposed altcrnativc engineercd dcsign and to prove that the performance mects the intent of this code. 105.4.4 Construction documents. The registered design professional shall submit to the codc official two complete sets of signed and sealed co~lstructiondocuments for the alternative cnginecretl design. The construction documents shall include floor plans and a riser diagram of the work. Wlicrc appropr-iatc. the construction documents shall indi2006 INTERNATIONAL PLUMBING CODE@
105.4.6 Inspection and testing. The alternative cngineercd design shall be tcsted and iiispccted in accordance with the requirements of Sections 107 and 312. 105.5 Material and equipment reuse. Materials. equipment and devices shall not be reused unless such cle~ncntsh a w becn reconditioned. tested, placed in good and proper working condition and approved.
SECTION 106 PERMITS 106.1 When required. Any owner, authorized apcnt or contractor who desires to construct. enlarge. altcr. repair. move, demolish 01-chargethe occupancy of a building or structure. or to crect, install. enlarge, alter, repair, remove, convcrt or rcplace any plumbing system, the installation of which is regulated by this codc, or to cause any such work to bc done, shall first maltc application to the code official and obtain the requircd permit for the work.
106.2 Excmpt work. The following work shall bc cxcrnpt froin thc recluiremenl for a pcrmit: 1. The stopping of leaks in drains. water. soil, waste or vcnt pipe provided, however. that if any concealed trap, drainpipe, water, soil, waste or vent pipe bcconics dcfective and it becomes necessary to rcmove and replace the sanic with nevY material, such work shall be considered as new work and a permit shall be obtaincd and inspection made as provided in this codc. 2. The clearing of stoppages or the repairing of lcalis in pipes, valvcs or fixturcs, and the reinoval and reinstallation of water closets, providcd such rcpairs do not involve or require the replaccmcnt or rearrangement of valves, pipcs or fixturcs.
Exemption from the permit requircmcnts of this codeshall not be deemed to grant authorization for any work to be donc in violation of the provisions of this codc or any other laws or ordinances of this jurisdiction.
106.3 Application for permit. Each application for a pcrnlit, with the required fee, shall be filed with the code official on n for-111furnihhed for that purpose and shall contain a general description of the proposcd work and its location. The application shall be signed by the owner or an authorized agent. The pcrmit application shall indicatc the proposed occupancy of all parts of thc building and of that portion of thc sitc or lot, if any, not covered by the building or structure anti shall contain such other information required by the codc official. 106.3.1 Construction documents. Construction documents, engineering calculations. diagranls and other such data shall be submitted in two or more scts with cacll appli-
ADMINISTRATION
cation fol-a prrn~it.The codc official shall reiluirc construction documents, cornputations and specifications to be prepared and designed by a registered design professional when required by state law. Cor~structiondocuments shall be drawn to scale and shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in dctail that thc work conforrns to the provisions of this code. Const~uctiondocuments for buildings more than two stories in height shall indicate where penetrations will be made for pipe, fittings and conlponcnts and shall indicate thc materials and n~cthodsfor maintaining reqnired str~lct ~ ~ rsafety, al fire-resistance rating and fireblocking.
Exception: The code official shall have the authority to waive the suhniisqic~nof col~structiondocumcnts, calculations or othcr data if the nature of the work applied for l i reviewing of constl-uction docu~ncntsis not is s ~ ~ cthat ncccssary to dctcrmine cornpliance with this code. 106.4 By whom application is made. Application for a permit e the person or agent to install all or part of any shall bc n ~ a d by plurubing systcm. Thc applicant shall meet all qualifications cstahlislied by statute, or by nllcs promulgated by this code, or by ordinance or by resolution. The full name and address of the applicant shall be statcd in the application. 106.5 Pcrn~itissuance. Thc application, construction documcnts and othcr data filed by an applicant for permit shall be reviewed by the code official. If the code official finds that tlie proposcd work confornls to the requireincnts of this code and all laws and ordinances applicable thereto, and that the fees spccificd in Section 106.6 have bcen paid. a permit shall be issucd to the applicant. 106.5.1 Approved construction documcnts. When the code official issucs tlie pentlit where construction documcnls are requil-cd, the construction documents shall be cndorsed i n writing and stamped "APPROVED." Such approvcd construction docunlents shall not be changed, nlodificd or altered without author-i~ationfrom thc codc official. All work shall bc done in accordance with the approvcd construction documents. Thc code official shall have the authority to issue a permit for the constr~tctionof a part of a plumbing system before the entire construction documents for the whole systcm lii~vcbeen subniitlcd or approved. provided adequate information and detailed statements have been filed coinplying with all pertinent requirements of this code. The holders of such permit shall yrocccd at their own risk w~thoutassurancc that the penuit for the entirc plumbing system will be grantcd.
106.5.2 Validity. The issuance of a permit or approval of construction documcnts shall not be construed to be a permit for, or on approval of. any violation of any of t l ~ cprovisions of this code or any other ordinance of the jurisdiction. No pcrmit presuming to give authority to violatc 01-cancel the provisions of this code shall bc valid. 'I'hc issuancc of a permit based upon constmction documents and other data shall not prevent thc code official from tlicrcaftcr requiring the correction of errors in said construction documcnls and othcr data or from preventing building
operations being carried on thcreunder when in violation of this codc or of other ordinances of this jurisdiction.
106.5.3 Expiration. Evcry perrnit issucd by tlic codc official ~uiderthe provisions of this code shall cxpirc by Iimitation and become null and void if thc work authorized by such pennil is not commenced within 180 days from thc date of such pennit. or if the work authorized by such pcrmi t is suspended or abandoned at any time aftcr the work is commenced for a period of 180 clays. Before such work can hc recommenced, a ncw permit shall hc first obtained and the fee therefor shall be one-half the aniouiit required for a new per~nitfor such work, providcd no c h ~ i ~ ~havc g e s been inade or will be madc in the original construction documents for such work, and provided further that such suspcnsion or abandonment has not exceedcd 1 year. 106.5.4 Extensions. Any pcrmittee I~oldingan unexpired permit shall have the right to apply for an cxtcnsion of thc lime within which the permittee will commence work under that permit when work is unable to bc comrnenccd within the time required by this section for good and satisfactory reasons. The code official shall cxtcnd the time for action by the permittee for a period not exceeding 180 days if thcrc is reasonable cause. No permit shall be extended morc than once. The fee for an extension sliall be onc-half the a~nount required for a ncw permit For such worli. 106.5.5 Suspension or revocation of permit. 'I'hc code official shall revoke a permit or approval issucd under thc provisions o17thiscode in case of any false statement or misrepresentation of fact in the application or on the construction docuilients upon which tlie pennit or approval was based. 106.5.6 Retention of construction documents. One set of construction documents shall bc retained by thc codc ofticia1 until final approval of the work co\rcrt.d therein. One set of approvcd construction docurnents shall bc rcturned to thc applicant, and said set shall be kept on thc site of the builtling or work at all tiines during which thc work authorized thereby is in progress. 106.6 Fees. A perinit shall not bc issuetl until tlic tees prcscribed in Section 106.6.2 havc bcen paid, and an arncndincnt to a per~ilitshall not be released until the additional fce. if any, due to an increase of the plunlbing systems, has been paid. 106.6.1 Work comrne~lcingbefore permit issuance. Any person conui1ences any work on a plumbing systenl beforc obtaining the necessary pern~itsshall bc sul3jcct to 100 percent of the usual permit fcc in addition to the required p e ~ m i fees. t
106.6.2 Fee schedule. The fees for all plumbing work shall bc as indicated in tlie following sclicdule: [JUKISDJCTION TO INSERT I\PPRC)I'RII\TI: SCI-IElICldi]
106.6.3 Fee refunds. The code official shall authorize the refunding of I'ees as iollows: I . The full amount of any fee p a d hcrcunder that wa\ crroncously paid or collccted. 2006 INTERNATIONAL PLUMBING CODE@
2. Not Iliorc than [SPECIFY PERCEKTAGE percent of the pernlit fee paid whcn no work has becri done undcr a permit issued in accord:mce with this code.
3. Not 111ore than
[SPECIR PERCENTAC;E~percent of the plan rcvicw fee paid whcn an application for a permit for which a plan review fce has bcen paid is withdrawn or canceled before any plan revicw effort has bcctl expended.
Thc codc official shall not authorize the refunding of any fee paid except upon writtcn applicatioll filedby the or~ginal permittee not later than IS0 days after the date of fee payment.
SECTION 107 INSPECTIONS AND TESTlNG 107.1 Required inspections and testing. Thc code official, upon notification from the permit holder or the permit holder's agcnt, shall make the following inspections and such other inspcctio~lsas neccssary. and shall either release that portion of the construction or shall notify the permit holder or an agent of any violations that nmst bc corrccted. The holder ofthe permit shall be responsible for the scheduling of such inspections. I . Undcrgro~~nd inspcction shall he made after trenches or ditches arc excavated a l ~ dbedded. piping installed, and bcforc any backfill IS put in place. 2. Rough-in inspection shall be made after the roof, f r m ing, fi~cblocking,firestopping, draftstopping and bracing is in place and all sanitary, stol-m and water distribution piping is roughed-in, and prior to the installation of wall or ceiling membranes.
3. Final inspection shall be made nitcr the building is complete, all plumbing fixtures arc in place and properly connectcd. and the structure is ready for occuancy.
107.1.1 Approved agencies. Test rcports submitted to the codc official for consrdcratron shall be developed by approved agcncics that have sat~sficdthe requirements as to qualitication\ and reliability. 107.1.2 Evaluation and follow-up inspection services. Prior to the approval of a closed, prefabricated pl~unbing systcln and the issuance of a plumbing permit, the code official shall require the submittal of an evaluation report on each prcfabricatcd plu~nbingsystcm indicating the cornplctc details of the plumbins systcm, including adescription ot the systeln and its components, the basis upon which the plumhing systcm is being cvaluatcd, tcst results and similarinformation, and other data as neccssary for the codc official to dclc~mincconforlnancc to this code. 107.1.2.1 Evaluation service. The codc ofticial shall des~gnatcthc evaluation aervice of :III approved agency as thc c\~aluationagency, and review such agency's evaluation report for adccluacy and conformance to thts codc. 107.1.2.2 Follow-up inspcction. Except where ready acccss is provided to all plu~nbingsystems, servicc cquipmcnt and acccssolies for complcte inspectio~~ at the sitc without disassembly or dismantling, the code official shall conduct thc frequency of in-plant inspections nec2006 INTERNATlONAL PLUMBING CODE@
essary to ensure confo1711anccto lhc approved cvalu:ltion report or shall dcsignate an indcpcndcnt, approved inspcction agency to conduct such inspcctions. Thc inspection agency shall furnish the code official with the follow-up inspection manual and a rcport of inspcctions upon request, and the plumbing systeln shi~llhnvc all identifying label permanently affixcd to the systcm indicating that factory i~lspectionshave becn performed.
107.1.2.3 Test and inspcction records. All requircd tcst and inspection records shall be availaiblc to the codc official at all timcs d u r ~ n gthe fabrication of the plumbing system and the erection of the building. or such records as the code official designates shall be filed. 107.2 Special inspections. Special inspcctions of altcrnativc engineered design plumbing syhtc~nsshall be conducted in accordancc with Scctions 107.2.1 and 107.2.2. 107.2.1 Periodic inspection. The registered dcsign professional or designated inspector shall periodically inspcct and observe the alternative enginecred design to ctcterminc that the installation is in accordance with thc approved construction documents. All discrepancies shall bc brought to the i~nlnediatcattention of thc plulnbing contractor for correction. Records shall be kept of all inspections. 107.2.2 Written report. Thc rcgistercd dcsign profcssio~~~ll shall submit a fi nal report in writing to thc code official L I P ~ I I complctiou of the installation, certifying that the alternativc engineered design conforms to tlie approved construction documents. A notice of approval for thc plumbing systcln shall notbe issued until a wr~ittencertification has beell subnlitted. ~
-
107.3 Testing. Plumbing work and systems shall be tcsted as req~rircd in Section 312 and in accordance with Sections 107.3.1 through 107.3.3. Tests shall be made by the permit holder and observed by the codc official. 107.3.1 New, altered, extended or repaired systems. New plumhing systems and parts of existing systc~usthat have been altered, cxtcnded or repaired shall be tested as prescribe~lI~ercinto disclose leaks and dcfccts, esccpt that tcsting is not requircd in the following cases: 1. In any case that does not include addition to, rcplacement. alteration or relocation of any water supply, drainage or vent piping. 2. In any case whcrc plumbing ccluipn~cntis sct up tem-
porarily for exhibition purposes.
107.3.2 Equipment, material and labor for tests. All ecluipment, material and labor required for tcsting a plumbing system or part thereof shall bc furnished by thc pcrn~it holdcr. 107.3.3 Reinspection and testing. Whcrc any work (11. installation docs not pass any initial tcst or inspection. the neccssary corrections shall be nudc to con~plywith this code. The work or installatio~ishall then he i-csubmittcd to the code official fcx inspection and testing. 107.4 Approval. After the prescribed tests and inspections indicate that the work complies in all I-cspoctswith this codc, a notice of approval shall be issued by the codc official.
ADMINISTRATION
107.5 Temporary connection. The code official shall havc the authority to authorize the temporary connection of the building or system to thc i~tilitysource fos thc purpose of testing plumbing systems or for use undcr a temporary certificate of occupancy.
unlawful construction or to restrain, correct or abatc LI violation. or to prevent illegal occupancy of a building. structure or premises, or to stop an illegal act. conduct. business or utilization of the plumbing on or about any premises.
SECTION 108 VIOLATIONS 108.1 Unlawful acts. It shnll be unlawful for any pcrson, firm or corporation to erect, construct, alter, rcpair. remove, demolish or utilize any plumbing system; or cause same to be done, in contlict with or in violation of any of the provisions of this codc.
108.7 Unsafe plumbing. Any plumbing I-egulatcdby this codc that is unsafe or that constitutes a lire or health hazard, insanitary condition, or is otherwise dangerous to human lifc is hereby declared unsafe. Any use of plu~nbingregulated by this code constituting a hazard to safety, health or public welfare by reason of inadequate maintenance, dilapidation, obsolcscc~~ce, fire hazard. disaster, damage or abandonment is hcrcby declared an unsafe use. Any such unsafe cquip~ncntis hereby declared to be a public nuisance and shall be abated by rcpair, rehabilitation, demolition or renioval.
108.2 Notice of violation. The code official shall serve a notice of violation or order to the person responsible for the erection. installation, alteration. cxtcnsion, repair, removal or dcmolition of plumbing work in violation of the provisions of this codc, or in violation of a detail statement or the approved constriction docunlcnts thcreundcr, or in violation of a permit or ccltificate issued under the provisions of this code. Such order shall dirccr the disco~ltinuanceof the illegal action or condition and thc abatc~nentof the violation.
108.7.1 Authority to condemn equipment. Whencver the code official tictcrmincs that any plumbing, or portion thercof. regulated by this codc has bccomc hazal-tlousto life, health or property or has become insanitary, the codc official shall ordcr in writing that such plumbing either be removed or restored to :I safe or sanitary condition. A time limit for compliance with suchorder sh;~llbc specificdin the writtcn notice. No pcrson shall use or maintain dcfcctivc plumbing after receiving such noticc.
108.3 Prosecutionof violation. If thc notice of violation is not complicd with promptly, the code official shall request the legal counscl of the jurisdiction to institute the appropriate proceeding at law or in ecluity to restrain. correct or abate such violation, or to require the removal or termination of the unlawful occupancy of thc structurc in violation of the provisions of this code or of the ordcr or direction made pursuant thercto.
When such plumbing is to be disconnectcd. writtcn notice asprescribed in Section 108.2 shall be given. In cascs of immediate danger to life or property, such discon~~cction shall be made immediately without such noticc.
108.4 Violation penalties. Ally person who shall violate a provision of this code or shall fail to comply with any of the requirements thereof or who shall erect, install, alter or repair plumhing work i l l violation of the approvcd construction documents or directive of the code official, or of a pennit or certificate issucd under the provisions ofthis code, shall be guilty of a [SPECIFY OFFENSE]. punishable by a fine of not more than [AMOUNT] dollars or by irnprisonmcnt not exceeding [NUMBER OFDAYSI~ or both such f i ~ and ~ e imprisonment. Each day that a violation c o ~ ~ t i i ~ after u c s due notice has bcen served shall be deemed a separate offcnse. 108.5 Stop work orders. Upon notice from the codc oficiall work on any plumhing systein that is being done contrary to the provisions of this code or in a dangc~.ousor unsafe marlncr shall i~nn~ctliately ccasc. Such notice shall be in writing and shall be given to the owncr of thc property. or to the owner's agent, or to the person doing the work. The noticc shall state the conditions under which work is authorized to resume. Where an cmcrgency cxists, the code official shall not be required to give a writtcn notice prior to stopping the work. Any person who shall continue any work in or about the structurc after having bcen served with a stop work order, except such work as that person is directed lo perform to rclnove a violation or unsafe condition,shnll bcli:~bleto a fine of not less than [AMOUNT] dollars or nlorc than (,\h40r.iNT\ dollars.
108.6 Abatement of violation. The i~nposilionof the penalties herein prrscribcd shall not preclude the lcgal ofticcr of the jurisdiction from instituting appropriate action to prevent
108.7.2 Authority to disconncct service utilities. The codc official shall have the authority to authorize disconnection of utility service to the building. structurc or system rcgulated by the technical codes in case of an crnelgcncy, where necessary, to eliminate an immediate danger to lifc or property. Where possible, the owncr and occupant of the building, st~ucturcor service systcrn shall bc notified of thc decision to disconnect utility scrvicc prior to taliing such action. If not notified prior to disconnecting, the ourncr or occupant of the building. structure or scrvicc systclns shall be notified in writing, as soon as practical thcrcaftcr. 108.7.3 Connection after order to disconnect. No pcrson shall make connections from any energy. fuel, power supply or water distribution system or s ~ ~ p pcncrgy, ly fuel or water to any equipment regulated by this code that has been disconnected or ordered to bc discunncctcd by the code official or the use of which has been ordered to be discontinued by the code official until the codc official authorizes the rcconncction and use of such equipment. When any plumbing is maintained in violation of this codc, and in violation of any noticc issued pursuant to the c official s1i;lll institute any provisions of this section, t l ~ codc appropriate action to prevent, restrain, correct or abatc the violat~on.
SECTION 109 MEANS OF APPEAL 109.1 Application for appeal. Any person shall havc the right to appcal a decision of the codc official to thc board of appeals. An application for appcal shall be based on a claim that thc true 2006 INTERNATIONAL PLUMBING CODE@
ADMINISTRATION
intcnt of this code or the nrlcs legally adopted the]-eundcr havc becn incorrectly intcrpretcd, the provisions of this code do not fully apply. or an cqually good or better form of construction is proposed. The application shall be filed on a form obtained from thc code official within 20 days after the notice was served.
109.2 Men~bershipof board. The board of appeals shall conrs by the chicf appointing autliorsist of fivc ~ n e ~ n h eappointed ity as iollows: one for 5 ycars, onc for 4 years. one for 3 years. one for 2 years and one for 1 year. Thereaftel; each new mellibcr shall scrvc for 5 years or until a successor has been appointed. 109.2.1 Qualifications. The board of appeals shall consist of fivc indi~~iduals. one from each of the following professions or disciplines: 1. Registered design professional who is a registered architect: or a builder or superintendent of building construction with at least 10 years' experience, 5 years of which shall have bcen in responsible charge of work.
2. Registered dcsigri professional with structural cngineering or a~chitecturalexperience. 3. Registered dcsign professional with mechanical and plumbing cnginecring experience; or a mechanical and plumbing contractor with at least I0 years' cxpcI-icnce,5 ycars of which shall have been in responsible charge of work.
4. Registered design professional with electrical engineering cxpcrience; or an electrical contractor with at lcast 10 ycars' experience, 5 years of which shall have bcen in responsible chargc of work. 5 . Rcgiste~.ectdcsig~iprofessional with fire protcction engineering cxpcrience; or a fire protection contractor with at lcast 10 years' experience, 5 years of which shall havc becn in responsible charge of work.
109.2.2 Alternate members. The chief appointing aurhority shall appoint two altclnaic mcmbers who shall bc callcd by thc board chairnian to hear appeals during the absence or disqualification of a n~cmber.Alternate mcmbers shall possess the rlualifications required for board ~ncnlbership.and shall bc appointed for 5 ycars or until a successor has been appointed. 109.2.3 Chairman. The board shall annually select one of its mc~riberxto scrve as chairman. 109.2.4 Disqualification of mernber. A mc~nbcrshall not hcar an appeal in which that member has any pcrsonal, profcssional or fillancia1 interest. 109.2.5 Sccret:lry. Thc chicf administrative officer shall designate n qualified clerk to serve as secretary to the Imard. The sccrctary shall filc a detailed record of all proceedings in the officc of the chief administrative officer.
109.2.6 Compensation of members. Compensation of members shall I>cdetermined by law. 2006 INTERNATIONAL PLUMBING CODE@
109.3 Notice of meeting. The hoard 5hnll mcct upon noticc from thc chairman. within 10 days of the tiling of an appcal or at stated periodic meetings. 109.4 Open hearing. All hearings before thc board shall bc open to the public. 'l'he appellant, the appellant's reprcsentative, thc code official and any pcrson whose interests are affected shall he givcn an opportunity to be hcard. 109.4.1 Procedure. The board shall adopt and makc available to tlie public through the secretary proccdul-cs under which a hearing will be conducted. Tile proccdurcs shall not require compliance with strict rules of cvidencc, but shall mandate that only relevant infor~nationbe received.
109.5 Postponed hearing. When five niemhcr~are not przwnt to hear an appeal. either the appellant or the appcllant's reprcsentative shall have the right to request a postponement of the hearing. 109.6 Board decision. The board shall modify or reverse the decision of the codc official by aconcurring of thrcc mcmbcrs.
109.6.1 Resolution. The decision of the hoard shall hc by resolut~on.Certified copies shall be f~irnisliedto the appellant and to the codc official. 109.6.2 Administration. The code official shall takc i~nmediatc action in accordance with the dccision of the board. 109.7 Court review. Any person, whether or not a previous party of thc appeal, shall have the right to apply-to the appropriate court for a writ of certiorari to correct crrors of law. Application for review shall be made in the manner and timc required by Inw following the filing of the dccision in thc officc of the chicf administrative officer.
2006 INTERNATIONAL PLUMBlNG CODE@
CHAPTER 2
SECTION 201 GENERAL
waste pipe and the flood level rim of the receptacle into which the waste pipc is discharging.
201.1 Scope. Unless otherwise expressly stated, the following words and terrns shall, for the purposes of this code, have the ~nea~iings shown in this chapter.
AIR GAP (Water Distribution System). The unobstructed
201.2 Interchangeability. Words stated in thc present tense include the future; words stated in the masculine gender ~ncludcthe feminine and neuter; the singular number include5 the plural and the plural thc singular.
vertical distance through the free atmosphere between thc lowest opening from any pipc or faucet >upplying water to a tank, plurr~bingtixtuie or other dev~ceand thc flood levcl rim of thc receptacle.
A1,TERNATIVE ENGINEERED DESIGN. A plumbing system that perfo~msin accordance with the intent of Chapters 3 through 12 and provides an equivalent levcl of perforrnar~ce 201.3 Terms defined in other codes. Where terms are not defined in this code and are defined in the Tntpniatiorzal B ~ ~ i l d - for the protection of public healtli, safety and wcll'are. The system dcsign is not specifically regulated by Chapters 3 through iizg COIILJ, Ii~teu~u~io1zu1 Fire Code: ICC Electricul Code, Inter12. rlniior~ul/"LLL'~ GUSCode ortheInrerilaliorz~l1Mecl~ctrzicalCode, sucll terms shall have thc meanings ascribed to thern as in thosc ANCHORS. See "Supports." coclcs. ANTISIPHON. A tern1 applied to v a l ~ e sor mechanical 201.4 Ternis not defined. Where terms are not defined dcviceh that elirninatc siphonage. through the rncthodh authorized by this section, such terms shall have ordinarily accepted ~ncaiiiilgssuch as the context APPROVED. Acceptable to the codc official or other n11t11or- I ity having jurisdiction. i~~iplies. SECTlQN 202 GENERAL DEFINITIONS ACCICPTED ENCINEEKING PRAC'TICE. That w h ~ c h conforms to acccptccl principles. tcsts or standard3 of nationally recogni7ed technical or scientific authorities.
ACCESS ('SO). That which enables a fixture, appliance or ecluip~r~cnt to be reached by ready access or by a ineans that first rccluircs the ~.cmov:ilor inovclncnt of a panel, door or similar obstruction (see "Ready :~cess").
ACCESS COVER. A relnovablc plate, usually secul-cd by it to a pipe or pipe fitting for the bolts or screws, to ~ ) e r ~ naccess purposes of inspection, repair or cleaning.
ADAP'TIICR FIT'I'ING. An approted co~lncctingdevice that
APPROVED AGENCY. An established and recognized agency approvcd by the code official and that is regularly engaged in conducting tests or f~imishinginspcctio~~ services.
AREA DRAIN, -4 receptacle designed to collcct surface or storm watcr from an open area.
ASPIRATOR. A lilting or dcvice supplied with watcr or other fluid under positive pressure that passes through an intcgnll orifice or constriction, causing a vacuum. Aspirators are also I-efcrrcclto as suction apparatus. and are similar in ol~crationto an ejector.
BACKFI,CIW. Pressirre creatcd by any means in tlic water distribution system, which by being in excess o f ~11cprcssure in the water supply mains causes a potential backflow condition.
suitably and properly joins or adjusts pipes and fittings which do not otherwise fit together.
Backpressure, low head. A pressure less than o r equal to 4.33 psi (29.88 kPa) 01- the pressure cxcrtcd by a 10-f'oot (3048 mni) column of watcr.
AIR ADMITTANCE VALVE. One-way valve designed to
Backsiphonage. The backtl'low of potentially conta~ninatcd
allow air to enter the plumbing drainagc system wlic~inegative pressures develop in the piping system. The device shall close by gravity and seal the vent terminal at zero differential prcssure (no flow contlitions) and under positive internal pressures. The purpose of an air admittance valve is to provide a method of allowing air to entcr the plumbing drainagc system without the usc of a vcnt extended to open air and to prevent sewer gases from escaping into a building.
AIR BREAK (Drainage System). A piping arrangement in
water into the potable water system as a I-esi~lt of the prcssurc in the potable watcr system falling below atmospheric pressure of the plumbing fixtures. pools. tanks or vats connected to the potablc water distribution piping.
Backwater value. A device or valve installed in the building drain or sewer pipe where a sewer is subject to backflo\l: and which prevents drainagc or waste f i o ~ nbacking up into a low levcl or fixtures and causii~ga tlooding contlition.
which a drain from a fixture, appliance or dcvice discharges indilcctly into anothcr fixture, receptilclc or interceptor at a point below the flood levcl rim and above the trap seal.
Drainage. A re\crsal of flow in the drainagc sgstcm.
AlK GAP (Drainage System). The unobstructed vertical dis-
ble watcl- supply from any source cxccpt thc intended source.
tnrlcc through the free atmosphere between the outlct of the 2006 INTERNATIONAL PLUMBING CODE@
Water supply system. The flow of water or other liquids. mixtures or substances into the distribution pipes of a pota-
DEFINITIONS
BACKFLOW CONNECTION. Any arrangement whereby backflow is possible.
Storm. A building sewer that conveys stornl water or othcr drainage, hut not sewage.
BACKFLOW PIIGVENTEII. A device or means to prevent
BUII,D%NGSUBDIUIN. That portion of a drainage system
bacl
that does not drain by gravity into the building scwer.
BALL COCK. Sce "Fill valve."
BUILDING TRAP. A device, fitting or asscinbly of fittings
BASE FL001) E1,EVATION. A I-eferer~ce point, determined
installed in the building drain to prevent circulation of air between the drainage system of the building and the building sewer.
in accordance with the building code. based on the depth or peak elevation of flooding, including wave height, which has a 1 percent (100-year flood) or greater chance of occul-ring in any given year.
BATHROOM GROUP. A group of fixtures consisting of a watcr closet, lavatory, bathtub or showcr, including or cxcluding a bidet. an emergency tloor drain or both. Such fixtures arc locatcd together on the same floor level.
BEDPAN S'TEARIER 01%BOILER. A fixture utilized for scalding bcdpans o r urinals by direct application of steam or boiling watcr.
BEDPAN SrASHER AKD STERILIZER. A fixture designcd to wash bcdpans and to flush the contents into the sanitary drainage system. tncluded arc fixtures of this type that providc for disinfecting utensils by scalding with steam or hot water. BEDPAN WASHER HOSE. A device supplied with hot and cold water and locatcd adjacent to a watcr closet or clinizal sink to be utilized for cleimsing bedpans.
BRANCH. Any part of the piping system except a riser, main or stack.
BRANCH INTERVL4L.A vertical measurement of distance. 8 fcct (2438 m ~ n 01) more in developed length, between the corincctions of horizontal branches to a drainage stack. Measurcments arc taken down the stack from thc highest horizontal branch connection.
BRANCH VENT. A vent connecting one or more individu,iI vents with a vent stack or stack vent.
BUI1,DlNG. Any structure occupied or intended for supporting or sheltering a i y occupancy.
CIRCUIT VENT. A vent that connccts to a horizontal drainage branch and vents two traps to a niaximun~of eight traps or trapped fixtures connected into a battery.
CISTERN. A small covered tank for storing water for a home or farm. Gencrally, this tank stores rainwater to be utilized for purposes other than in the potal~lewater supply, and such tank is placed underground in most cases. CLEANOUT. An acccss opening in thc drainage system utilized for the removal of obstructions. Typcsof cleanouts include a removable plug or cap. and a removable fixture or fixture trap. CODE. These regulations. subsequent amendments tlicreto, or any emergency rule or regulation that the administrative authority having ju~isdictionhas lawfully adopted. CODE OFFICIAL. The officer or othcr designated authority charged with the administration and enforce~ncntof this code, or a duly authorized representatlvc. COMBINATION FIXTURE. A fixture conlhining one sink and lauridry tray or a two- or three-co~upartmentsink or laundry tray in one unit.
C O M B ~ A T I O NWASTE AND VENT sYsrrE:n4. A spccially designed system of waste piping e~nbodyingthe horizontal wet venting of one ormorc sinks or floor dl-ainsby rncans of a conimon waste and vent pipe adequately sized to providc free movement of air above the flow line of the drain.
COMBINED BUILDING DHABN. See "Building drain, combined."
COMBINED BUILDING SEWER. See "Buil(1ing sewc~-,
BIJJ1,DING DRAIK. That part of thc lowest piping ~ T L drainI
combined."
age system that receives the discharge from soil, waste and othcr drainagc pipcs inside and that extends 30 inches (762 mm) in developed length of pipe beyond the exterior walls of the building and conveys the drainage to the building sewer.
COMMON VENT. A vent connecting at the junction of two fixture drains or to a fixturc branch and scrving as a vent for both fixlures.
Combined. A building drain that conveys both sewage and stomi watcr or othcr drainage.
Sanitary. A building drain that conveys scwagc only Storm. A building drain that conveys storm water or other drainage, but not sewage.
BUIL1)ING SEWER. That part of the drainage systerl~tkdt extends from thc end of the huilding drain and conveys the discharge to a public scwer, private sewer, individual sewage disposal system or other point of disposal.
Combined. A huilcling scwcr that conveys both sewage and storm water or othcr drainage.
Sanitary. A building scwcr that conveys sewage only.
CONCEALED FOULING SURFACE. Any surface of a plumbing fixture which is not readily vis~blcand is not scoured or cleansed with each fixture operation. CONDUCTOR. A pipe inside the building that conveys stol.m water from the roof to a storm or conibined building drain. CONSTRUCTION DOCUMENTS. All of the written, graphic and pictorial tiocuments prepared or asselllblcd for describing the design, location a i d physical characteristics of thc clcments of the project necessary for obtaining a building permit. The construction drawings shall be drawn to an appropriate scale. CONTAMINATION. An ilnpairment of the cluality of the potable water that creates an actual hazard to the public hcallh 2006 INTERNATIONAL PLUMBING CODE@
thro~lghpoisoning or through the spread of disease by sewage, industrial fluids or wastc.
Storm. A drainage system that carries rainwater, surface watcr. s~ibsurfacewater and similar liquid wastes.
CIII'rICAI, LEVEL (C-I,). An elevation (height) reference point that deterrnines thc minimum height at which a baclcflow prcvcnter or vacuunl breaker is installed above the flood level rim of Lhc fixture or receptor served by the device. The critical lcvel is the elevation lcvcl below which there is a potential for baclcflow to occm.. If the critical level marking is not indicated on the dcvicc, the bottom of the device shall constitute the critical Icvel.
EFFECTIVE OPENING. The mininium cross-scctior~alarca at the point of water supply discharge, ~ncasuredor cxprossed in tc1-111~of ~ t l diameter c of acircle or, if the opening is not circular, the diameter of a circle of equivalent cross-section:ll arcn. For faucets and sirnilnr fittings. the effective opening shall be measured at thc s~nallestorifice in the fitting body or in the supply piping to the fitting.
C R O S S CONNECrrION.Any physical connection o r arrangement between two o t h e ~ ~ v i separate se piping systems, one of which contains potable water ant1 the other either water of unknown or questionable safety or steam. gas or chemical, whereby thcre cxists thc possibility for flow liom one system to the otller. with the direction offlow depc~~ding on the pressure differential between the two systems (see "Backflow"). DEAD END. A branch lcading ~ I - ~ IaI soil, I waste or vent pipe; a building drain; or abuilding scwcr, and terminating at adcveloped length of 2 fcet (6 10 mm) or more by mcans of a plug, cap or other closed fitting. DEI'TN O F WATER SEAL. The dcpth of water that would have to bc removed froin a full trap beforc air could pass through the trap. DESIGN P'1,OOD ELEVATIOK. The elevation of the "clcsign flood," including wave height, relative to the datum specified on the eornmunity's legally designated flood hazard map. DEVELOYEII LENGTH. The length of a pipeline measured along the centerline of thc pipc and fittings. DISCHARGE PIPE. A pipe that conveys thc discharges from plumbing f~xturesor appliances. DRAIN. Any pipe that carries wastewater or water-borne wastes in a building drainagc system. DRAINAGE FITTINGS. Type of fitting or fittings utilized in thc drainage systenl. DI-ainagcfittings are similar to cast-iron fittings, except that instead of having abell and spigot. drainage fittings are recessed and tapped to eliminate ridges on thc insidc of the installed pipe. DRAINAGE FIX'ITJRE UNIT Drainage (dfi~).A nlcasure of the probable discharge into the drainage system by various types of plumbing fixtures. The drainage fixture-unit value for a particular fixture dcpcnds on its volun1c rate of drainagc discharge, on the time duration of a single drainage operation and on the avcragc time between successive operations. DRAINAGE SYSTEM. Piping within a public or private premise that convcys sewage, rainwater or other liquid wastcs to a point of disposal. A drainage system does not include the mains of a public sc\vcr systcm or a private or public sewage treatment or disposal plant. Building gravity. A draiuagc system that drains by gravity into thc building sewer.
Sanitary, A drainagc systcm that carries scwagc and cxcludes stornm, surface and ground water. 2006 INTERNATIONAL PLUMBING CODE@
EMERGENCY FLOOR DRAIN. A floor drain that docs no[ receive the discharge of any drain or indirect wastc pipc. and that protects against damage f r u ~ naccidental spills, fixture overflows and leakage. ESSENTIA1,LY N O N T O X I C 'TRANSFER FLUIDS. Fluids having a Gosselin rating of 1, including propylcnc polydin~cthylsiloxanc; glycol; mineral oil; hydrochlorofluoro-carbon, chlorofluorocarbon and cnrhon refrigerants; and FDA-approved boiler watcr additives for steam hoilcrs. ESSENTIALLY TOXIC TRANSFER FLIJIDS. Soil, wastc or gray water and fluids having a Cosselin rating of 2 or Inore including ethylene glycol, hydrocarbon oils, am~noninrcl'rigerants and hydrazine. EXISTING INSTAL1,ATIONS. Any plumbing system regulated by this code that was legally installed prior to thc effcctivc date of this code, or for which a pcr~rlitto install has been issued. E'illJCET. A valve end of a watcr pipc through which water is drawn from or held within the pipe.
FILL VALVE. A water supply valve. opcncd or closed by Incans of a float or similar dcvice, utilized to supply water to a tank. An antisiphon fill valve contains an antisiphon dcvice in the form of an approved air gap or vacuum breaker that is an integral part of the fill valve unit and that is positioned on tlic discharge side of thc water supply control valve. FIXTURE. See "Plumb~ngtixturc." FIX'FCRE XRANCII. A dl3111berving two or mole fixtures that discharges to another drain or to a .;tack. FIXTURE D I U I N . The drain fi-om the trap of o fixt~lreto a junction with any other drain pipc. FIXTURE FITTIKG
Supply fitting. A fitting that controls the volumc and/or directional flow of water and is either attached to or acccssihle from a fixturc. or is uscd with an opcn or atmosphe~ic discharge. Waste fitting. A combination of co~nponcntsthat conveys the sanitary waste from the outlct of afixtu1.c to the connection to the sanitary drainage system. FlXTlJRE SUPPI,Y. The water supply pipc connecting a fixture to a branch water supply pipe or directly to a main watcr supply pipe. FLOOD LEVEL RIM. The edge ot the rcccptaclc from which watcr overflows.
DEFINITIONS
FLOOD HAZARD AKEA. The greater of the following two LlTCLIS:
1 . Thc arca within a floott plain subject to a 1-perccnt or grcatcr chance of flooding in any given ycar. 2. The area designated as a flood hazard arca on a community's flood hazard map or as olherwisc legally dcsignated.
FLOW CONTROL (Vented). A device installed upstream from the interceptor having an orificc that contl-01s the rate of flow through the interceptor and an air intake (vent) downstream from the orificc that allows air to be drawn into the flow strcam. FLOM' PRESSURE. The pre\sure in the water supply pipc near thc faucet or water outlct while the faucet or watcr oullct is widc open and flowing. F1,USH TANlC. A tank designcd with a GI1 valve and flush valve to flush thc contcnts of the bowl or usable portion of the fixture. FLUSWOnlETEli TANK. A device integrated within an air accumulator vcsscl that is designed to discharge a predctermined clua~itityof water to fixtures for flushing purposes. FLUSHOMETEK VALVE. A valvc attached to a pressurized watcr supply pipe and so dcsigned that whel~activated it opens thc linc for dircct flow into thc fixture at a ratc and quantity to operate the fixture properly, and then gradually closes to reseal fixturc traps and avoid watcr hammcr. GREASE INTERCEPTOR. A plumbing appurtenance that is installed in a sanitary drainagc system to intercept oily and grcasy wastcs h-om a wastcwaler dischargc. Such device has thc ability lo interccpt frce-floating fats and oils. GREASE-LADEN WASTE. Eftlucnt dischargc that is produccd from food processing, food preparation or other sourccs where grcasc, fats and oils enter automatic clishwatcr prerinse stations, sinks or other appul-tcnances. GREASE REMOVAL DEVICE, AUTOMATIC (GRD). A plumbing appurtenallce that is installedin the sanitary drainage system to intercept frce-floating fats, oils and grease from wastewater dischargc. Such a device operates on a time- or evcnt-contr-olled basis and has thc ability to remove free-floating fats. oils ancl greasc autoluatically witl~outintervention from thc user cxccpt for maintenance. GRIDDED WATER 1)ISTRJBUTION SYSTEM. A water distribution system where cvery waterdistribution pipe is intercnnnccted so as to provide two or more paths to each Fixture supply pipc. HANGERS. See "Supports." HORIZONTAL BRANCH DRAIN. A drainagc branch pipe cxtendi~lglaterally from a soil or wastc stack or building drain, wit11or without \~crtic:~l scclio~lsor branchcs, that receives the disd1ai.g~from twoor morc fixture drains or branches and conducts thc discharge to the soil or waste stack or to the building drain. HOHJZONTAI- PIPE. Any pipc or fitting that makcs an angle of less than 45 dcgrccs (0.79 rad) wit11 the horizontal.
HOT WATER. Water at a telnperaturc greater than or cyual to 110°F (43°C). HOUSE 'TRAP. See "Building trap." IKDIRECT WASTE PIPE. A wastc pipe that docs not connect directly with the drainage system, but that discharges into the drainagc systcm through an air break or air gap into a trap, fixture, receptor or interceptor. INDliVIDUAL SEWAGE DISPOSAL SYSTEM. A systc~n for disposal of domestic sewage by mcans of aseptic tank,ccsspool or mechanical treatment. designcd for utilization apart from apublic sewer to serve a single establishment or building. INDIVIDUAL VENT. A pipe installed to vcnt a f i x t ~ ~trap re and connects with thc vcnt system abovc thc fixture scrvctl or terminates in thc open air. INDIVIDUAL WATER SUPPLY. A watcr supply that scrvcs one or more families, and that is not an approvcd public watcr supply. INTERCEPTOR. A devicc designed and installeti to scpnratc and retain for re~noval,by automatic or ~nanualmeans. dclctcrious. hazardous or undcsirnblc matter fro111 liorn~alwastes, while permitting normal sewage or wastcs to dischargc into the drainage systcnl by gravity. JOINT Expansion. \i loop, return bend or relurn offsct that provides for the expansion and contraction in a piping systcm and is utilized in tall buildings or wherc there is a r a p ~ d change of te~npcrature,as in power plant?. stcam roollls a ~ ~ r i similar occupancies.
Flexible. Any joint betwecn two pipes that pelnl~t\onc pipc t or dcflect~onof to bc dcflccted or 111oved~ i l h o umovenlcnt the other pipe. Mechanical. See "Mechanical joint." Slip. A type of joint made by means of a washer or a qxcial type of packing compound in which one pipe 1s slippcd into the end of an adjacent pipe. LEAD-FLPEE PIPE AND FITTINGS. Containing not nioi-e than 8.0-perccnt lead. LEAD-FREE SOLDER AND F1,CIX. Containing not nlorc than 0.2-percent lead. LEADER. An cxtcrior drainagc pipc for conrcying stnrni water from roof or gutter drains to an approved mcans of disposal. LOCAL VENT STACK. A vertical pipc to which connections are made from the fixture sidc of traps and through which vapor or foul air is I-cmovedfrom thc fixturc or dcvicc utilixcd on bcdpan washers. MACERATING TOILET SYSTEMS. An asscmbly consisting of a water closet and sump with a macerating pump that is designed to collect, grind and pump wastcs fi-om thc water closet and up to two other fixtures conncctetl to thc sump. MAIN. The principal pipe artcry to which branchcs arc conncctcd. MANIFO1,l). See "Plumbing appurtenaiicc." 2006 INTERNATIONAL PLUMBING CODE@
DEFINITIONS
MECHANICAL JOINT. A cconcction between pipes, fittings, or pipes and fittings that is not screwed, caulked. threaded, soltiered, solvcnt cemented, brazcd or welded. A joint in which compression is applied along the centerline of the pieces bcingjoined. In some applications; the joint is part of a coupling, fitting or adapter. MEDICAI, GAS SYSTEM. The con~plctcsystem to corivey medical gases for dircct patient application from central supply systerils (bulk tanks, manifolds and medical air compressors), with pressure and operating controls, alarm warning systcrns, related components and piping networks extcriding to station outlet valves a1 patient use points.
MEDICAL VACUUlLl SYSTEMS. A systern consisting of central-vacuum-producirig e q u i p m e ~with ~ t przssure and opcrating controls, shutoff valves, alann-warning systems, gauges and a nctwoikof pipir~gextending lo and terminating with suitable station inlets at locations where patient suction may be requircd.
NONPOTABLE WATER. Water not safe for drinking, personal or culinary utilization.
NUISANCE. Public nuisance as known in conimon law or in eqnity jurispmdcnce; whatcvcr is dangerous to hurna~ilifc or detrinicntal to health: whatcvcr structure or premises is not sufiicicntly ventilated, scwcrcd, drained, cleaned or lighted, with respcct to its intcndcd occupancy; and whatcver rendcrs the air. or human food, drink or water supply unwholcsome.
OCCUPANCY. The purpose for which a building or portion thcrcoi is utilized or occupicd.
OFFSET. A combination of approved bends that makes two changes in direction bringing one section of the pipc out of line but into a line parallel with the othcr section. OPEN AIR- Outs~dcthe structure.
PLUMBING. The practice, materials and fixtures utilized in
P1,KJMBING FIXTURE. A rcccptaclc or dcvicc that is cither permanently or ten~porarilyconnected to the water distribution system of the prctnises and demands a supply of water therefrom: discharges wastewater. liquid-bornc waste mntcl-ials or sewage either directly or indirectly to thc drainage system of the premises; or requires both a water supply connection and a disdiarge to the drainage systc~nof the pl.cmiscs.
PLUMBIR'G SYSTEM. Includes the water supply and distribution pipes; plumbing fixtures and traps; water-treating or watcr-using ccluipment; soil, waste and vent pipes: and sanitary and storm sewers and buildilig drains; in addition to thcir rcspcctive conncctions, devices and appilrtenances within a structure or premises. POLLUTION. An impairrncnt of the quality of the potablc water to a degree that does not crcate a hazard to the public health but that does advcrwly and onrcaronal~lyaffcct thc acsthctic qualities of 911c~hpotablc watcr for domestic use POTABLE WKI'EK. Water frec from impurities prcsent in amounts sufficient to cause disease or harmful physiological ei'fccts and conforming to the bactcriological and chemical quality requircmcnts of the Public Health Servicc Drinking Watcr Standards or the regulations of the public hcalth authority having jurisdiction.
PRIVATE. In the classification of plumbing tixtur-es, "private" applies to fixturcs in residences and apartmerits, and to fixtures i n nonpublic toilet rooms of hotels and motels and similar installations in buildings where the plumbing fixtul.cs arc intended for utilization by a family or an individual.
PUBLIC OR PUBLIC UTILJZATION. In the classification of plumbing fixtul-cs, "pitblic" applies to fixturcs in general toiIct rooms of schools, gymnasiums, hotcls. airports. bus and railroad stations, public buildings, bars, public comfort stations, office buildillgs, stadiums, stor-es, restaurants and other installations where a number of fixtures arc installed so that their utilization is similarly unrestricted.
the installation, maintcnancc, extension a ~ alteration ~ d of all piping, fixtures, plumbing appliances and plumbing appurtenances, within or ad,jacent to any structure, in connection with sanitary drainage or storm drainage '~cilitics; vcnting systems; and public or private water supply systems.
PUBLIC' FVATEII MAIN. A watcr supply pipe for public uti-
P1,UMBING APPLIANCE. Any one of a special class of
READY ACCESS. That which cnablcs a fixturc, appliarlce or equipment to be directly reached without requiring the remov:~l or movement of any panel, door or similar obstruction and without the use of aportable laddcr, stcp stool or-similar dcvice.
plumbing fixtures irltended to perform a special function. lncludcd are fixtures having the operation or control dcpcndcnt on onc or more energized components, such as motors. controls, hcntiu;! clcments, or pressure- or tcrnperature-sensing elcmcnts. Such fixturcs ase manually adjusted or co~itrolledby the owncr or operator, or are operated automatically through one or morc of the following actions: a time cycle, a temperature range, a pressure range, a measurcd volmne or weight.
PLUMBING APPURTENANCE. A ~nanofacru~.ed dcvice, or an on-the-job assembly of compoprefabricated :~ssen~bly neut parts that is an adjunct te, thc basic piping systern and plumhing fixturcs. An appurtenance dcmands no additional watcr supply ant1 does riot add any discharge load to a fixture or to thc drainngc systcni. 2006 INTERNATIONAL PLUMBING CODE@
lization controlled by public authority.
QUICK-CLOSING \<4I,VE. A valve or f i ~ ~ ~that c e t closcs automatically when released manually or that is controlled by a mechanical means for fast-action closing.
REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTEK. A baclcflow prevention dcvicc consisting of two independently acting checkvalvcs, internally force-loaded to a normally closed position and scparatcd by an internicdiate chamber (or zone) in which thcre is an automatic relief mcans of vcnting to the atmosphere, interr~allyloadcd to a ~lornlally open position between two tightly closing shutoff valves and with a nicans for testing for tightness of the checks and opening of the relief mcans.
REGISTERED DESIGN PROFESSIONAL. An individual who is rcgistcred or licensed to practice professional architccture or engineering as defined by the statuto~yrequirc~ncntsof
DEFINITIONS
the professional registration laws of the state or j~lrisdictionin which t l ~ cproject is to be constructed.
RELIEF VALVE Pressure relief valve. A pressure-actuated valve held closed by a spring or other means and designed to relieve pl-essurc automatically at the pressurc at which such valve is set. Temperature and pressure relief (T&P) valve. A combination relief valve designed Lo [unction as both a temperature relief and a pressurc rclicf valve. a'enrperaturc relief valve. A temperature-actuated valve dcsigncd to discharge automatically at the temperature at which such valve is set. RELIEF VENT. A vent whose pnmary function is to provide circulation of air hctwecn drainage and vent systems. RIM. An unobstructed open edge of a fixturc. RISER. See "Watcr pipe. riser." 1100F DRAIN. A drain installed to rcccivc water collecli~lg on thc surface of aroof and to discharge such water into leader or a conductor. IPOUGN-IN. Parts of the plumbing system that are installed prior to the installation of fixtures. This includes drainage, watcr supply, vent piping and the necessary fixture supports and any fixtures that are built into the structure. SELF-CLOSING FAUCET. A faucet containing a valve that autoniatically closes up or^ dcacrivation of the opening nlcans. SEPARATOR. See "I~~te~ccptor." SEWAGE. Any liquid waste containing animal or vegctablc matter in suspension or solutiorr, including liquids containing chemicals in solution.
SEV17AGE EJECTORS. A device for lifting sewage by entraining Ihc sewagc in a high-velocity jet of steam, air or water. SEWER Building scwer. Sce "Building scwcr." Public sewer. A common sewer directly contr-olled by public authority. Sanitary sewer. A sewer that carries sewage and excludes storm, surface and pround watcr. Stor111 sewer. A sewcr that conveys rainwater, surface l a r wastes. watcr, subsurf~ccwater and s i ~ ~ ~ iliquid SLOPE. 'The full (pitch) oi'a line of pipe in reference to a horizontal plane. In drainaze, thc slope is expressed as the fall in units vefiicnl per units horizontal iperce~lt)for a Icngth of pipc. SOIL PIPE. A pipc that conveys sewage containing fecal matter to the b~tildinydr-ain or building sewcr. SPILLPROOF VACUUM BREAKEK. An assembly consisting of one chccli valve force-loaded closed and an air-inlct vcnt valve force-loaded open to atmosphere, positioned dawnstl-carn of ~ l i cchcck valve, and located between and including two tiphtly closing shutoH'valves and a test cock.
STACK. A general term for ally vertical line of soil, waste. \ cnt or inside conductor piping that cxtcnds through at lcast one story with or without offsets. STACK VENT- The extension of a soil or waste stack ahovc the highest horizontal drain cor~ncctcdto the stack. STACK VENTING. A mcthod of venting a fixturc or fixtures through the soil or waste stack.
STERILIZER Boiling type. A boiling-type stcriliacr is a fixturc of a nonpressure type utilized for boiling instruments, utcnsils or other equipment for disinfcction. These devices are portable or arc connected to the plumbing system. Instrument. A device f o ~the sterilization of various instruments. Pressure (autoclave). A pl-e5sul-evesscl fixturc dcsigncd to utilize steam under prcssure for stcrilizing. Pressure instrument washer sterilizer. A pressure ir~strunlerlt washer sterilizer is a pressure vcsscl fixture dcsigncd to both wash and sterilize instruments during the operating cycle of the fixture. Utensil. A device for the sterilization of utensils as utili7ed in health care services. Water. A water sterilizer is a device for stcrilizing watcr and storing sterile watcr. STlrERI1,IZER VENT. A separate pipe or stack, indirectly connected to the building drainage systcn1 at thc lower tcrminal. that receives the vapors from lionpressure sterilizers, or thc exliausL vapors from pressure sterilizers, and conducts the vapors directly to the open air. Also called vapor, steam, atn~ospheric or exhaust vent. STORM DRAW. Scc "Drainage system, sto~.m.'' STRUCTURE. That which is built or constt.uctcd or a portion lhercof. SUBSOIL DRAIR. A drain that collects subsurface watcr or scepagc water and coll\Jeyssuch water to a place of disposal. SUMP, A talk or pit that receives sewagc or liquid waste. located below the normal grade of thc g r a ~ i t ysystem and that must be empticd by mechanical means. SUMP PUMP. An automatic water pump powcrcd by an clectric motor for the re~novalof dra~nagc.except raw sewage, fiom a sump. pit or low point. SUM? VENT. A vent from pl~clin~atic sewagc cjcctors, or sin]ilar equipment, that terminates separately to the open air. SUPPORTS. Devices for supporting ant1 securing pipc, fixtures and equipment. SWIMMING POOL. Any structure. basin. chambcr or tank containi~~g an artificial body of water for swirnmirlg. diving or ~ mole ) recreational bathing hav~nga depth of 7 feet (6 10 ~ n nor at any point. TEMPERED WATER. Watcr having a temperahlrc range between 85°F (29°C') and 1 10°F(43°C). 2006 INTERNATIONAL PLUMBING CODE@
THIRD-PARTY CERTIFICATION AGENCY. An approved agency operating a product or material certification sytcln that incorporatcs initial product testing, asscss~nentand survcillancc of a manufacturer's quality control systeni. 1'HIRl)-PAlZTY CERTIFIED. Certification obtained by the ~nanufactureriildicaling that the function and performance characteristics of a product or matcrial have hecn determined by lesting and ongoing surveillance by an approved third-party certification agency. Assertion of certification is in the for111of identification in accordance with the requirements of the third-party certification agency. THIRD-PARTY TESTED. Procedure by which an approved testing laboratory provides documentatio~l t h a ~a product. material or system confor~nsto specified requirements. TRAP. A fitting or dcvice that provldes a liquid seal to prevent the cnli\sion of scwcr gases without materially affecting the flow of sewage or wastcwater through thc flap. TRAP SEAI,. The vcrtical distance between the weir and thc top of the dip of the trap. UNS'I'ARLE GROUND. Earth that does not provide a nuiform bearing for the barrel of the scwcr pipe bctween thejoints at the bottom of the pipe trench.
VACUUM. Any pressure less than that exerted by the atnlosplic~e. VACUURT BREAKER. A typc of backflow preventer installed on openings subject to nornml atmospheric pressure that prevents backtlow by admitting atmospheric pressure through ports to thc discharge a ~ d eor the device. VKN'I' PIPE. Sec "Vcnt system." VENT STACK. A vertical vcnt pipe installed primarily for the purpo5c of providing circulation of air to and from any part of the dl ai~lagesystem. VENT SYSTEM. A pipc or pipcs installed to provide a tlow of air to or frcjrn a drainagc systern. or to provide a circulation of air within such system to protect trap seals from siphonage and backpressurc. VER'TICAI, PIPE. Ally pipc or fitting that inalccs LIII angle of 45 degrees (0.79 rad) or morc with tlie horizontal.
WALL-HUNG WKTER CLOSET. A wall-mounted water clo\ct i~tstallcdin such a way that thc hxturc docs not touch the floor. WASTE. The di\cllnr~cfrom any fixture, appliance, area or appurtenance that docs not contain fecal matter. WAS'I'E PIPE. A p ~ p cthat conveys only waste.
WATER-HAMMER AKRESTOR. A device utilizcd to ;~bsorbthc pressure snrge (water hammer) that occurs when water flow is suddenly stopped in a water supply system. WKI'ER MEA'PER. Any hcating appliance or equipment that heats potable water ant1 aupplics such watcr to thc potable hot water distribution system. WATER MAIN. A water supply pipe or system of pipes, installed and m;iintainc[l by a city, township, county, public utility company or other public entity. on public pmpcrty, in the 2006 INTERNATIONAL PLUMBING CODE@
street or in an approved dedicated cascmcnt of pulilic or community use.
WATER OUTLET. A discharge opening through which watcr is supplied to a Cixlure, into the atmosphcrc (except into an open tank that is part of the water supply system), to ahoiler or hcating system, or to any devices or equipnicnl requiring watcr to operatc but which are 11otpart of the plumbing systcln. WATER PIPE Riser. A water supply pipe that extends onc full stoiy or more toconvey watcr to branches or ton group of fixtures. Water distribution pipe. A pipe within the stlxlctLlre or on thc prc~niscsthat conveys watcr fro111 tlic watcr service pipe. or from the meter when the lnctcr is at thc st~.ucture,to the points of utilization. Water service pipe. The pipc from the walcr main or othcl. source of potahlc water supply, or from the mctcr when the meter is at the public right of way, to the watcr distribution systern of the building served. WATER SUPPLY SYSTEM. The water service pipe, water distribution pipes, and the ncccssary connecting pipes, fittings. colltrol valves and all appurtenances in or adjacent to tlie structure or premises. WELL Bored. A well constructed by boring a hole in the ground with an auger and installing a casing. Drilled. A well constructed by making a hole in the ground witha drilling machine of any typc and installir~gcasingand screen. Driven. A well constructed by driving a pipc in thc ground. Thc drive pipc is i~suallyfitted with a well point and screen. Dug. A well conctructcd by cxcavati~~g a large-diamctcr shaft and installing a casing. WHIRIA'OOL BATHTUB. A plumbing appliance consisting of a bathtub fixture that 1s equipped and tilted with a circulating piping systeni designed to accept. circulate and discharge bathtuh water upon each use. YOKE VENT. A pipc connecting upward from a soil or wastc stack to a vcnt stack for thc purposc of prcvcnting prcssurc changes in the stacks.
2006 INTERNATIONAL PEUMBlNG CODE@
CHAPTER 3
GENERAL REGULATIONS SECTION 301 GENERAL 301.1 scope. ~h~ provisions of this chapter sllall the geneml regulations regarding the installation of plulnbillg [lot specitic to other chapters. 301.2 System installation. Plumbing shall be installed with due ~egardto prescrvatlon of thc strength of structural nicmbcrs and prevention of damage to walls and other surfaces through fixture usage 301.3 Co~inectionsto the sanitary drainage system. All plumbing fixtures. drains, appurtenances ant1 appliances used to rcccive or discharge liquid wastes or sewage shall be directly conncctcd to t l ~ esanitary drainage system o r the building or prclnises, in accordance with thc requirements of this code. This section shall not be construed to prevent the indirect waste systcnls rcquircd by Chapter 8. 301.4 Connections to water supply. E v e ~ yplumbing fixture, device or appliance rcquiringor using water for its proper operation shall bc dircctly or indirectly connected to the water supply systcln in accordancc with thc provision? of this code. 301.5 Pipe, tube and fitting sizes. Unless otherwise specified, the pipe, tubc and tittins sizes specified i r ~this codc are cxprcssccl in nominal or standard sizes as designated in the refcrcnccd matcrial standards. 301.6 Prohibited locations. Plumbing systems shall not be located in an elcvator shaft or in an elevator equipment room. Exception: Floor drains, SLIIII~Sand sump pumps shall be pe~inittedat the hasc of the shaft provided they are indirectly connected to the plu~ubingsystem. 30'1.7 Conflicts. Where conflicts between this code and the conditions of tlic listing or the nianufacturer's installatio~~ illstmctions occur, thc provisions of this code apply. Exception: Wherc a codc provision is less restrictive than the conditions of the listing of the cquipmcnt or appliance or the rna~lufacturer'sinst;~llationinstructions, tlic conditions of the listing and manufacturer's installation instructions shall apply.
sewel. until it has been dctern~incdby the codc official or other a~~thority having jurisdiction that thc introduction thereof will not dan~agetlic public sewer system or interfere with the functioningOf the sc\'age treatlnerlt plar1t.
SECTION 303 MATERIALS 303.1 Identification. Each l e n ~ t hof pipe and each pipe fitting. trap, fixture, material and device utilized in a plumbins system shall bear the identification of the manufacturer. 30'3.2 installation of materials. All materials uscd shall he. installed in strict accordance with the standards under which the materials are accepted and approvcd. 111the abscncc of such installation procedures, the manufacturer's installation instructions shall be followctl. Where the requirements of rcfercnced standards or manufacturer's installati011 instructions do not conform to minimum provisions of this codc, the pl-o\,isions of this code shall apply. 303.3 Plastic pipe, fittings and components. All plastic pipe. fittings and components shall bc third-party certified as conforming to NSF 14. 30'3.4 Third-party testing and certification. All plunibing products and materials shall comply with the referenced standards, specilications and performance criteria of this code and shall be identified in accordance with Scction 303.1. When requircdby Table 303.4, plumbing products and materials shall either be tested by an approved third-party testing agency or certified by an approved third-party certification agency.
SECTION 304 RODENTPROOFING 304.3 General. Plu~-nbingsystems shall bc dcsigned and installed in accordancc with Sections 304.2 through 304.4 to prevent rodents fro111entering structures.
304.2 Strainer plates. ,411 strainer plates on drain inlets shall SECTION 302 bc designed and installed so that all openings are not greater EXCLUSION OF MATERIALS DETRIMENTAL than 0.5 inch (12.7 mm) ill least dimension. TO THE SEWER SYSTEM boxes. Mctcr boxcs shall be constructed in such a 302.1 ~ ) ~ ~or dangerous ~ i ~ materials. ~ ~ ~t ~~cinclers l h or ~ 304.3 ~ Meter . manner that rodcnts are prcvcnted from cntcring a structure by rags: flammable. poisonous or explosive liquids or gases; oil, way of the water service pipes connecting the lnetcr box and or any insoluble material capable of lhe structure. damaging or overloading the building drainage or scwcr systcm, or capablc of interfering with tlic normal operatior, of the 304.4 Openings for pipes, In or on ht,.uctul.es openings scwagc treatment processes, shall not be deposited. by any have been made in walls; floors or ceilings for the passage of means, into such systcms. u i ~ e .s .such o~eninrrs - shall be closed ant1 ~ r o t e c ~ chvd the 302.2 Industrial wastes. Waste products From manufacturing installation of approved metal collars that are securely fastcncd or industrial operations shall not be introcluccd into the public to the adjoining structure. -
-
.
2006 INTERNATIONAL PLUMBING CODE@
&
GENERAL REGULATIONS
TABLE 303.4 PRODUCTS AND MATERIALS THIRD-PARTY AND THIRD-PARTY CERTIFICATION - - REQUIRING - TESTING -- ---- -- --
I
PRODUCT OR-MATERIAL - - -
t
r
-
- -
-
-
-
+ - - -- -
-
! I'o~ablc water s~pplysystem components and potable wilter .f _ i x t_u ~fittings ~_ ~_ -
-
--
-
THIRD-PARTY - - - -- CERTIFIED - - -
-
-
--
-
I
I
THIRD-PARTY TESTED
I
--
-
Requircd
-
jSanltary di-ainngc and vcnt system compouerlls &. . ---. .- . --
~
~-
~
--
-~
-
~
I
!Waste Fixture fittings I
I
,
( S L.O Idrainan? .. I ~ ~ system . ..
I ~ l t ~ r n. hfixturcs i n ~.
cornpollents .- . _--.
.
~-.L
.
-
~ a ~. l. ~- f prevention l o -w devices -
-
.
.
~
~~
~-
-
I
-
-
-
-
j~lil~soil - drai~~age -~ . - syslern ~ ~. components -
1
.
. -.
_ Required
-
Required
~
-
1
All ~others-
,.-_ ~ -~
~-
~~
Required ~.
~~
t1
i
~
I
~.
-
.
!
.
-
~ I
i
-
~
-
_-
.
-~
~-
All olhc1.s
! i~
~
-.I 1 ~
l ~ ~ e c iwaste a l system- colnponelits . . , ~ - .
-
-.
I ~ a L cdisll.ibu~ion r systcm safety dcvices .
P&sLic pipc, ~. fittings and pipe-related--components -
I
appliances 1'Plulnbi~~n .-5 . .
-
~-
.
I
!
A 11 othcrs -. .
- ~ -
L.
I
1 -
1
/ Plastic pipe, fittings and pipe-related components -. Plastic pipe, fittings and pipe-1,elatcd components
~
-
i i
-.
i
~
Requircd -
----
~
1
--
1
.
SECTION 305 PROTECTION OF PIPES AND PLUMBING SYSTEM COMPONENTS 305.1 Corrosion. Pipcs passing through concretc or cinder w:llls and floors or otlicr corrosive matcrial shall be protected against external corrosion by a protectivc sheathing or- wrapping or otlicl. mcans that will withstand any reaction from the lime and acid of concretc, cinder or other corrosive material. Shcatliing or wrapping shall allow for expansion and contraction of piping to prevcnt any rubbing action. Minil~iumwall thickness of matcrial shall be 0.025 inch (0.64 mm). 305.2 Breakage. Pipes passing through or under walls shall be protcctctl from brcakagc.
305.3 Stress and strain. Piping in a plumbing systcln shall be installed so as to prevent strains and stresses that exceed the sti-uct111-a1 strength of the pipc. Whcre necessary, pro\:isions skull be niadc to protcct piping fiom damage resulting from cxpansion. contraction and structural settlement.
305.4 Sleeves. Annular spaccs between sleeves and pipes shall be lillcd 01-lig111ly caullicd in an approved manner. Annular spaces bctwecn slccves and pipcs in firt-resist~ncc-rated assemblies shall bc fillcd or tightly caulked in accordance with the I~ztcrfzatio~zul Rllikli~l,(:Code.
305.5 Pipes through or under footings or fo~tndationwalls. Any pipc that passes undcr a Sooting or through a foundation wall slrall bc provided with a relieving arch, or a pipe slecve pipc shall bc built into the foundation wall. The sleeve shall be two pipc sizes greatcr than thc pipc passing through the wnll.
305.6 Freezing. Water, soil and waste pipcs shall not be installed outsitlc of a building. in attics or crawl spaccs, concealcd in outsidc walls, or in any other place subjcctcdto ti-eezing tcniperature unless adcquatc provision is made t o protect such pipcs from frcezi~igby insulation or hcat or both. Exterior water supply systcni piping shall be iiistallecl not less than 6 inches ( I 52 mln) below the frost lint and not less than 12 inchcs ( 3 0 5 mni) bclow grade.
-
1
.
I .
. ~-
Required ~
j
305.6.1 Sewer depth. Building sewers that connect to private sewagc disposal systcms shall bc a mini~iiumof [NLiMBER] inches (mm) bclow finished g1-adca1 thcpoint of scptic tank connection. Building scwcrs shall bc a ~ i ~ i n i m uofn ~ [NUMBER] inches (inm) below grade.
305.7 Waterproofing o f openings. Joints at the roof and around vent pipes, shall be made water tight by thc use of Icad, copper, galvanized stcel; aluminum, plastic or otlier appro\~cd flashings or flashing material. Exterior wnll opcnings shall be nude waier tight.
305.8 Protection against physical damage. In conccnlcd locations whcrcpiping, other than cast-iron or galvanized stcel. is installed thl-ough holes or notches in studs. joists, raftcrs or similar members less than 1.5 inchcs (38 mm) from the nearcst cdge of thc mcmber, thepipc shall be protected by shicld platcx. P r o t e c t i v e s h i c l d p l a t e s s h a l l bc a r n i n i ~ n i ~ m of 0.062-inch-thick ( I .6 mm) steel, shall cover thc ;Ireit of thc pipe whcrc the nieiiiber is notchcd or borcd. and shall extend a niini-. nlum of 2 inchcs (51 mm) abovc sole plates and bclow top plates.
305.9 Protection o f components o f plumbing system. Components ot a plumbing system installcd along alleyways. cirivcways, parking garagcs or other locations expo\cd to danagc shall be recessed into tlic wall or othcrwise pn>tectcd in an approved manner. SECTION 306 TRENCHING, EXCAVATION AND BACKFILL 306.1 Support of piping. Buried piping \l1:111 hc 5opported throughout its cntire length.
306.2 Trenching and bedding. Where trcnclics arc cxcav:~ted such that the bottom of thc trench foniis the hcd for tlic pipc, solid and continuous load-bearing suppc>rtshall bc provided bctwecn joints. Bell holes, hub holes and coupling holes shall bc provided at points whcrc the pipc is joi~lcd.Such pipe shall on blocks to gradc. In instances where the not be s~~pportcd 2006 INTERNATIONAL PLUMBING CODE@
GENERAL REGULATIONS
~natcrials manuPacturcr's installation instructions are morc rcstrictivc than lhosc prescribed by the codc. the material shall be installed in accordance with the morc rcstrictivc requircnlcnl.
306.2.1 <)verexcavation. Wherc trenches arc excavated below the in~tallat~on level of the pipc such that thc bottonl of thc trench docs not form the bed for the pipc, the trench sllall be backiillcd to the in\tallaliou level of the bottom ot the pipe with sand or fine gravel placed in layers of 6 inchcs (1 52 mm) maximum depth and such backfill shall be cornpacted after each placement.
306.2.2 Rock removal. Wherc rock is encountered in trenching, the rock shall be removed to a minimum of 3 inches (76 mrn) below the installation levcl of the bottom of thepipe, and the trench shall be backfilled to the installation lcvcl of the bottom of thc pipe with sand tamped in place so as to provide unii'orm load-bearing support for the pipe b c t w e c ~joints. ~ The pipe, including the joints, shall not rest on rock at any point.
386.2.3 Soft load-bearing materials. If soft ~natcrialsof poor load-bearing quality are found at the bottom of the trench, stabilization shall be achieved by overexcavating a minimum of two pipe diameters and backiilling to the installatio~ilcvel of the bottom of'thc pipe with fine gravel. crushed stone or a concrete foundation. The concrete foundation sllall bc bedcled with sand tamped into place so as to provide uniform load-hearing support for thc pipe hetwezr~ joints.
306.3 Backfilling. Backfill shall bc free from discarded construction matcrial arid debris. Loose earth free from rocks. hro-ken concrctc and frozen chunks shall bc placed in the trench in 6-inch ('1 5 1 mm) layers and tamped in place until the crown of the pipc is covercd by 12 inclies (305 mm) of tamped earth. The backfill ~nlderand beside the pipc shall be compacted for pipe support. Backtill shall be brought up evenly on both sides of the pipe so thai the pipc remains aligned. In instances where the manufact~~rer's installation instructions for inaterials are more rcstricti\7c than those prcscribed by the code, the material shall hc installed in accol-dance with the more restrictive requirement.
306.4 Tunneling. Whcre pipe is to be installed by tunneling. jacking or a combination of hoth, the pipe shall be protected from danlagc during installation and froin subsequent uneven loadirig. Whcre cal-th tunncls arc used, adequate supporting structorcs shall bc providedto prevent future settlillgorcaving.
307.2 Cutting, notching or bored holes. A framing mc~nber shall not he cut, notched or bored in excess of limitations specified 111 the Interizutiarzul Rrtildirzg Codc.
307.3 Penetrations of floor/ceiling assemblies and fire-resistance-rated assemblies. Penetrations of floorlceiling assemblies and assemblies recl~iiredto !lave a tire-rektancc rating shall he protected in accordancc with the Iizterriat~onulBuiMii~g cod^.
[B] 307.4 Alterations to trusses. Truss mcinbcrs and components shall not be cut, drilled. notchcd, spliced or otherwisc alteredin any way without written concurrence and :~pprovalof a registered design profcssional. Alterations resulting in thc addition of loads to any member (e.g., HVAC ccluipment. water heater) shdl not be pcrrnittcd withoul verification that the truss is capable of supporting such additional loading.
307.5 T r e ~ ~ clocation. h Trcnchcs installcd parallel to footings shall not extend belov, the 45-degree (0.70 rad) bearing plane of the footing or wall. 387.6 Piping materials exposed within plenums. All p~ping materials exposed with~nplenums shall comply with the prowsions of the Ir~tenz~~tio~iul Mechuiric(11Code.
SECTION 308 PIPING SUPPORT
308.1 General. All plumbing piping shall be supportccl in accordancc with this section.
308.2 Piping seismic supports. Wherc carthqlrakc loads arc applicable in accordance with the building codc, plumbing piping suppons shall he designed and installed for thc seismic forces in accordancc with the Irztc~rrzatiovzalB~~ildiilg Code.
308.3 Materials. Hangers, anchors and supports shall support the piping and the contents of the piping. Hangcrs and strapping nlatcrial shall be of appl-oved ~rlatcrialthat will not promote galvanic action.
308.4 Structural attachment. Hangers and anchors shall bc attached to the building construction
ill
an approved manner.
308.5 Interval of support. Pipc shall bc supportccl in accordance with Table 308.5.
Exception: The interval of support for piping systcms dcsig~~cd to PI-ovidc for expansionfcontraction shall conform to the cngineercd design in accordancc with Section 105.4.
308.6 Sway bracing. Rigid support sway brac~ngshall be provided at changes in dircction grcatcr than 45 dcgrces (0.79 rad) for pipe sizes 4 inches ( 102 rnm) and larger.
SECTION 307 STRUCTURAL SAFETY
307.1 General. In the process of installit~gor repairing any part of a plu~nbinzand drainage installation, the finished floors. walls. ceilings. tile workor any other part of the buildir~gorprenlises that must bc changed or replaced shall be left in a safe struct~~ral condition in accordancc with the requirenlent:; of the hztcntcttio?rcllIlrtilcling Code.
2006 INTERNATIONAL PLUMBING CODE@
308.7 Anchorage. Anchorage shall be prob~dedto restrail) drainagc piping from ax~almo\ement.
308.7.1 Location. For pipc sizes grcater than 4 inchcs (102 mm), restraints shall he provided for drain pipes at all changes in dircction and at all changes in dianlctcr greater than two pipc sizes. BI-aces,blocks. rodding and other suitable methods as specified hy rhc coupling manufilcturer shall be ~~tilized.
GENERAL REGULATIONS
TABLE 308.5 HANGER SPACING . -
1
1-
PIPING MATERIAL -
-
I
MAXIMUM VERTICAL
MAXIMUM HORIZONTAL SPACING (feet) -
-_
with thc manufacturer's installation instructions. I-lot and cold water piping shall not he grouped in tllc aamc bundle.
..
-
~
--
SPACING
SECTION 309 FLOOD HAZARD RESISTANCE
(feet)
--.
,AUS pipe
309.1 General. Plumbing systems and equipmerl~in structures
I Brass pipc -
-
~
~~
~
-
-.
-
~
!copper . or.copper-:~lloy . ~.- . pipc - .
,
.i
10
i
1I
10
-,. !
. .
-
~
!cross-linked polyethylene 1I (lJES). pipc ~ . .~.-.. ~ ~.
4I
2.67 (32 inches) -.
IC~YS-linked polyelhylenel
j
2.67
-
'
,ICPVC i 1 (
a~;rni~ium/cl-~~bs-li~iked ~)olyt.thylene(PGX-AL-PEX) 1
CP!!
.
_
.
_
.
pipe or tubing. 1 inch and smaller. -
ICPVC
'
,
3 --
and larger
,~Stecl pipe ~
~
~
~
~
.
i
~.
I
1 i
-.
-
j I
-
-
I?
..- .-
2. Pump seals in individual water supply systcins whcre thepilmp is located below the d e s i y floodclcvation.
10" -
.~-
I
I
10"
--
~L
-. -
loc;~tcdbelow the design flood clevation provided that the systems are designed and installed to prevent water from entering or acculnulating within their components and the syslenis are constructed to resist hydrostatic and hydrodynamic loads and stresscs, including the cffccts of buoyancy, during the occurrence of flooding to the design flood elcvation. 1. All watcr service pipes.
-.
4
j
~ ~ . *
*.
-~
-~~
.--.'
i
I
pij~mol.tubing. 1 I/, inches I
1
jI
10
i
(32 inches)
I
[B] 309.2 Flood hazard. For structures located in flootl hazzu-d areas, the following systems and eqoipn~entshall be located at or above thc design flood elevation. Exception: The following systcn~sarc: permitted to bc
~
, )
15~-. .-
6 I I/,-inch diarneter ; ~ n dsmaller i i ._-
~ ~- ~
!copperor. copper-alloy tubing, 1 1 'I2-inch diarneter and larger . . . .
I
- -- -l 5...-.. -
1
3. Covers on potable water wells shall hc sealed. except where the top of the casirip well or pipe sleeve is elevated to at least 1 foot (305 r111n) above the dcsign flood clevation.
4. All sanitary drainage piping
I 5 . All storm drainage piping. 2.57 1 4 1 6. Manhole covers shall be sealed. except whcre cle(32 inches) . _ ~_--, -..t-.--.-.._-.. vated to or above the design flood elevation. I i ~~ol~~thylenelalurnin~~~nl 1 2.67 7. All other plumbing fixtures, faucets; fixture fittings, 11 . P olyrithylrne (YE-At-PE) pipe 1 (32 inches) . . - ~+ -.I piping systcms and cquipnicnt. 1 ~ ~ o l ~ ~ r o(PP) ~ ~pipe l c nore i 2.67 [32 inchesj ) I Oh ; 8. Water heaters. 1 ~ubino1 inch and snlaller
1
i
IPR pipe or tubing
.-~L
-
~-~
-
I
1
I--.
12
4.
1 Copper or coppel.-alloy tubing, Ii
I '
j s
1 Cast-iron pipe I -~ -~
_ -
_
1
erected in flood hazard areas shall bc constl-uctcdin accordance with the requirements of this section and the Ir~terr~c~tio~rul Buildirzg Code.
~
1
9. Vents and vent systcms. [B] 309.3 Flood hazard areas subject to high-velocity wave action. Structures locatcd in flood hazard areas subject to
I inch = 15.4 mm, I loot = 304.8 mm. a. The m n x i m ~ ~ m l~orizontnlsp:lcing of cast-iron pipe lianpcrs shall be increased to 10 t'cet where 10-foot lengths of pipe ;lur ~nst;~lled. h, hlidsc~>~y g~~id forc \i/cs 1- inches and slnallen Fur- ST:
*
308.8 Expansion joint fittings. Expansion joint Fittings shall bc usetl only whcrc necessary to provide for expansion and contraction of the pipes. Expansion joint fillings shall bc of the typical material suitable for use with the type of piping i l l which such fittings are installed.
high-velocity wave action shall meet the rccluircincnts of Section 309.2. The plulllbing systems, pipes and fixtures shall not bc mounted on or penetrate through walls intcntlcd to hrcali away under flood loads.
SECTlON 310 WASHROOM AND TOILET ROOM REQUlREMENTS 310.1 Light and ventilation. Washrooms and toilet rooms shall he illuminated and ventilated in accor-clailcc with the I~zter~iutiorznlR~lil~iinfi Code and Ii~.tc~rl~ntionrrl M~clinr~ic.nl Code.
310.2 Location of fixtures and piping. Piping, fixtures or 308.9 Parallel water distributionsystems. Piping hurldles for manifold systcms \hall he wpported in accordance with Tahlc 308.5. Support at changes in dirxction shall he in accordance
equipment shall not be located in such a mantiel as to intcrfcsc with the normal operation ofwiildows, doors or other tncans of egress openings. 2006 INTERNATIONAL PLUMBING CODE@
GENERAL REGULATIONS
310.3 Interior finish. Interior finish surfaces of toilet rooms shall co~iiplywith the Itlrcrr~atior~nl B~iilliilgCocie.
ascertain wlicther the pressurc has rcachcd all parts ofthe sy5Icm.
310.4 Water closet compartment. Each watcr closct utilizcd by the public or cmployecs shall occupy a scparate compartrrlcnt w ~ t hwalls or partitions and a door e~iclosingthe flxtures to cnsurc privacy.
312.1.1 Test gauges. Gauges used for testing shall bc as follows:
Exceptions: I. Water closct compart~nentsshall not be required i l l a singlc-occupant toilct room with a locliable door. 2. Toilet rooms Ivca~edin day care and child-care faeilitics and containing two or more water closets shall be permitted to havc one watcr closet without ari enclosing compartment. 310.5 Urinal partitions. Each urinal utilized by the public or c~nployecsshall occupy a scparate area with walls or partitions to providc privacy. The conskuction uf such walls or partitions shall incorporate warcrproof, smooth, readily cleanable and nonabsorbent finish surfaces. The walls or partitions shall bcgin at a height not more than 12 inches (305 mni) from and extcnd not less than 60 inches (1534 mn1) above thc finished floor surfacc. The walls or partitions shall extc~idfrom the wall surface at each side of the urinal a mininiurn of 18 inches (457 mm) or to a point not less than 6 inches ( I 52 mrn) beyond thc outermost front lip of the urinal measured from the finishcd back wall surtacc, whichever is greater. Exceptions: 1. Urinal partitions shall notbc required in a single occupant or unisex toilet rooiii with a lockable door. 2. Toilct rooms located in day care and child care facilitics and containing two or illorc urinals shall be permitted to havc one urinal without partitions.
SECTION 311 TOILET FAClLlTlES FOR WORKERS 311.1 Gencr:~l.Toilet facilities shall be provided for constmction workers and such facilities shall be maintained in a sanitary condition. Construction worker toilet facilities of the nonsewcr type shall conform to ANSI 24.3. SECTION 312 TESTS AND INSPECTIONS 312.1 Required tests. The permit holdcr shall niake the applicable tcsts prescribed in Sections 3 12.2 through 3 12.9 to detcrniine compliance with the provisions of this codc. The permit holdcr shall give rcasonablc advance notice to lhe code official whcn thc plumbing work is ready for tests. The ecluipment, material, power and labor necessary for tlie inspection and test sliall bc fi~rnislledhy the permit holder and the permit holder sliall be responsible for determining that tlie work will wilhstand thc tcst prcssure prescribed in the following tcsts. All plumbing systenl piping shall be tested with either watcr or. for piping systcnis other than plastic, by air. After the plumbing fixturcs h a w hccn set and their traps filled with watcr, ttic entire drainage systcm shall IE submitted to final tests. Thecode official sliall rcqi~irethe removal of any cleanouts if nccessary to 2006 INTERNATIONAL PLUMBING CODE@
I. Tests requiring a pressure of 10 pounds per squarc inch (psi) (69 kPa) or lcss shall utilize a testing gauge having increments of 0.10 psi (0.69 kPa) or Icss. 2. Tests requiring a prcssure of grcatcr than 10 psi (69 liPa) but less than or equal to 100 psi (683 hP,l) shall utilize a testing gauge having tncrcrncnts of I psi (6.9 kPa) or less. 3. Tests requiring a pressure of grentcr t1i;ui 100 psi (689 kPa) shall ulilizc a testing gaugc having incrc~ncntsof 2 psi ( 14 kPa) or Icss.
312.2 Drainage and vent water test. A watcr tcst shall bc applied to the drainage systcm either in its cntircty or in sections. If applied to the entire system, all opc~iingsin the piping shall be tightly closed, exccpt the highest opcning. and thc system shall be filled with waterto thc point of ovcrflow. If tlie system is tested in sections, each opcning shall be tightly plugged exccpt the highest opcnings of the scction undcr tcst, and each scction shall bc fillcd with water, but no section shall be testcd with less than a 10-foot (3048 mm) hcad of water. In testing successive sections. at least thc uppcr I 0 fect (3048 ~ n mof ) the next preceding section shall be tested so that no joint or pipe in the building, except the uppcmiost 10 feet (3048 nini) of the systcm, shall havc becn submitted to a tesl of less than a 10-foot (3048 mm) head of water. This pressure sliall bc hcld for at least 15 minutes. The systcm shall then be tight at all points. 312.3 Drainage and vent air test. An air test sliall bc rr~adcby forcing air into the system until therc is a uniform gaugc pressure of 5 psi (34.5 kPa) or sufiicicnt to balance a 10-inch (254 mm) column of mercury. This prcssure shall bc held for a test period of at least 15 minutes. Any adjustments to thc test pressure I-equircdbecauseof changes in anlbient tempcraturc or thc seating of gaskets shall bc made prior to thc beginning of the test period. 312.4 Drainage and vent final test. The final tcst of the conipleted drainage and vent system shall bc visual and insufficient detail to detel-mine co~npliancewith the provisions cif this codc except that the plumbing shall be subjected to a smoke test whcre tlecessary for cause. Wherc the smokc tcst is utilized. i t shall bc ~ n a d cby filling all traps with watcr and t11c11introducing into the entire systcrn a pungent, thick smoke producecl by one or more smoke machines. Whcn the smoke appears at stack openings on the roof, the stack opcnings shall bc closcd and a pressure equivalent to a I-inch watcr column (248.8 I'a) shall be held for a test pcriod of not less than 15 ~ninutcs. 312.5 Water supply systerli test. Upon completion of a scction of or the entire water supply system, thc system, or portion completed shall be tested and proved tight undcr a watcr prcssure not less than the working pl-essurc of the systcln: or, for piping systems other than plastic, by an air tcst of not lcss than 50 psi (344 kPa). 'This pressure shall bc hclcl for at lcast 15 nlinLltes. Thc water utilized for tests shall bc obtained fl-o~u a potable source of supply. The rcquired tcsts shall bc performed iu accordance with this section and Section 107.
GENERAL REGULATIONS
312.6 GI-avity sewcr test. Gravity sewer tests shall consist of plugging thc end of thc building sewer at the point of connection with the p ~ ~ b lSCWCI-. ic filling the building scwer with water, tcsting with not lcss than a 10-foot (,3048 mm) head of water and m:lintaining such pressurc for 15 minutes.
[MI 314.2.1 Condensate disposal. Condensate from all cooling coils and cvaporcltors shall be convcycd fro111the drain pan outlet to an approved placc of disposal. C o ~ ~ d c ~ i sate shall not discharge into a street, alley or other arcas so as to cause a nuisance.
312.7 Forced sewcr test. 1;orced sawer tests shall consist of plugging the end of the builtling sewer at the point of conncction with the public scwer and applying a pressure of 5 psi (34.5 I&) greater than the pump rating, and maintaining such pressure for 15 minutes.
[R4] 314.2.2 Drain pipe materials and sizes. Co~nponents of the condensate disposal system shall be cast iron, galvanized steel, copper, cross-linked polycthyle~ie.polybutylcnc. polycthylene. ABS. CPVC, or PVC pipe or tubing. All coniponcnts shall bc selected for the pressure and temperature rating of the instr~llation.Condensiite waste and dmin line sizc shall not be less than 'I.,-inch (19 uun) internal dianlctcr and shall not decrease in size from the drain pan conncction to thc place of condensate disposal. Where tlle drain pipes from Inore than one unit are manifolded togcther for condellsate drainage, the pipe or tubing shall be sizcd in accordmcc with an approved method. All horizontal sections of drain piping shall be installed in uniform alignment at a uniforin slope.
312.8 Storm drainage system test. Storm drain systems within a building shall he tcsted by water or air in accordance with Section 3 12.3 or 3 12.3.
312.9 Inspection and testing of backflow prevention assernblies. Inspection and testlng shall comply with Sections 3 17.9.1 and 3 12.9.2. 312.9.1 Inspections. Annual inspections 5hall be made of all backflow prevention asscn~bliesancl air gaps to deterniinc whether they arc operable.
312.9.2 Testing. Reduced pressure principle baclcflow prcvcnter assemblies, double check-valve assemblies, pressure vacuum breaker asscniblics. reduced pressure detector firc protection hackflow prevention assemblies, double chcck detector fire protection backflow prevention assemblies, hose connection backflow prcventcrs. and spill-proof vacuum brcakers shall be tested at the time of installation. i~imiccliaiclyafter rcpairs or relocation and at least annually. The tcsting proccdurc shall be performcd in accordance with one of the following standards:
pi
ASSE 5013. ASSE 5015, ASSE 5020, ASSE 5047. ASSE 5048. ASSE 5052, ASSE 5056, CSA B64. I0 or CSA B64.10.1.
SECTION 313 EQUlPMENT EFFICIENCIES 313.1 General. Ecjuipmcnt efficiencies chall bc in accordance E T I ( J ~C~OI I' Z S ~ I - Vrode. ~~~OII with thc JIIT(~~II(I~~OII(I/ SECTION 314 CONDENSATE DISPOSAL
[MI 314.1 Fuel-burning appliances. Liquid combustion byproducts of condensing appliances shall be collected and discharged to an approved plumbing fixture or disposal arcs in accordance with the ~uanuft~cturcr's installation instructions. Condensate piping shall be of approved corrosion-resistant malcrial ant1 shall not be sniallcr than the drain conncction on the appliancc. Such piping shall maintain a minimum hol.izontul slope in the direction of dischargc of not less than onc-eighth unit vertical in 12 units horizontal (1-percent slol.'c). [Mj 314.2 Evaporators and cooling coils. Condensate drain systems shall bc provicicd for equipment and appliances containing evaporators or cooling coils. Condensate drain systerns shall bc designed, constructed and installed in accordance with Scctions 3 14.2.1 tl11.ough 3 142.4.
[M] 314.2.3 Auxiliary and secondary drain systerns. In addition to the requirements of Section 3 14.2.1. a secondary drain or auxiliary drain pan shall be required for each cooling or evaporator coil or fuel-fired appliance that produces condensate, where damage to any building components will occur as a result of overflow from the equipment drain pan or stoppage in the condcnsatc drain piping. One of the f o lowing methods shall he used:
1 . An auxiliary drain pan with a scparatc d r n i ~shall ~ bc provided under the coils on which condensation will occur. The auxiliary pan drain shall discharge to a conspicuous point of disposal to alcrt occupants in the event of a stoppage of the primary drain. Thc pan shall have a minimum clepth of 1.5 inchcs (38 mm), shall not be lcss than 3 inches (76 mm) larger than the unit o nwidth s and length and shall hc or the coil d i ~ ~ ~ c n s iin constructcd of corrosion-resistant material. Mctallic pans shall have a mini~iiumthickness of not lcss than 0.0276-inch (0.7 mm) galvanized sheet metal. Nonmetallic pans shall have a minimum thicl
I
3. A water level detectiondevice conforn~ingto UI, 508 shall be provided that will shut off the etluipn~cnt served in thc cvcnt that the primary drain is bloclccd. The dcvice shall be installed in thcpriniary drain linc, the overflow drain line or in the equipnicnt-supplicd 2006 lFdTERNATlONAL PLUMBING CODE@
GENERAL REGULATIONS
drain pan loca~edat a point higher than the p r i ~ n a ~ drain line connection and below the overflow rim of such pan. Exceptiu~l:Fuel-fired appliances that automatically shut down operation in the event of a stoppage in the condensate drainagc system.
[MI 314.2.3.1 Water level monitoring devices. On downflow units and all other coils that have no seconda~y drain and no li~eansto install an auxiliary drain pan, a water. level monitoring device shall hc installed inside the primary drain pan. This device shall shut off the equipment served in the event that the primary dr-ain becomes rcstrictcd. Externally installed devices and devices ins~alledin the drain line shall not be permitted. [MI 314.2.4 Traps. Condensate drains shall be trapped as rciluircd by the equipment or appliance inanufacturcr.
2006 INTERNATIONAL PLUMBING CODE@
2006 lNTERNATlONAL PLUMBING CODE@
CHAPTER 4
FIXTURES, FAUCETS AND FIXTURE FITTINGS SECTION 401 GENERAL 401.1 Scopc. This chapter shall govern the materials, design and installation of plumbing fixturcs, faucets and fixture fittings in accordance with thc type of occupancy. and shall provide for thc rnininlum nun-rberof fixtures for various types of occupancies. 401.2 Prohibited fixtures and connections. Water closets having a conccaled tlap seal or an unventilated space or having walls that arc not thoroughly washed at each discharge in accordance with ASME A 1 12.19.2R.1sl~allbe prohibited. Any wcltcr closet that pcrnlits siphonage of thc contents of the bowl back into the tank shall be prohib~tcd.Trough urinals shall be prohibited. 401.3 Wiltcr conservation. The maxirnurn water flow ratcs and flush volulnc for plumbing fixturcs and fixture fittings shall comply with Section 604.4.
SECTION 402 FIXTURE MATERIALS 402.1 Quality of fixtures. Plumbing fixtures shall be constl-uctcd of approved rnatcrials; with slllooth, iinpervious surfaces, fsec frcl~ndefects and conccaled fouling surfaces, and shall conform to standards cited in this code. All porcelain enarnclccl surfaccs on plumbing fiutures shall be acid resistant.
4022 Materials for specialty fixtnl-es.Matcrials for specialty fixtures not otherwise covered in this codc shall bc of stainless steel. soapstone, chemical stoneware or plastic, or shall hc lincd with lead, coppel--base alloy. nickel-copper alloy, corrosion-resistant stccl or other material cspecially suitetl to the application for which the fixture is intcndcd. 402.3 Sheet copper. Sheet copper for general applications shall confonii to ASTM B 152 and shall not weigh less than 12 ounces per square foot (3.7 kglrn'). 402.4 Sheet lead. Shcet lead for pans shall not wcigh less than 4 pc>uncisper square foot (10.5 Iigim') coated with an asphalt paint 01- other approved coating.
SECTION 403 MlNlMUM PLUMBING FACILITIES 403.1 Minilnum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. Typcs of occupc~ncicsnot shown in Table403.1 shall bc considered individually by the code official. ?'he number of occupants shull be dcter~liincdby the Inrcrr~crrioiztrlBrtiliirzg Code. Occupancy cl:~ssification shall bc determined in accordance with the Irzter.rrntior7nl Bcriltlir~g Code.
TABLE 403.1 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES"
2006 INTERNATIONAL PLUMBING CODE@
FIXTURES, FAUCETS AND FIXTURE FITTINGS
TABLE 403.1-continued MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURESa (See Sections 483.2 and 403.3)
i
1
i
I
I I
I
I
I
r
i I
I i sink
exceeding 50
I 1 per 50
I per 50
1 per 100 I
I per 10
1 per 10
1 pcs room'
1 per 35
I
I
/
-
1 pcr t e l l
i
I 1
I per 500
I 1 per 15
'
I
1 per 15 -. .
1-4
~
~~~-
~
I per 15 (~~l7l7t;lz~ie'~j
2006 INTERNATlONAL PLUMBING CODE@
FIXTURES, FAUCETS AND FIXTURE FITTINGS
TABLE 403.3-continued MlNliUUM NUMBER OF REQUIRED PLUMBING FIXTURESa (See Sections 403.2 and 403.3)
1
I NO.
6
I
-
7
I
1
i
OTHER
410.1)
-
(see j Sections 403.2, 1403.4, 403.1.1 and !403.4.1)
I
(SEE
SECTION
R- I
1
L..
-
1
.
-
. .
-
1 llotels, ~nolels.
i
I_-
1
boarding houses I (transient) 41-
/
1 par 500
1
,I.
-
1
/
1
~ e l v i c est~ations. shops. aaleimonis, 1 ' markets and shoppino centers ' 3
M
I scsvice
I per750
sink
i
-
..
_ _
~_
. . -
.i
-
.-
~
~ ~ ~. - ~ - . ~ ~
~~
i poi sleeping unit
I psr sleeping w i t
I
I pet. 1 sleeping unit 1I
1 scl~ice sink
--
R-3
11 frateliiities, sororities and
1
bonl-ding houscs !(not Wnnsirnt)
i
1
I pcr 10
i I
1 per I 0
!
1
!I
1
1 sink per
I
j dwelling
/ unit: I
I
1 per dwelling unit
1 a~~tornalic
I withher
i
( connectio~~
!
per 20
1 T
i I
.
) dwellillg .
.
_
.
1 1 1
1
R-3
i i
1
~
I
t ~ lhmily o dwellings
-
~-~
--
- ~i ~ ,
~~
~
I carelnssisted Living
R-4
,.1 f a c ~ l l t ~ e s
.-
I Scoiage (see
.
.
I I kitchen dwclling
-
I ;iutomatic I clothcs j wilshcr
)
- 1I-
~~~--
I
I
1
units . ~.~~
, .
1 unit; I
I con~~cction
1
~ . -~ ~ -- ~ - ~ - ~--
~
I per dwciling itnit
I
! sink pet-
/
I pcr dwelling unit
i j i
I Rcsidclttiill ~
1 per dwelling utiit
1
Ii
I i~..~.
'i
,
j / One- and
kitchen
I clolhes
-I
: ~ n d403.4.1 )
-~~
-
1 1"' dwelling unit
I 403.4
~
I
1 D o m ~tories. i
1
8
~
I
I Retail scores,
i bIel.c:lntilc
! l7\esidcntial
FOUNTAIN
SHOWERS
-
.
;
-
CLASSIFICATION -
' BATHTUBS1 ' I
LAVATORIES
per dwcllin~ j unit ~
-1
~~
~~~
~-
I pel R
I per 10
J
) S T I . L I ~ ~ I I T Cti)r S the 1 1 storage of goods; i S-l S-2
I warehouses,
I
/ storehouse a1d 1 I freight depots. Low I
1 per 100
1 pel 100
See Section 41 1
I pet- 1,000
I and Moduratc
1 Harard.
- -.-- -
- -
a. Thc fixlures show^^ arc haserl o n one tixture bcilig the minimum reqiiil-cdIor tl!e nomher of prrsoils lndicatcd or any Traclioo of thc nuirihcr of pel-~otls indiu~tcd. 'l'hc niimhc~-or oscup,tncs shall he determined hy thc Iiitrrilrrrioiirrl Ri~ilrli~lg C'orlc. h. Tbilct hicilitics for, eiilplc~yrc?s l ~ i l he l sfparate from tilcilities For inmates or patients. L.. A singlc-occupant toilet room w,ith une water closet and one 1:lmtory serving not marc than two ailjaccnt patient sleeping units shall hc permitted \vhercsuch n)om is provided with direct access from each paticnt room and with provisions for privacy. d. The occupant load for seasonal outdoor seating aud cnicrtainrnent al-eas shall he il~cludedxvhcn determining the m i n ~ n ~ u numbcr rn ol'licllicizs required. 1
2006 INTERNATIONAL PLUMBING
CODE^
FIXTURES, FAUCETS AND FIXTURE FITTINGS
[B] 403.1.1 Unisex toilet and bath fixtures. Fixtures loca~cdwithin u ~ ~ i s ctoilet x and bath~ngroo111s conlplying with Scction 404 are pe~mittcdto be included in determ~ning thc minimum reyuired numhcr of fixtures for asscrnbly and mcrcantilc occupancies.
403.2 Scparatc facilities. Where plumbing fixtures arc rerluircd, scparatc Facilities shall bc provided for each sex.
rn
1. Sep:trute facilities shall not be required f o ~dwelling units and slcening . - units.
I)
2. Seoaratc facilities shall not be reuuircd in structures or tenant spaccs with a total occupant load. including both crnployecs and customers, of 15 or less.
3. Separate facilitics shall not be required in mercantile occupancies in which the maximurn occupant load is 50 or less.
403.3 Number of occupants of each sex. The required water closc(s. lavatories. arid showcrs or bathtubs shall be distributed equally between the sexes based on thc percentage of each sex itnlicipatcd in the occupant load. The occupant load shall be colnposcd of 50 percent of cach sex, unless st;itistical data approved by the code official indicate a different distribution of the sexes.
sS
403.4 Reyuired public toilet facilities. Customers. patrons and visitors shall be provided wilh public toilet facilities in structures and tenant spaccs intended for public utilization. The acccssiblc route to public facilitics shall not pass through kitchens, storage roorus, ciosets or similar spaccs. Employees shall be provided with toilet facilities in all occupancies. E~~iployee toilet facilitics sliall bc cithel- scpa-att: or combined employee and public toilct facilities. 403.4.1 I,ocation of toilet facilities in occupancies other than covered malls. In occupancies other than covered malls. the rcquired public and ernployec toilet facilities shall hc located not more than one story above or below the space requir-ed to bc provided with toilet facilities, and the path of t~xvelto such facilities shall not cxceed a distance of 50U feet (I52 n ~ ) . Exception: The location and maxiniunl travel distances to I-ccluircdenlployee facilities in factory and industrial occupancies are pem~ittedto exceed that required hy this section, provided that the location and maximum travel distance are approved. 403.4.2 Location of toilet facilities in covered malls. In covered Inall buildings, the rcquired public and employee toilet facilities shall bc located not rnorc than one story abovc or bclow thc space required to be provided with toilct facilities, and the path of travel to such facilities shall not exceed a distance of 300 feet (91 430 mm). In covered rnall huildings, the requir-cd facilities shall be based on total square footage, and facilities shall be installed in each individual store or in a central toilet area located in accordance with this section. The 111axirnum travel distance to central toilct facilitics in covercd nlall buildings shall be measured from the main entrance of any store or tenant space. In covcrcd 11ial1buildings, where employees' toilet f -cl~' I '~ 't ~ are es
.
28
no1 provided in the individual store, the masin~umtravel distance shall be measured from thc employee's work area of the store 01. tenant space.
403.4.3 Pay facilities. Where pay facilities arc ir~stallcd. such facilities shall be in excess of thc rcquircd minilnu~u facilities. Required facilitics shall bc frce of cli~u-ge. 403.5 Signage. Rcquired public facilities shall be designatcd by a legible sign for each sex. Signs shall be readily visible and located near the entrance to cach toilet facility.
SECTlON 404 ACCESSlBLE PLUMBING FACILITIES 404.1 Where ~Vequired.Accessible plu~nbingfacilities and fixtures bl~allbe provided in accordance w ~ t hthe I~ltet.~zatro~l~rI Building Code.
SECTION 405 INSTALLATlON OF FIXTURES 405.1 Water supply protection. The supply lines and fittings for every plumbing fixlure shall be installed so as to prevent backtlow.
405.2 Access for cleaning. Plurnbirig fixtures shall be installed so as to afford easy access for cleaning both the fixture and the area around the fixture. 405.3 Setting. Fixtures shall be set level tund in proper align ment with reference to adjacent walls. 405.3.1 Water closets, urinals, lavatories and bidets. A water closet, urinal, lavatory or bidet shall not he set closcr than 15 inchcs (381 mm) from its center to any sidc wall. partition, vanity or other obstruction, or closcr than 30 inches (762 n ~ l n )centcr-to-ccntcr betwucn adjacenl fixtures. There shall bc at least a 2 1-inch (533 mm) cleal.ance in front of Lhe water closet, urinal, lavatory or bidet to any wall, fixture or door. Water closet conlpart~nentsshall not be less than 30 inches (762 mm) wide and hO inches (I524 mm) deep (see Figure 405.3.1).
I
405.3.2 Public lavatories. In e~nployceand public toilct roonis, :he required lavatory shall be located in the same loom as the required water closet 405.4 Floor and wall drainage connections. Connections between the drain and floor outlet plumhing fixtures shall be made with a floor flange. The flange shall be attached to the drain and anchored to the structure. Connections between the drain and wall-hung walel- closets shall be madc with an approved extension nipple or horn adaptor. Thc water close1 shall bc bolted to the hanger with corrosion-rcsist;i~~t bolts or screws. Joints shall be sealed with an approved claston~eric gasket. flange-to-fixture connection coinpl ying with ASME A1 12.4.3 or an approved sctting compound. 1 405.4.1 Floor flanges. Floor flanges for water closets or similar fixtures shall not be less than 0.125 inch (3.2 ~ n m ) thiclc for brass, 0.25 inch (6.4 nim) thick for plastic, and 0.25 inch (6.4 mm) thick and not less than a 2-inch (51 nim) caulking depth for cast-iron or galvanized malleable iron. 2006 INTERNATIONAL PLUMBING CODE@
FIXTURES, FAUCETS AND FIXTURE Fl?TlNGS
dimension or other approved arrangcmcnt so as to provide access to the slip joint connectio~isfol- inspection and rcpair.
405.9 Design and installation of plumbing fixtures. Integral fixture fitting mounting surfaces on manufactured plumbing fixtures or plumbing fixtures constructed 011 site, shall mcet the design requirements of ASME A1 12.10.11vI or A S M E A1 12.19.1M.
SECTION 406 AUTOMATIC CLOTHES WASHERS
21 IN CLEAHPNCE
406.1 Approval. Domestic automatic clothes washers shall conform to ASSE 1007.
FIGURE 405.3.1 FIXTURE CLEARANCE
Floor flanges of hard lcad shall weigh not less tt~anI pound, 9 ounces (0.7 kg) and shall be composed of lead alloy with not less than 7.75-percent antimony by weight. Closct scrcws and bolts shall bc of brass. Flanges shall be secured to thc building structure with corrosion-resistant scrcws or bolts.
405.4.2 Securingfloor outlet fixtures. Floor ourlet fixtures shall be secured to the floor or floor flanges by screws or bolls of cosrosion-1.esistant material. 405.4.3 Securing wall-hung water closet bowls. Wall-hung water closct bowls shall bc supported by a concealed metal carrier that is attached to the building structural n ~ c n ~ b e\o r s that strain is not translnittetl to thc closct conncctor or any other part of the plumbing system. Thc carsicr shall conform to ASME A1 12.6.lM or ASME A1 12.6.2. 405.5 Water-tight joints. Joints formed where fixtures come in contact with walls or floors shall be sealcd. 405.6 Plulnbing in nlental health centers. In mental health ccnters, pipes or traps shall not be cxposed. and fixtures shall be bolted through walls. 405.7 Design ofoverflows. Where any fixture is provided with an overflow, the wastc shall he dcsigned and installed so that standing watcr in the fixture will not rise in the overflow when the stopper is closed, and no water will remain in thc o\?erilow when the fixture is empty. 405.7.1 Connection of overflows. Tlic overflow fi-om any fixture shall discharge into the drainage system on the inlet o~ tjx~uresidc of the trap. Exception: Thc ovcrflow from a flush tank senling a water closet or urinal shall dischargc into thc fixture scrvcd. 405.8 Slip joint connections. Slip joints shall be made with an approved elastomcric gaskct and shall only hc installed on the trap outlet, trap inlet and within the trap seal. Fixturcs with concc;rlctJ slip-joint connections shall bc provided with an access pancl o r utility space at least 12 inches (305 mm) in its sniallest 2006 INTERNATIONAL PLUMBING CODE@
406.2 Water connection. The water supply to an automatic clothes washer shall be protected against backflow by an air gap ~nstalledintegrally within the mach~ncconforming to ASSE 1007 or with the installation of a backflow prcvcntcr i n accordance with Section 608. 406.3 Waste connection. The wastc from an automatic clotlies washer shall discharge through an air breali into :I standpipe in accordance with Section 802.4 or into a laundry sink. The trap and fixture drain for an automatic clothcs washer standpipe shall be a rainimuni of 2 inches (5 1 111111)i n diameter. Thc automatic clothes washer fixture drain shall conncct to a branch drain or drainage stack a minilnum of 3 inches (76 rnm) in diameter. Automatic clothes washers that discharge by gravity shall be permitted to drain to a waste receptor or an approved trench drain.
I
SECTION 407 BATHTUBS 407.1 Approval. Bathtubs shall conform to ANSI 2124.1, A S M E A1 1 2 . 1 9 . 1 M , A S M E A1 1 2 . 1 9 . 4 M , A S h I E A1 12.19.9M, CSA B45.1, CSA R45.3 or CSA B45.5. 407.2 Bathtub waste outlets. Bathtubs shall have waste outlets a minimum of 1.5 inches (38 mm) in diameter. The wastc outlet shall be equipped with an approved stopper. 307.3 Glazing. Wlndows and doors within :I bathtub encloqure shall conform to tlie safety glaz~ngrecluircrnents of the I~rrer~rrltioizal Buildirz,q Code. 407.4 Bathtub enclosure. Doors within a bathtub cnclosure shall confonu to ASME A1 12.19.15.
SECTION 408 BIDETS 408.1 Approval. Bidets shall conforin to ASME A 1 11.19.2M, ASME A1 12.19.9M or CSA B45. I. 408.2 Water connection. The water supply to a bidct shall be protected against backtlow by an air gap or backflow prevcnter in accortiance with Scction 608.13.1. 608.13.2, 608.13.3, 608.13.5. 608.13.6or 608.13.8. 408.3 Bidet water temperature. l h e dlschargc watcr tcmperature from a bidct fitting shall be li~nitcdto11 maximum temper-
FIXTURES, FAUCETS AND FIXTURE FlTTlNGS
aturc of 110°F (43°C) by a water ternjlerature limiting device conforming to ASSE 1070.
lime a minimum outlet of not less than 3 inchcs (76 nim) in diametcs.
SECTION 409 DISHWASHING MACHINES 409.1 Approval. Donicstic dishwashing ~nachinesshall conl-i)rni to ASSE 1006. Commercial dishwashing machirles shall conform to ASSE 1004 and NSF 3.
SECTION 413 FOOD WASTE GRINDER UNITS 413.1 Approval. Domestic food wastc grinders sh:~Il co11hr11i to ASSE 1008. Commercial food wastc grinders shall conform to ASSE 1009. Food waste grinders shall not incrcase ~ l i c drainage fixture unit load on the sanitary drainagc sysicm.
409.2 Water connection. The water supply to a dishwashing machinc shall hc protected against backtlow by an air gap or backtlow prcvcntcr in accordance with Section 608. 409.3 Waste conncction. T h c waste conncction of a dishwashing ~liacliineshall comply with Section 802.1.6 or 802.1.7, as applicable.
SECTION 410 DRINKING FOUNTAINS 410.1 Approval. Drinking fountains shall conform to ASIME Al11.19.1M,AShilEA1 12.19.2MorASMEAl 12.19.9Mand water coolcrs sl~allcontbrrn to ARI 1010. Drinking fountains and watcr coolers shall conform to NSF 61, Section 9. Where water is scrved in restaurants, drinking fountains shall not be rcquircd. In other occupancies, where drinking fountains are required, water coolers or bottlcd watel-dispensersshall be per1~1itted to be substituted for not more than 50 percent of thc required drinking fountains. 410.2 Prohibited location. Drinking fountains shall not he installed in public restrooms.
SECTION 41 1 EMERGENCY SHOWERS AND EYEWASH STATIONS 411.1 Approval. Emergency showers and eyewash stations shall conform to ISEA Z35X.1. 411.2 Waste connection. Waste connections shall no1 be recluired for emergency showers and eyewash stations.
SECTION 412 FLOOR AND TRENCH DRAINS 412.1 Approval. Floor drains shall conform to ASME A1 12.6.3, ASME A1 12.3.1 or CSA B79. Trench drains shall comply with ASME A1 12.6.3. 112.2 Floor drains. Floor drains shall have reinovcuble strainers. Thc floor drain shall be constructed so that the drain is c;rpablc of being cleaned. Access shall be provided to the drain inlet. 412.3 Size of floor drains. Floor drains shall havc a mini~nuni 2-inch-diameter ( 5 1 mm) drain outlet. 412.4 Public laundries and central washing facilities. In public coill-opcmicd laundrics and in the central washing facilities of multiple-fa~ililydwellings, the rooms containing automatic clothcs washers shall he provided with floor drains located to rcadily drain the entire floor area. Such drains shall 30
413.2 Domestic food waste grinder waste outlets. Dolnestic food waste grinders sliall bc conncctcd to a drain of not less than 1.5 inches (38 mm) in diameter.
413.3 Commercial food waste grinder waste outlets. Commercial food wastc grinder-sshall be conncctcd to a drain a minimum of 2 inches (5 1 m ~ nin) diameter. Con~mercialfood waste grinders shall be connected and trapped scparatcly from any othcr fixtures or sink co~npartments. 413.4 M'ater supply required. All food waste grinders shall be providcd with a supply of cold water.
SECTION 414 GARBAGE CAN WASHERS 424.1 Water coimection. Thc water supply to a garbage can washer shall be protected against backflow by all air gap or a baclctlow preventer in accordance with Section 608.13.1. 608.13.2, 608.13.3, 608.13.5, 608.13.6 or 608.1.3.8. 414.2 Waste connection. Garbage can was1icl.s shall bc trapped separately. 'l'he reccptaclc receiving thc waste frorn the washer shall have a rclnovable baskct or strainer to prevent [lie discharge of large particles into the drainage system.
SECTION 41 5 LAUNDRY TRAYS 415.1 Approval. Laundry trays shall conform to ANSI 2124.6, ASME A1 12.19.1M, ASME A1 12.l9.3M, ASME A1 12.J 9.9M, CSA B45.2 or CSA B45.4. 415.2 Waste outlet. Each cornpal-tment of a la~indrytray shall be provided v;ith a waste outlet a niiiiimum of 1.5 inches (18 mm) in diameter and a strainer or crossbar to restrict tlie clcar opening of the waste outlet.
SECTION 416 LAVATORIES 4116.1 Approval. Lavatories shall conform to ANSI Z124.3, A S M E A 1 1 2 . 1 9 . 1 M , ASlME A 1 1 2 . 1 9 . 2 M , ASIMF, A112.19.3M.ASME.AlI2.19.4M~ ASMEAI 12.19.9M. CSA B45.1. CSA B45.2, CSA B45.3 orCSAI345.4. GI-oupwahh-up equipment shall confol-111to the requiremcnls of Section 402. Every 20 inches (508 lnm) of rim space shall be considered as one lavatory. 416.2 Cultured marble lavatories. Culturerl marhlc vanity tops with an integral lavatory sllall cor~for~n to ANSI Z124.1 or C'SA 845.5. 2006 INTERNATIONAL PLUMBING CODE@
FIXTURES. FAUCETS AND FIXTURE FlTTlNGS
416.3 Lavatory waste outlets. Lavatories shall have waste ouilcts not lcss than 1.25 inches (33 nlm) in diametcr. A strainer. pop-up stoppcr, crossbar or othcr cLevice shall be providctl to rcstrict thc clcar opening of the waste outlet. 416.4 Moveable lavatory systems. lMoveable lavatory systems shall comply with ASME A l 12.19.12. 416.5 Tempered water for public hand-washing facilities. 'Tempered watcr shall bc delivered from public hand-washing facilities through an approved watcr temperature limiting dcvicc that conforms to ASSE 1070.
SECTION 417 SHOWERS 417.1 Approval. Prefabricated showers and shower cornpartmcnts shall confor~nto ANSI 2 124.3, ASME A l 12.19.9M or CSA Bil-5.5. Shower valves for individual showers shall conform to the rcquiremcnts of Section 424.3. 417.2 Water supply riser. Evcry water supply riser from thc shower valve to the shower head outlet. whcthc~exposed or not, shall bc attached to thc mucture in an approved manner. 417.3 Shower waste outlet. Wastc outlcts scrving showers shall bc at lcast 1 inches (38 mm) in diamcter and, for other than waste outlets in bathtubs. shall have removable strainers not lcss than 3 inches (76 mrn) in diametcr with strainer openings not lcss than 0.25 inch (6.4 nnn) in minimum dimension. Wherc cach showcr space is not providcd with an i~ltlividual wastc outlet, thc waste outlet shall he located and the floor pitchcd so that wastc from onc shower does not flow over thc floor area serving another shower. Waste outlcts shall be fastcned to thc wastc pipc in an approved manner. 417.4 Shower compartments. All shower compartments shall have a minimum of 900 square inches (0.58 n12) of interior cross-scctional area. Shower compartments shall not be less than 30 inches (762 mm) in minimu111 dimension ~neasured from thc finished intcrior dimension of the compartmcnt; cxclusivc of fixture valves, showcrheads, soap dishes, and safcty grab bars or rails. Except as required in Section 404, the minimum required area and dimension shall be measured from thc fi nishcd interior dimension at a height equal to the top of the threshold and at a point tanscnt to its ccnterline and shall be continucd to a hcight not less than 70 inches (I778 mm) ahovc the showcr drain outlet. Exception: Shower compartments having not less than 25 inches (635 ~ n min ) minimum dimcnsion measured from the finishcd in~criordimension of thc compartmentl provided that the shower compartment has a minimum of 1,300 square inches (.838 m2) of cross-scctional arm. 417.4.1 Wall area. The wall area above built-in iubs with installed shower hcads and in showcrcompartrr~rntsshall be constructed of smooth, noncorrosive and nonabsorbent waterproof materials to a height not lcss than 6 feet (1829 mm) above the room floor level, and not lcss than 70 inches (1778 mm) where measured from the compartmcnt floor at Such walls shall form a water-tightjoint with cach the tlr;~i~i. other and with either the tub, receptor or shower floor. 2006 INTERNATIONAL PLUMBING CODE@
417.4.2 Access. The shower compartmcnt ~lccessand cgress opening shall havc a minimum clear and unohstructcd finished width of 22 inches (559 mm). Shower compartments required to bc designed in conforlnancc to accessibility provisions shall comply with Section 404.1. 417.5 Shower floors or rcceptors. Floor surfaccs shall bc constructed of inlpervious, noncorrosivc, nonahsorbcnt andwaterproof materials. 417.5.1 Support. Floors or rcceptors under shower compartments shall be laid on. and supported by, a smooth and structurally sound base. 417.5.2 Shower lining. Floors utldcr shower compartments, except where prefabricated receptors have been provided, shall be lincd ant1 made water tight utilizing matcrial complying with Sections 4 17.5.2.1 through 417.5.3.4. Such liners shall turn up on all sides at least 2 inches (51 ~ n m ) above the finished threshold level. Liners shall bc recessed and fastened to an approvcd backing so as not to occupy thc space requircd for wall covering, and shall not he nailed or perforated at any point lcss than I inch (25 intn) above the finished threshold. Lincrs shall bc pitched onc-fourth unit vertical in I 3 units horizontal (2-perccnt slope) and shall be sloped toward the fixture drains and be sccurcly fastcncd to the waste outlet at the scepage cntrance. making a water-tight joint between the liner and thc outlet. Exception: Floor surfaces onder showcr hcads providcd for rinsing laid dircctly on thc ground arc not rccluircd to con~plywith this section. 417.5.2.1 YVC sheets. Plasticized polyvinyl chloridc (PVC) sheets shall be n mi~lirn~u~n of 0.03C) inch (1.02 mm) thick, and shall meet the rcquircments of ASTJMD 4551. Sheets shall bc joincd by solvcnt w c l d i n in accordance with the manufacturer's installation instl-uctions. 417.5.2.2 Chlorinated polycthyle~ieICPE) sheets. Nonplasticizcd chlorinated polyethylcnc shcet shall be a niinimurn 0.030 inch (1.02 mm) thick. and shall n ~ e cthe t requirements of ASrTR4D 4068. The liner shall bc joincd in accordance with the manufacturer's installation instructions. 417.5.2-3 Sheet lead. Sheet lcad shall not weigh less than 4 pounds per squarc foot (19.5 kg/m2) coated with an asphalt paint or othcr approvcd coating. The lead sheet shall be insulated from conducting substanccs othcr than thc connecting drain by ~ S - I J O L(6.80 I I I ~ kg) asphalt felt or itscquivalent. Sheet lead shall bcjoined by burning. 417.5.2.4 Sheet copper. Sheet copper shall conform to ASTM B 152 and shall not wcigh less than 12 ourlccs pcr squarc foot (3.7 kg/m2). 'UIC copper shcet shall be insulatedfrom conducting substances other than the connecting drain by 15-pound (6.80 kg) asphalt felt or its equivalent. Sheet copper shall bc joined by brazing or soldering. 417.6 Glazing. Wlndows and doors w~thina \howc~enclo\urc shall conform to the safety glazing requircmcnts ofthc 11rtenli~tionul R~~lldiizg Co~fe.
FIXTURES, FAUCETS AND FIXTURE FITTINGS
SECTION 418 SINKS 418.1 iipproval. Sinks shall conform to ANST Z124.6, ASME A112.19.1M, ASME A112.19.2M. ASME A112.19.3M, ASME A l 32.19.4M, ASME A1 J2.19.9M, CSA 845.1, CSA B45.2, CSA B45.3 or CSA B45.4. 418.2 Sink waste outlets. Sinks shall be provided with waste outlets a minimum of 1.5 inches (38 rnm) in diameter. A strainer or crossbar shall bc provided to restrict the clear opening of Lhc waste outlet. 418.3 Moveable sink systems. Moveable sink systems shall comply with ASME A1 17_.19.12.
SECTION 419 URINALS 419.1 Approval. Urinals shall confol-nl to ANSI 2124.9, ASME Al12.19.2M, CS.4 B45.1 or CSA R45.5. Urinals shall confol-m to the water consuniption requirements of Scction 1 604.4. Water supplied urinals shall confornl to the hydraulic perfomlance requirements of ASMB A1 12.19.6, CSA B15.1 or CSA B45.5. 419.2 Substitlition for water closets. In ench bathroom or toilet roonl. urinals shall not be substituted for more than 67 percent of lhc required water closets in assembly and educational occup:~ncies.Urinals shall not be substituted Sor more than 50 percent of the required water closcts in all other occupancies.
[B] 419.3 Surrounding material. \Val1 and floor space to a point 2 feet (6 10 nim) in front of a urinal lip and 4 feet (12 19 n i n ~abovc ) the floor ancl at least 2 feet (610 mni) to each side of the urinal shall hc waterproofed with a \rnooth, readily cleanal>lc. nonabsorbent material. SECTION 420 WATER CLOSETS 420.1 Approval. Water closets shall conform to the water consumptiohArequirementsof Section 604.4 and shall conform to ANSI 2124.4, ASME '41 12.19.2M. CSA B45.1, CSA B45.4 or CSA B45.5. Water closets shall conform to tlie hydraulic perforniance requiren~entsof ASME Al 12.19.6. Water closet tanks shall collform to ANSI 2124.4, ASME A1 12.19.2, ASME A l 12.19.9h5, CSA B45.1, CSA B45.4 or CSA B45.5. Elcctro-hydraulic water closcts shall colllply with ASME A112.19.13. 420.2 Water closets for public or employee toilet facilities. Water closet bowls for public or en~ployeetoilet facilities shall be of the elongated type. 420.3 Water closet seats. Water closets shall be equipped with seatsof snlooth. nonnbsorbcnt material. All scats of watesclosets provided for puhlic or employee toilet facilities shall he of the hinged open-front type. Integral water closct seats shall be of thc same material :is the fixturc. Water closet seats shall be si7cd for the watcr closct bowl type. 420.4 Water closet connections. A 4-inch by 3-inch ( 102 mm by 76 mm? closct bend shall be acceptable. Where a 3-inch (76 mm) bend is utilized on water closets. a 4-inch by 3-inch (102
mni by 76 nun) flange shall be installed to receive the lixturc horn.
SECTION 421 WHIRLPOOL BATHTUBS 421.1 Approval. Whirlpool bathtubs shall comply with ASME A1 12.19.7M or with CSA B45.5 and CSA B45 (Supplement 1). 421.2 Installation. Whirlpool bathtubs shall be installed and tested in accordance with the manuhc~urer'sinstallation inst~uctions.Tlie pump shall be located abovc the weir of thc fixture trap.
!t
421.3 Drain. T i c pump drain and circulation piping shall be sloped to drain the water in the volute ancl the circukition piping when the whirlpool bathtub is empty. 421.4 Suction fittings. Suction fittings for whirlpool bathtubs shall comply with ASME A1 12.19.8M. 421.5 Access to pump. Access shall be provided to circulatiou pumps in accordance with the fixture or pi~nlpmanufacturer's installation instructions. Where the manufacturer's instructions do not specify the location and minimum size offield-fahricated access openings, a 12-inch by 12-inch (305 rnm by 305 ~ n m )minimum sizcd oper~ingshall be insttlllcd to provide access to the circulation pump. Wherc pumps arc located mol-c than 2 feet (609 mm) from the access opening, an 18-inch by 18-inch (457 mm by 457 mm) minimum sized opening shall be installed. i\ door or pane! shall be permitted to closc the opening. In all cases. the access opcning shall be unobstructed and of the size necessary to permit the removal and replaccmcnt of the circulation pump. 421.6 Whirlpool enclosure. Doors within a whirlpool cnclosure shall conforni to ASME A l 11.19.15.
SECTION 422 HEALTH CARE FIXTURES AND EQbllPMENT 422.1 Scope. This scction shall govern those aspects of health care plumbing systems that diffcr from plumbing systcms in other structures. Health care plumbing systelns shall confor111 to the requirements of this section in addition to the other requirements of this code. The provisions of this section shall apply to the special devices ant1 ecluipmcnt installcd and maintained in the following occupancies: nursing honlcs, homcs for the aged, orphanages, infirmaries, first aid stations, psychi:~tric facilil.ies, clinics, profcssio~ialoffices of dcntisrs and doctors, mortuaries, educational facilities, surgery, dcntist~y,rescarch and testing laboratories, establishments manufacturing pharnlaceutical drugs and medicines, and other structures with siniilar apparatus and equipment classificd as plumbing.
422.2 Approval. All 5pecial plu~r~bing fixtures, cqu~pn~ent, dcviccs and apparatus shall he of an approved typc. 422.3 Protectiora. All devices, appurtenl~nces,appliances and apparatus intended to serve some special fi~nction,S L I L as ~ sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to either the water supply or drainage system, shall be provided with proteclion against backtlow, 2006 INTERNATIONAL PLUMBING CODE@
FIXTURES, FAUCETS AND FIXTURE FITTINGS
flooding, fouling. contamination of thc water supply system and stoppage of thc drain.
422.4 Materials. Fixturcs designed for therapy. special cleansing or disposal of wastc m:~terials,co~nbinationsof such purposes, or any other special purpose, shall be of smooth. inipcrvious, cor~osion-resistantmaterials and. where subjected to tenlperatures in excess of 180°F (82"C), shall be capable of withstanding. wilhout damage. higher temperatures. 422.5 Access. Access shall be provided to concealed piping in connection with special fixtures where such piping contains steam traps, valves, relief valves, check valves. vacuum breakers or othcr sinlilrrr items that require periodic inspection, servicing, maintenance or rcpair. Access shall be provided to concealed piping [hat requires periodic inspection, maintenance or rcpair. 422.6 Clinical sink. A clinical sink shall have an integral trap in which the upper portio~iofa visible trap scal provides a water surface. 'Thc fixturc shall be designed so as to permit complete I-enloval of the contents by siphonic or blowout action and to reseal the trap. A flushirlg rim shall provide water to cleansc thc inlerior surface. Thc fixture shall have the tlushing and cleansing characteristics of a watcr closet. 422.7 Prohibited usage of clinical sinks and service sinks. A clinical .sink scrving a soiled util~tyroom shall not he considcrcd as a subslitute for. or be utilized as, a servlce sink. A service sinli shall not bc utilizcd for the disp~s;llof urine, fecal lnattcr or othcr hurnan waste. 422.8 Ice prohibited in soiled utility room. Machines for manufacturing ice, or any device for the handling or storagc of icc, shall not bc locatcd in a soilctl ulility room. 422.9 Sterilizer eijuipment requirements. The approval and installation of all stcrilizcrs shall conform to the requirements ~~al Code. of thc I ~ ~ r e n r a r i oMec,hunic~rl 422.9.1 Sicrilizer piping. Access for thc purposes of inspect~onand niaintenance shall he provided to all stcrilixrpiping and dcvices necessary for the operation of stcrilizcrs. 422.9.2 Steam supply. Steal11supplies to sterilizers, including those connected by pipes fi-on1 overhead mains or bra~~ches, shall be drained to prevent any moisture from rcaching thc sterilizer. Thc condensate drainagc from thc steam supply shall be discharged by gravity. 422.9.3 Stearn condensate return. SLeam condensate returns froni sterilizers shall be a gravity return system. 422.9.4 Condensers. Pressure sterilizers shall be equipped with a means of condensing and cooling the exhaust steam vapors. Nonprcssure sterilizers shall bc equipped with a dcvice that will aulotuatically control the vapor. confining the vapors within thc vessel. 422.10 Special elevations. Control valvcs, vacuum outlets and dcvices protruding from a wall of an operating, cmcrgency. recovery, exanlining or dclivcry room. or in a corridor or other location whcrc patients are lransportcd on a wheeled stretcher. shall bc located at an elevation that prevents bumping thc patient crr stretcher against the cievice. 2006 INTERNATIONAL PLUMBING CODE@
SECTION 423 SPECIALTY PLUMBING FIXTURES 423.1 M'ater connections. Baptisteries, orn;~mcntaland lily pools, aquariums, ornamental fountain basins. swimming pools, and similar constructions. whcrc providcd with water supplies, shall be protected against backtlow in accordat~ce with Section 608. 423.2 Approval. Specialties requiring watcl- and wastc conncctions shall be submitted for approval.
SECTION 424 FAUCETS AND OTHER FIXTURE FITTINGS 424.9 Approval. Faucets and fixture fittings shall conform to AShlE A1 12.18.1 or CSA B125. Faucets and fixlure fittings that supply drinking watcr for human ingestion shall conform to the requirements of NSF 61, Section 9. Flexible water connectors exposed to continuous pressurc shall conforn~to the requirements of Section 605.6. 424.1.1 Faucets and supply fittings. Faucets and supply fittings shall conform to [he water consunlption rcquircnlcnts of Scction 604.4. 424.1.2 Waste fittings. waste fittings shall conforni to ASME A1 12.18.2, ASTM F 409. CSA B 125 or to one of thc standards listed in Tables 702.1 and 702.4 for above-ground drainage and vent pipe and filtings. 424.2 Hand showers. Hand-held showers shall confbnn to ASME A l 12.18.1 or CSA B 125.1. Hand-hcld showcrs shall provide backflow protection in accordance with ASME A112.18.1 01 CSA 3125.1 or shall be p~otcctcdagainst backflow by a device coniplying with ASME A1 12.15.3.
424.3 Individual shower valves. Individual shower and tub-shower combination valves shall be balanced-pressure. thermostatic or combination balancetl-PI-essul.c/tllc~-111ostatic valves that conform to the recluirenients of ASSE 10 16 or CSA B175 and shall be installcd at the point of use. Shower and I tub-showcr comhination valves required by this section shall be equipped with a ~neansto limit the maximum selling of thc valvc to 120°F (3g°C), which shall bc field adjusted in accordance with the manufacturer's instructions. In-line thcrnmostatic valvcs shall not be utilizcd for co~npliancewith this section.
I
424.4 Multiple (gang) showers. Multiplc (gang) showcrs supplied with a single-temper-ed water supply pipe shall have the water supply for such showcrs controlled by an approvcd automatic temperature control mixing valve that confor~nsto ASSE 1069 or CSA B 125, or each shower head shall be individually corltrolled by a balanced-pressure, thermostatic or combination balanced-pressure/thermostatic valvc that confornls to ASSE 1016 or CSA B125 and is iustalled at thc point of use. Such valves shall be ccluipped with a means to limit thc maximum setting of the valve to 120°F (49°C). which shall he ticld adjusted i n accordance with thc manufacturer's instructions. 424.5 Bathtub and whirlpool bathtub valves. Thc hot watcr supplied to bathtubs and whirlpool bathtubs shall bc limitctl~o a maximum ternpcraturc of 120°F (49°C) by a water te~upcrature limiting dcvice thatconfonns to ASSE 1070, except whcrc
FIXTURES, FAUCETS AND FlXTURE FITTINGS
such protection is otherwise providccl by a combination tublshowcr valve in accordance will1 Section 424.3.
B
424.6 Hose-connected outlets. Faucets and fixture fittings with tiobe-connected outlets shall conform to ASME A111.18.3M o r C S A B l 2 5 . 424.7 Il'cmperatu~-e-acltuated,flow reduction valves for individual fixture fittings. Temperature-actuated, flow reduction devices. where installed for indiviclual fixture fittings, shall conform to ASSE 1062. Such valves shall not be used alonc as a substitute for thc balanced prcssure, thermostatic or combination shower valves required in Section 424.3. 424.8 'l'ransfer valves. Deck-mountcd bath/showcr transfer valvcs containing an integral atmospheric vacuum breaker shall conform to the requil-cme111sof AShlE A1 12.18.7.
SECTION 425 FLUSHING DEVICES FOR WATER CLOSETS AND URINALS 425.1 Flushing devices required. Each water closet. urinal. clinical sink and any plunlbing fixture that depends on trap siphonape to dischargc the fixture contents to the drainage systen1 shall be provided with a flushomcter valvc, flushometcr tank or a flush tank designed and installed to supply water in cluantity a l ~ drate of flow to flush the contents of thc fixture. cleansc the fixture and rcfill the lixture trap.
the tank at the maximum rate at which the tanks arc supplictl with water according to the manufacturer's design conditions. The opening of the overflow pipe shall be located above the flood level r11n of the water closet or urinal or above a secondary overtlow in the flush tank.
425.3.3 Sheet copper. Sheet copper utilized for flush tank linings shall confonn to ASTM B 152 and s11;111 not wcig11 less than 10 ounces pcr squarc foot (0.03 kgln~'). 425.3.4 Access required. All parts in a flush lank shall hc accessible h r repair and replacement. 425.4 Flush pipes and fittings. Flush pipes and filtings shall be of nonferrous material and shall conform to ASMI5 A112.19.5 or CSAB125.
SECTION 426 MANUAL FOOD AND BEVERAGE DISPENSING EQUIPMENT 426.1 Approval. Manual food and beverage dispensing equipment shall confor~nto the requirements of NSF 18. SECTION 427 FLOOR SINKS 427.1 Approval. Sanitary floor sinks shall conform to thc requircmcntx of ASME A1 12.6.7.
425.1.1 Separate for each fixture. A flushing dcvice hall not serve more than one fixture. 425.2 Flushometer valves and tanks. Flusho~ncter\ralvcs and m on tanks shall c01np1y with ASSF. 1037. V a c ~ ~ ubreakers flushomcter valves shall conform to the performance requirenlents of ASSB 100 1 or CSA B64.1.1. Access shall be providcd to vacuum brcalcers. Flushotneter valvcs shall he of the water-c.onservation type and shall not bc utilized where the watcr pressure is lower than the minimum requircd for nor~nal operation. When operated, the valvc shall auto~naticallycornplctc the cyclc of operation, opening f~tllyand closing positively undcr the watcr supply prcssure. Each flushornctcr valve shall be provided with a means for regulating the flow through thc valvc. The tl.ap acal to the fixture shall bc automatic:~lly ~.cfillcdaftcr each valve flushing cyclc. 425.3 Flush tanks. Flush tanks equipped for manual flushing shall be controlled by a device designed to refill the tank after each discharge and to shut offco~nplctelythe watcr flow to the tank whcn the tank is fillcd to operational capacity. The trap scal to thc fixture shall bc automatically refillcd aftcr each flushing. The water supply to flush tanks equipped for automatic flushing shall be controlled with a timing devicc or sensor control deviccs. 425.3.1 Fill valves. All flush tanks shall bc equipped with an antisiphon fill valve conforming to ASSE 1002 or CSA I3 125. The fill valve backflow prcvcnter shall be loc:~tedat least 1 inch (75 111111)abovc the full opening of the overflow pipe. 425.3.2 Overflows in flush tanks. Flush tanks shall be pro\idcd with o\,crflows discharging to thc water cloaet or urinal connected thereto and shall be si7.ed to prevent tlooding 2006 INTERNATIONAL PLUMBING CODE@
CHAPTER 5
VVABER HEATERS SECTION 501 GENERAL
501.1 Scope. The provisions of this chapter shall govern the ~natcrials,dcsign and installation of water heaters and the related safcty devices and appurtenances.
502.2 Rooms used as a plenum. Water heaters using solid, liquid or gas fuel shall not be installed in a room containing air-handling niachi~ierywhen such roorn is used as a plenum. 502.3 Water heaters installed in attics. Attics cont;~ininga water lleater shall be provided with an opellinp ;ind unobstructed passageway large enough to allow relnoval of the water heater. he passageway shall not be lcss than 30 inches (762 mm? high and 22 inches (559 nim) wide and not more than 20 feet (6096 mm) in length when mcasured along the centerline of thc passagcway from thc opcning to the water hcater. The passageway shall have continuous solid flooring not lcss than 21 inchcs (GI 0 mm) wide. A level scrvicc spacc at least 30 inclies (762 mm) deep and 30 inchcs (762 urn) widc shall be present at the front or service side of the water heater. The clear access opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm by 762 mm) whcre such dimensions 31-e large enough to allow removal of the watcr heatcr. ~
501.2 Water heater as space heater. Where a conlbinat~oil potahle water hcating and spacc heating system requires water for space hcat~ngat tcmpcratures higher than 140°F (60°C), a mastcr thermoqtatic mixing valve complying with ASSE 1017 shall be providcd to limit the water supplied to the potable hot watcr clistrihution system to a temperature of 140°F (60°C) or less. The potabilily of the watershall bema~ntaincdthroughout the system. 501.3 Drain valvcs. Drain valvcs for emptying shall he ~nstallcdat the bottom ot each tank-type watcr heatcr and hot water storage tank. Drain valvcs shall conforn~to ASSE 1005. 501.4 Location. Water heaters and storage tanks shall be located and conncctcd so as lo provide access for observation, maintcnancu, wrvicing and replacement. 501.5 Water heater labeling. All watcr hcaters shall be third-party certified. 501.6 M7atertemperature control in piping frotn tankless heaters. The temperature of water from tanl
-
502.4 Seismic supports. Where earthquake loads are applicable in accordancc with thc Inteulatio~zulBuilding Cod@,watcr heater supports shall be designctl and installed for the seismic forces in accordance with the Irztenlationtrl Blrildi~rgCodc.
SECTION 503 CONNECTIONS
503.1 Cold water line valve. The cold water branch line from the main watcr supply line to each hot water storage tank 01. watcr heater shall be provided with a valvc. located near the equiprncnt and serving only thc hot water storage tank or water of the heater. The valve shall not interfere or cause a disr~~ption cold water supply to the remainder of thc cold water system. The valve shall bc probided with access on {hesame floor level as thc water hcatcr served. 503.2 Water circulation. The method of connecting a circulating water heater to the tank shall providc proper circulation of watcr through the watcr heatcr. Thc pipe 01-tubes required for the installation of appliances that will draw from the watcr hcatcr or storage tank shall comply with the provisions of this code for material and installation.
SECTION 504 SAFETY DEVICES SECTlON 502 INSTALLATION
503.1 Gencral. U'atcr heaters shall he installed in accordance with the manufacturer's installation instmctions. Oil-fired water- hcatcl-s shall conform to the requirements of this code L / ~ ~ o I / L I /Code. Elcctric water hcaters and the I ~ I . ~ L > I . I z IWe~Iiuizir(11 shall conform to the requirements of this code and provisions of thc ICC Elrc.it.ic.cil Codc. Gas-fired water healers shall conFuel Giis Code. form to the requircmcnts of the Ii~tet~r~rrtiorir~l 2006 INTERNATIONAL PLUMBING CODE@
504.1 Antisiphon devices. An approved nicans, such as a cold watcr "dip" tube with a holc at thc lop or a vacuum rclicf valve installed in thc cold water supply line nbovc thc top of the heatcr or tank, shall be provided to prevent siphoning of any storage water heatcr or tank. 501.2 Vacuunl relief valve. Bottom fed watcr hcaters and bottom fed tanks connected to water hcillcrs shall have a ~ ; I ~ U L I I ~ relief talve installed. The vacuum relief valvc shall coi~lply with ANSI 2 2 1.22.
WATER HEATERS
504.3 Shutdown. A rncans for disconnecting an clectric hot water supply systeni from its energy supply shall be provided in accordance with the ICC Electrical Codr. A separate valve sh:11 I bc provided to shut off the energy fuel s~ipplyto all other lypcs of hol water supply syste11is. 504.4 Rclief valvc. All storage water heaters operating above atlilosphcric pressure shall be provided with an approved, sclf-closing (Ic\icred) pressure rclief valve and temperature relicf val\~eor corubinntion thereof. The relief valve shall confor111to ANSI 221.22. The relief valve shall not be used as a means of controlling thcrnlal expansion.
504.4.1 Installation. Such valves shall be installed in the shcll of thc wakr hcatcr tank. Tc~llperaturcrelief valves shall he so locntcd in the tank as to bc actuated by the water c 6 inches (152 nun) of thetank scrvcd. Fnr instailain ~ l i top tions with scparatc storage tanks, thc valves shall be installed on the tank and therc shall not be any type of valvc installed hctwcen the water heatcr and thc stol-age tank. Thcre shall not be a chcck ~ a l v or e shutoff valve betwcen a relief valvc and thc hcatcr or tank served.
504.5 Kelief valve approval. Temperature and pressurc relief valvcs. or conibinntions thereof, and encrgy cutoff devices d and shall have a temshall bcar the labcl of a11a p p ~ o \ ~ cagcncy pcraturc sctting of not more than 210°F (99°C) and a pressure setting not cxcecding the tank 01-watcr heater manufacturer's ratctl worlcing pressure or 150 psi (1035 m a ) : whichevcr is Icss. The relieving capacity of cach pressure relief valve and each tc~npcl.aturerclicf valvc shall equal or cxcecd the lieat input to thc watcr heater 01-storage tank. 504.6 Requirements for discharge piping. The discharge piping scrving a pressure relief valve, temperature relicf valve or combinatin11 thereof shall:
12. Not have valves or tee fittings. 13. Be constructed of those materials lisrcd in Section 605.4 or matc~ialsIcsted. ratcd and ~lpprovedfor such use In accordance with ASMt: A1 12.4.1. 504.7 Required pan. Wherc water heaters or hot water storage tanks are installed in locations whcrc lcakagc of thc tanlis or collnections will cause damage: the tank or water hcnter shall be installed in a galvanized steel pan having a minimwn thicliness of 24 gage, or other pans approved for such use. 504.7.1 Pan size and drain. The pan shall be not less than n ) and shall be of sufficient size and 1.5 inches (38 ~ n ~deep shape to receive all dripping or cvndcnsatc froin tho tank or water heater. The pan shall be drainctl by an intlircct waste pipe having alninilnum diameter of 0.75 inch ( I9 mm). Piping for safety pan drains shall be of thosc materials listcd in Table 605.4. 504.7.2 Pan drain termination. The pan tl~-ainshalL c,xtcnd full-size and terminatc ovcra suitably located indircct waste receptor or noor drain or cxtend to the cxtcrior of thc build) not ing ar~dterminate not less than 6 inches (152 m ~ n and more than 24 inchcs (610 mm) above the ad.jacent ground surfacc. SECTlON 505 INSULATION [El 505.1 Unfired vessel insulation. Unfircd hot watcr storage tanlis shall be insulatcd so that heat loss is li~nitcdto a maximum of 15 British thermal units per hour (Btuih) per square foot (47 W/m2) of cxtcrnal tank SUI-faceal-ca. Fol- plirposes of determining this heat loss. the dcsign ambient tcn1pcrature shall not be higher than 65°F (I 8°C).
1. Not he dircctly connected to thc drainage systcm. 2. Dischargc through an air gap located in the same room as the water hcater. 3. Not he sn~allcrthan the diamcter of the outlct of the valve scrvcd and shall discharge full s i x to the air gap.
1.Sene a single ~cliefdevice and shall not connect topiping scrving any other relief device or equipment.
5. Discharge to the floor, to an indirect waste receptor or to the outdoors. Whcre discharging to the outdoors in arcas subjcct to freezing, discharge piping shall be first piped to an indirect waste receptor through an air gap located in a conditioncd arca. 6. Discharge in a inanner that docs not cause personal injury or stnlctural dasn:~ge.
7. Dischargc to a termination point that is rcadily obse~vable by the building occupants. 8. Not bc trapped. 9. Bc installed so as to flow by gravity
10. Not tcrminatc molc rhan 6 inches ( 1 52 mm) abovc the floor or wavtc rcccptor. 1 1. Not have a threaded connection at the end of such pipislg. 2006 INTERNATIONAL PLUMBING CODE@
+r
I
CHAPTER 6
WATER SUPPLY AND DlSTWlBLlPlOlM SECTION 601 GENERAL 601.1 Scope. This chapter shall govcrn the materials, design and installation of water supply systems, both hot and cold, for utilization in conncctio~lwith human occupancy and habitation and shall govern the installation of individual water supply systems. 601.2 Solar energy utilization. Solar energy systems used for hcating potable wntcr or using an independent medium for hcating potable watcr shall comply with the applicable requircments of this code. The usc of solar energy shall not compromisc the rcquire~nentsfor cross connection or protectiorl of the potablc watcr supply system rcquircd by this codc. 601.3 Existing piping uscd for grounding. Exihtirlg metallic watcr scrvice piping uscd for electrical grounding shall not be replaccd with non~netalllcplpe or tubing until other approved mcans of grounding is provided. 601.4 Tests. The potablc water distribution systcm shall hc tested in accordancc with Scction 3 171.5.
SECTION 602 WATER REQUliRED 602.1 General. Every structure equipped with plu~nhingtisturcs and utilizcd for human occupancy or habitation shall be provided with n potablc supply of watcr in the amounts and ar the pressures specified in this chapter. 602.2 Potable water required. Only potablc water shall bc supplicd to plun~bil~g fixtures that providc watcr for drinking, bathing or culinary purposes, or for the processing of food, medical or phannaceutical products. Unless otherwise provided in this code, potable water shall bc supplied to all plunlbing fixtures. 602.3 Individual water supply. Where a potable public water supl.~lyis not available, iridividual sources of potablc water supply shall bc utilized.
602.3.1 Sources. Depcndcnt on geological and soil conditions and thc amount of rainpall, individual water supplies arc of thc followin? types: clrilled well, driven well, dug well. borcd well. sp1.111g.stream or cistern. Surfacc bodies of water and land cisterns shall not be sources of individual watcr supply unless properly trcatcd by approvcd means to prevcnt contamination. 602.3.2 Minimum quantity. 'l'he combined capacity of the source and storage in an individual watcr supply systcln shall supply tile f i x t ~ ~ rwitli c s watcr at rates rtndprcssures as rccluircd by this chaptcr. 602.3.3 Water quality. Water froln an individual water supply shall I?c approved as potablc by the authority having jurisdiction PI-iorto conncction to the plumbing system. 2006 INTERNATIONAL PLUMBING CODE@
602.3.4 Disinfection of system. After construction or major rcpair. thc individual water supply systcln shall be p ~ ~ r g eofd deleterious matter and disinfected in accordance witli Section 610. 602.3.5 Pumps. Pumps shall bc ratcd for the transport of potable watcr. Pumps in an individual water supplj :y s stcm shall be constructed and installed so as to prevent contamination tiom entering a potable water supply through the pump units. Pumps shall be sealed to the well casing 01.covercd with a water-tight seal. Pun~psshall be designed to maintain a primc and installed such that ready access is provided to the pump parts of the entire asscmbly for repairs. 602.3.5.1 R ~ m penclosure. The pump room or cnclosure around a well pump shall he drained and protcctcd from freezing by heating or othcr approvcd means. Where pumps arc installed in basements, such pumps shall be mounted on a block or shelf not less lhan 18 inches (457 mm) above the basement floor. Wcll pits shall be prohibited.
SECTION 603 WATER SERVICE 603.1 Size of water service pipe. Thc watcr scrvice pipe shall be sized Lo supply water to the structure in thc cluantitics and at the pressures required in this code. Thc rnini~numdia~nctcrof watcr servicc pipe shall be -1, inch (19.1 ~ilm).
603.2 Separation of water service and building sewer. Water service pipe and the building sewer shall be scparatcd by 5 fcct (1524 mm) of undisturbed or cornpactetl earth. Exceptions:
1. The rcquircd scparation distance shall not apply where the bottom of the water service pipc within 5 feet 11524 m ~ n )of the sewer is a r n i ~ ~ i m ~of l r o17 inches (305 mm) above the top of the highest point of the sewer and the pipe materials conforn~lo Tablc I( 702.3. 2. Water service pipe is pcr~nittedto be localed in thc same trcnch with a building scwer, providcd such scwer is constr~~cted of materials listcd in Tablc 702.2. 3. Thc required scparation distance shall not apply where a watcr service pipc crosscs a sewer pipe, provided the water service pipe is sleeved to at lcast 5 feet ( I 524 mm) horizontally fro111the scwcr pipc centcrlinc on both sides of such crossing with pipe matcl.ials listcd in Tablc 405.3, 702.2 or 702.3. 6032.1 Water service near sources of pollution. Poiablc watcr service pipcs shall not be located in, undcr or abovc cesspools, scptic tanks, scptic tank drainagc ficlds or seepage pits (secSection 605.1 for soil and grou~ldwatcrconditions). 37
WATER SUPPLY AND DISTRIBUTION
SECTION 604 DESIGN OF BUILDING WATER DISTRIBUTION SYSTEM
604.4 Maxinlu~nflow and water consumption. l'hc maxiconsumption flow rates and quantities for all plumbing fixture!: and fixture fitti~igsshall be in acco~.dance with Table 604.4. I I ~ L ~ water II~
604.1 General. The design of the water distributio~isysten~ shall conform to acccpted engineering practice. Mcthods ntilized to dctcnnlnc pipc sizcs shall be approved.
Exceptions: 1. Blowout dcsign water closcts hav~nga ~ ~ ~ ; l x i m u6r n water consumption of 3.5 gallons (13 L) per flu5hing cycle.
604.2 System interconnection. At thc points of interconnection between the hot and cold water supply piping systems and the individual fixtures, appliances or devices, provisions shall be matlc to prcvcnt tlow betwccn sac11 piping systems. 604.3 Water distribution system design criteria. The water distribution system shall be designed, and pipe sizes shall bc selectcd such that under conditions of peak demand, the capacities at the fixturc supply pipe outlets shall not be lcss than shown in Table 604.3. The minimum flow rate and flow pressure providcd to fixtures and applia~lccsnot listed in Table 604.3 shall be in accordance with the manufacturer's installation instnlctions.
1
FIXTURE SUPPLY
OUTLET SERVING
.-.
1
-
~
OR FIXTURE FITTING
-
. .. . .- -
-
FLOW
-
-PLUMBING - . .. .--.-- ... I
-- . -~.
1-' ~ a v_a t o_-rpubl~c, ~, (met~.rjr~g)
pRESSsEjpi)+
(gpm)
r-~I
TABLE 604.4 MAXIMUM FLOW RATES AND CONSUMPTION FOR PLUMBING FIXTURES AND FIXTURE FITTINGS --
i-~
-
FLOW RATEa
5. Emergency showers
~ a v a t o rprivate ~ , ----
TABLE 604.3 WATER DISTRIBUTION SYSTEM DESIGN CRITERIA REQUIRED CAPACITY AT FIXTURE SUPPLY PIPE OUTLETS - - --- --- -
1
2. Vegetable sprays. 3. Clinical sinks having a maximum water consumption of 4.5 gdllons (17 L) per flushing cyclc. 4. Service sinks.
-
-
-
--
d"
-
.
I
.
.
..
Water clohct
- - .- .
~! 1
1
,
tI .
!
I
.
-
1~
~
~
0.5 gprn at 60 psi
i
.
-
-
i
-
-
~~
-
~-_/
! s i n k faucet
4
--
I
~ i l v r i o rpublic ~, (other than nletering) I Shol\~cr he -
7 2 gpn~at 60-psi -.. .z. _ . 14 0 25 galion p c ~metcnng cqcle
1
.
-
''
i:- gpm at 60 psi .
9
4 1
"t-"!'."i~
?.P ' ~!I.
i
-
-
~
i - 1I
~1 ~:
I I R e l l r pcxfl~lshin~cycle 1.6 gallons per flushing cyclc 1 --- ,-~ ~-
.
..
-~
~
.~
~~
~-
-
-
1 gallon = 3.785 I.; 1 gallon per minute = 3.785 Lim, 1 pound per squat-e inch = 6.805 kPa. a. ;Zhardheld shn\ver spruy is a showcr head. b. C o n s u ~ n p t i civlrrances ~~~ shall hc determined from ~.ckrencedstnndn~'ds.
For SI:
Ishowel., temperature controlletl-~!
Ii Slllcc)~k, : hoscbi@ -
-
-
-
-
~
i~Tnk,residential . -
~~
[ S i i , hcrvicc Urinal. valve ~
~
-~
I
i - - - --
-
-
~
( ~ a t cciosct. r. blow out, I flusholneter valve. _ . .
'-5
.
-
I
,.
-~ - . _ . ~ . ~
-
closet, siphonie. !usll?meler~valve--
!I
1 Water
/
~~~
-
I
I.~ I i
l l L _ .._) I
1
1 /water closet, - . Ilucl~on~cte~~ rank J -
.
! ~-. -
35
-. - . - -'
I.(,
25
-
I
,!.-
--
-.
I
i
25
I
1 -1
---
15
-!
-~~--
--
--(
For SI: I pound pcr squal'c inch = 6.895 kRt. 1 gallon per rnir~clte= -7.785 I,!m. Foradtlitioll:~l~~cquirerncr~tsfo~~llowratcs nlldqu:~ntiLiuh.see Sedion 604.4.
21.
I
!
15 - - ~
604.5 Size of fixture supply. The minimum size of a fixture supply pipc shall he as shown in Tablc 604.5. Thc fixturc supply pipe shall not tennillate more than 30 inches (762 nun) fro111 the point of co~inectionto the fixture. A reduced-size flexible water conncctor installed b e ~ w e e 1hc ~ i supply pipe and the fixture shall be of an approved type. The supply pipc shall extend to the floor or wall adjacent to the fixture. The minimum size of individual distribution lines utilized in griddcd or parnl- B lel water distribution systems sllall beas shown in Table 604.5. 604.6 Variable street pressures. Wherc strecl water main pressures fluctuate, thc huilding watcr distribution systcm sl~all be designed fbr the minimum pressure availablc. 604.7 Inadequate water pressure. Wherever water prcssurc tiorn the strect main or other source of supply is insufficient to providc fiow pi-essures at tixturc outlels as required under Tablc 604.3, a water pressure booster systc~nconforming Lo Section 606.5 shall be installed on thc building watcr xupply system.
2006 INTERNATIONAL PLUMBING CODE@
WATER SUPPLY AND DISTRIBUTION
TABLE 604.5 MINIMUM SIZES OF FIXTURE WATER SUPPLY PIPES -
I
-
-'-
>lilMUM FIXTURE
-
I
-
i~alhluhs" (60" x 32" and smaller) L -~ -
-
- -
-
-
- -
/
-
- -
.~+. .
-
~
. -
-
~
I Hose . hibbs .. ' I
,
!Kitchen sink" .. . . .
..
-
..
i
--
-
1
single head". ('Showcr, . ._ -
-
(~Inks. flushing rim -
-
I
!sinks, I . service
-
.
. . .-
)
,
.-A
-
ii
I I?
+I
~
water hammer. A water-hammer arrestor shall be inslalletl where quick-closing valves are utilized. Water-hani~mcr arrestors shall be installed in accordance with the manufacturer's specifications. Water-hammer arrestors shall conform to ASSE 1010.
604.10 Gridded and parallel water distribution system I manifolds. Hot water and cold watcr mnnifoltis installed with gridded or parallel connccted individual distribution lines to I each fixture or fixture fitting shall be designetl in accordancc with Sections 604.10.1 through 604.10.3. 604.10.1 Manifold sizing. Hot water and colt1 water manifold!, ,\hall be sized in accordancc w ~ t hTable 604.10. I . The total gallons per 111inuteis the demand of all outlets supplied.
1
I
!Laundry 1 . . ? 1. 2 or 3 compartments"
jI
~-i/" i iI
. .
-
I
~--]
~=
4
~-
'
I
I .L
!+
~
4
i
-
~~
I
I1 Drink~ngfountain
-
+
~
-
.
--
.-
, !combination . sink ~ ~ and . tray
- -
-
'I2 . _ _
i
I
iBathtobs"ilargcr-than 60" x 32") /Bide( 1
PIPE SITE
~nch)
- -
-
I
z
~
.-
.
i~-
---.
TABLE 604.10.1 MANIFOLD SIZING
I
- .
-
- I2 1
-
i
-.-
{
.; I
-_..
I~rinal,flush tank
I
I
1 Watcl closcc. tlu\h tdnk 1 Wlrte~closet. tlu\h valve
,
-
-
-
I ~ a t e closet. r Ilurhomcte~~ tank . .
-
_
-
I
-_I- I
-
_
--
-
-
.
1
~. ~-i
- - Ii
'4 1-
-
- ._
3/8 ~
I
.-
!I? ~--.
,
1
:
.----.
1
For ST:
1 inch = 25.4 mm, I foot = 304.8 mm, I pound per squme inch = h.S')SliPa. a. Where rlie dc\,elopcd lcrlyth of Ihe distributiv~~ line is 60feec or less, and the available prcssurc at hi: metel is a minimum of 35 psi, the mininru~nsize of an irulividual distribution iinc supplied iron1 u ~nn~~ifold 2nd irlst3lled as pi111 of a parallel waterdislribution system shall be one nc~minaltube size smallel. than Ihr s i x e s indicated.
604.8 Water-pressure reducing valve or regulator. Where water pressure within a building exceeds 80 psi (552 kPa) static. an approved watcr-pressurc reducing valve confornling to ASSE 1003 with strainer shall be installed to reducc thc pressure in thc building water distribution piping to 80 psi (551 kPa) static or Icss. Esception: Service lines to sill cocks and o ~ ~ t s i dhydrants, e and main supply riscrs whcre prcssure fro111 the mains is reduced to 80 psi (552 kPa) or less at individual fixtures. 604.8.1 Valve design. Thc pressure-rcducing valve shall be dcsignetl to remain opcn to permit uninterrupted water flow in case of valvc ftiilure. 604.8.2 Kcpair and rcmoval. All water-prcssure reducing valvcs, regulators and strainers shall be so constructed and installcd as to pernlit repair or removal of parts without breaking a pipeline or rcmoving the valve a l ~ dstrainer from the pipeline. 604.Water harnmer. Thc flow velocity of thc water distribution system shall bc controlled to reduce the possibility of' 2006 INTERNATIONAL PLUMBING CODE@
For SI:
1 inch = 25.4 Inm, 1 g:~llnr~ per lninule = 3.785 I.hn, 1 fool per second = 0.305 n~is.
604.10.2 Valves. Individual fixture shutoff valvcs installed at tllc manifold sllall be idenrilicd as tothc fixturc bcing supplied. 604.10.3 Access. Access shall bc provided to manifolds 604.11 Individual pressure balancing in-line vdves lfur il~dividuillfixture fittings. Wherc inttividual prcssure balancing in-linc valvcs for individual fiuturc fittings arc installcd, such valves shall comply with ASSE 1066. Such valves shall be installed in an accessible location aud shall not bc utilizcd alonc as a substitute for the balanccd pressure, thcr~nostaticor combination shower valvcs required in Section 424.3.
SECTION 605 MATERIALS, JOINTS AND CONNECTIONS
605.1 Soil and grountP water. The installation o r a water scrvice or water distribution pipc shall bc prohibited in soil and ground water contaminated with solvents. filels, organic compounds or other detrimental materials causing pcrmcation, corrosion, degradation or structural Failure of thc piping ~na~crial. Whcre detrimental conditions are suspected, a chemical analysis of the soil and ground water conditions shall bc rcquircd to ascertain thc acceptability of the wakr scrvice or watcr clistribution piping material for the specific installation. Whci-ecletrimental conditions cxist. approved alternative materials or routing shall bc required. 605.2 Lead content of water s ~ ~ p ppipe l y and fittings. Pipe and pipe fittings. including valves and fauccth, utili~cdin thc
WATER SUPPLY
AND
DISTRIBUTION
water supply system shall have a 11iaximumof 8-percent l a d content.
605.3 Cl'atcr service pipe. Water servicc pipe shall corlform to NSF 61 and shall conform to one of tlie standards listed in Table 605.3. All watcr service pipe or tubing. installed underground and outside of the structure, shall have a m i ~ ~ i m u m working pressure rating of 160 psi (I 100 kPa) at 73.4"F (23°C). Whcre the water pressure exceeds 160 psi (1 100 Wa), piping material shall haven minimum rated working prcssure equal to the highcst available pressure. Water service piping materials IIOLthird-party certified for water distribution shall terminate at or before the full open valve located at the entrance to the structure. All ductile iron water service piping shall be cement l o r tar li~lcclin accordance with AWWA C 104.
respective pipe standards or one of the standards listed in Table 605.5. All pipe fittings utilized in water supply systems shall also co~iformto NSF 61. The fittings shall not have ledges. shoulders or reductions capahlc of retarding or obstructing flow in the piping. D ~ c t i l cand gray iron pipe fittings shall bc cement mortar lined in accordance with AWWA C 104. 605.5.1 Mechanically formed tee fittings. Mcchanically extracted ontlcts shall have a height not less than threc tirr~es the thickness of the branch tube wall. 605.5.1.1 Full flow assurance. Branch tubcs shall not restrict the flow in the run tube. Adimpleldepth stop shall be Cormed in the branch tube to ensure that penetration ct For inspection purinto the collar is of the c o ~ ~ edepth. poses, a second dimple shall be placed 0.25 inch (6.4 mm) above rhe first dimple. Di~nplcsshall bc aligned with the tube run.
605.3.1 Dual check-valve-type backflow prcventer. Whcre a dual check-valve backflow prcvcntcris installedon tlie water supply system. it shall cornply with ASSE 1024 or CSA B64.G.
I -
605.5.1.2 Brazed joints. Mechanically formcd tee tittings shall be brazed in accol.dance with Section 605.14.1.
605.4 Mratcrdish-ihutian pipe. Water distribution pipe shall conform to h'SF 6 1 and sliall conform to one of the standards listed in Table 605.4. .411 hot water distribution pipe and tubing shall havc a minimum prcssure I-ating of 100 psi (690 M a ) at 180°F (82°C).
605.6 Flexible water canncctors. Flexible water connectors exposed to continuous pressure shall conforni to ASME A1 12.18.6. Access shall be provided to all flexiblc watcr connectors.
605.5 Fittings. Pipc fittings shall be approvcd For installation with the piping material installed and shall conform to the
.
~~
~-
~
~
I
i
-
-~~
-~
~~
.~
---
~~
~.
TABLE 605.3 WATER SERVICE PIPE~-..
~-
-~
~
M'CERIAL-~... _
.~
-
l ~ ~ r ~ l o n ~but;@ienc t r i l c styrene (ABS) plastic pip^ -
- ~ -
ji\sbcs(os-celnenl l ~ i ~ t l ~
~~
-
-
~
-
~~
--
~
--
--
-- -
-
L
-
iIASTM
.
~-~~
~
~
D 1527:ASTM
~~
I
I
--
1
-
BI"~pipc
~- - -
~
.~-
-
- - ~
-
~
~
;ASTM B 43
~
-
-
~
-
-
-
~
-
DucliJe;roil ~~Q!:LP~I'~.
-
-
-
-
~
~
~-~
---. ---
~~~~
--
W A. C IS IX ; ,' A. W --
~ -~ 4-(. : 1--1 5
53 -J 'ASTM-A .~~
-.
IASTM -?GTM
~
.
-
~
~
-
-
~~-
~-~ ~~~~-
-
---
40
~
~~
- -
I
~~
.
.--
-
~
-
~
.
.
.
. ~-~
~~
~
~~~
~
~-
~
- -
--
~
-
-
.
~l
-
~
-~
~
~~
~
~.
.--
-
.
.
~
..
i j
~
~~
--
I
.
I
I
~
'ii~ir*;3 I 2 ASrM A 778 _
1
.~. .
-
~
1I
.
-
~
~
--
- - - -
~
~
,
I
,
~
~
'ASTM D 1755. 1XSTM D '241. -. -2ASTM.D 2672 2.CSA _ . B137.3 i ASTM A 312; ASTM A 778 .-
-~
~-
.
~
D 2662; ASTM D 2666; ASTM D 3.709; CSA B 137.YM D 2239: CSA R 137.1 - - ~ ~
~
.
-
S t ~ j n l c s ~ s tpill? e ~ l (Typc~3i6/31kL)
~--
~
Polj,vinyl chloride . . (PVCj plastic . pipc.-Sb~inlchsstecl pips (Typc 3041104L) -
~
~~-..
~~
~
~
~-
Pol~~!!!~lcne ( ! ? E i _ y l + ~ ~ i ~ n ~ .~ ~ n.e ._ . - . - - - .!AX:!02737: C_SA8EL! . Poly~thyl~~l~alyminunlip~le!I~y1~n~~~P~-AL-PE~pILp~ _ IASTM F 1282; CSA B 137.9 ~ - . Polypropylene (PI-').plaslic pipe o r-tubing . -- L I ASTM . F2 "489. :1 CSA B137.1 I -
i
~~ ~
~
ASTM F 1281. CSA B137.10h4
- ~ - -~
Polycthyleile . -~. . -~ (PE) . -plastic ~ pipe ..
~ .
-
.- .
.
sipc . . Polyhutylctic iP6) plastic pip?-and L~~binf _ ~- ~ - . ~ ~
-
!
~~~~
~
~~-.-
-
- .
.
--
IAS'I'M F 876; ASTM F 877; CSA B--. 137.5
.-
-
-
~~-~
/ASTM B 75; ASTM B 88: ASTM B 251; ASTM B 447
~
ICro\\-l~nksdp o l y c t h y l r n c / n l i ~ ~ n ~ n ~ ~ d c r o ~polycthllc~ie \-11nM ; (PEX-AL-PEX)plpe - -- -
- -
~-
~
i
/ --! B 42. ASTM 'ASTM L.-. -.B 302 . -
~
iCro~>~-li!lkcd polycthylcne ~. ~. -. (PEX) ~.~ plastic tubilrg
~-
~~
~~-
tubing (Type K, WK, L, WL. M or WM) or copper-alloy . . I (Copper
~
~
~ASTMD 2846; ASTM F 441 : ASTM F 412; CSA £3-137.6 ~ ~.
-
~
~-
~~~
I.
polyvinvl chloride (CPVC) plastic pipe I C:hlorinatcd ~- !Copper , .or copper-alloy _ _pipe .-. _ . -_ ~.
I
~-
.
. ..
-
.
~
~
-
~~
4,
i
2006 INTERNATIONAL PLUMBING CODE@
. ~
~
WATER SUPPLY AND DlSTRlBUTlON
-
. . .
................
TABLE 605.4 WATER - - DISTRIBUTION PIPE
.
..
. .
.
,
!Br.CISS . . pipe. .
.
_~
.
. -_
. . . . . . .
.
.
pol)rinyl . . chloride (CPVC) plastic pipe and tubing Chloiinried . . ~ - ~. . . . . . --.. !Copper or coppel--alloy pipe ............... ...
,
~
-
~
~
-
.
.
i
.
.
. . .
I ICross-linkcd . polyethylene . (PEX) plastic. tubing -
..
~-
~
-.
IASTM ! ASTM ~
F 877; CSA B 137.5 ~
,.
~
.
-
.
.
.
.
.
.
-
-
Stilinlcss stcel pipe -(Type 3(14/304L)- . ............. ........
-
~-
-
i .!
.
-~
. . . . . .
--
--
-~ -
i
.....
-
.
F 1287
..
...
.---
I
. -I
. . . . . . .
-
Stainless - .......... s~cel-pipe. (Typc .. - 3 161316L)
I
.
.
~-~~--1-/ASTMF~~~~;CSABI~~.II
-~
.
---
I
i
1 1ASTM D 7309. CSA B137.SM
-
Polypropylene (PP) plastic pipe . or tubing .
~~-
.-..-~..~
...........
, i ASTM A 53
.. .
Polyctl1ylencIAluminu1nIPc~1yethylcne (PE-AL-PE) composite pipe-- i~~~~ - .---. .
~-
~
Galvanired steel pipe . . . . . . . . . . . _ . _ - . - .... -~ Polyhutylene (PB) plastic pipe and tubing ..
-~
~~
1IASTM F 1986
/cross-linked polyellrylene/alu~ni~~~~m/l~igl~-density polyethylene (PCX-AL-HDPE) . -
-~
~
~ASTMF 1281; CSA B137.10M ....
-
~~
-~ - -
B 75; ASTM B 88; ASTM B 251; .......
+
-
/Cross-linked polyetIryle11e/alu1ninu1~1/cross-linkcd polyethylene 1I-. (PEX-AL-PEX) pipe ............. ...... ...... ..
I
-.
..
42: ASTM --i ASTM .- - - --
-
.
...-- .
.
lCopper or copper-alloy .. tubing (Type K, WK, L, WL, M or WM) .
j
......................
D 2846; ASTM F 441: ASTM F442; CSA B 137.0.......... --
-
-
.........................
--
STANDARD
....
-.
I
! ASTM- B 43--
--
.........
-
........
-
.
-1
MATERIAL
-
.....
.-
~~. - --
.~
~
- -
~
~
IN
ASTM A 31 2 LASTM.A 778 - --
ASTM A 312: ASTM A 778 L
.
TABLE 605.5 PIPE FITTINGS
butadi~nc . . . . .styrene . (ABS) plastic -. 11 Acrylonitrile .- . .- -. -
/ ASTM D 2468
--
.
-~~
C h l o ~ ~ n a ~polyvinyl etl chlorldc ICPVC) p l a s h ~
-
-
-
F
1ASTM - 437, -- ASTM -- -
-
--
. .
F 438, - ASTM F 439, CSA B 137.6
I
C o p p c ~or coppcr alloy I
'~ASTMF 1986
(Cross-linked polyethylenc/al~~mi~~~~nlhigl~-density polycthylene ! (PEX-AL-HDPE)
I
iASTR/I F 877; ASTM F 1807: ASTM F 1960; ASTM F 2080: j ASTM F 2159: cs.4 B 137.5 -......................
Fittings Sor cross-linlcrd polyethylene (PEX) plastic tubing I
.............................
GI-nyiron and ductilc iron .......... .~
. . . . . . .
~
h4allenblc il-on
. . . . . . . . .
...
-
-
-
..
4'ASME B16.3
. . . .
. .
!AWWA C J10: AWWA ~153 . - ... .- ... ....................
..-$
. .. .........
..
,
-
.- .
--
~
1 Metal (brass) insert fiuings for Polycthylcnc/AIurninu~i~/Polyctlrylcne (PE-AL-PE) and C~.oss-linked ASTM F 1971 I Polyethylcnc/Alun~i~~u~~i/Polyethylenc (PEX-AL-PEX) ............... - . ................... . . . . . L. --
7 I 1
....................
I
.
~
~~
1
~
I 1 :
I
..
. . . .
Pol~~lltylcnc(PB2 plastic +~- ~ o l y c t l i y l (PE) ~ ~ n c plas~ic ....................... I! ~ o l y ~ r o p ~ l(PP) e n cplastic .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.-
.
-
.
-
.
-
~
__
1
-
~-
-
....................
- . .-
I
. ~.-.-
pipe ortubing
.
.
.
CSA R 137.1~1 +[ASTM- F 2389; -
. .
-
...
steel (Type 3 1613 16L) 11 Stninlcss . . . . . . . . . . . . . . . . . . . . . . . . . . .
2006 INTERNATIONAL PLUMBING CODE'
-
- ~-
--
...
.
.
- -
I
; ASTM B 137.1 .. -D 2600; CSA ..........
-~
..........
I steel (Type 3041304L) r F~ainless . ..............
-
........
I
IPolyvinyl chloridc (PVC) plas~ic ......................... -
.
CSA B137.8 .
.....
'ASTM .. D 2464. . ASTM D 2366: ASTM ............. D2
..-l~ .
. . . . . . . . . . . . .
-. . . . . .
I
....
.
.
.- .
-
~1
--
. .
-
-
ASTM A 3 1 1.ASTM A 778 .
:
~
L
I
........................
-
.
---
.
-
.
-~
-~
.~ -
~
.
~
Ii
WATER SUPPLY AND DISTRIBUTION
605.7 \7aTalvt.s. All valves shall be of an approvcd type and co111patihle with the typc of piping material installed in the systcm. Ball v a l ~ ~ cgate s , valves, globe valvcs and plug valves intended to supply drinking water shall meet the requirements of NSF 61. 605.8 Manufactured pipe nipples. Manufactured pipe nipples shall conform to one of the standards listed in Table 605.8.
-
I
--
TABLE 605.8 MANUFACTURED PIPE NIPPLES -. -- --
--
-
MATERL*L
--- -
-
I
605.12.3 Threaded joints. Thrcads shall confolm to ASME B1.20.1. Pipe-joint compound or tape \hall bc applied on the male threads only. 605.12.4 Welded joints. All joint surfaces shall bc clcancd. The joint shall be welclcd with an approved filler mctal. 605.13 Gray iron and ductile iro~~,joints. Joints for gray and ductile iron pipe and fittings shall comply with AWWA C1 1 1 and shall be installed in accorclancc with the manufacturer's installation instructions.
I
605.14 Copper pipe. Joints between copper or copper-alloy pipe or fittings shall comply wit11 Sections 605.14.1 through 605.14.5.
605.9 Prohibited joints and connections. The following types of joints and con~lcctionsshall be prohibited:
605.14.1 Brazed joints. All joint surfaces shall be clcancd. An approved flux shall be applied where recluirccl. Thejoint shall be brazed with a filler metal conforming to AW S A5.K.
-
-
Bras,
I
-
-
-
.coppel-, chromrum-plated - - -
-
(Stcrl
-
-
_
--
STANDARD_---
-
ASTM B 687-
---1LGICIA?3i -L-_-
-j -
-_-_I
1. Cemenr or concrete joints 2. Joints ~ n a d cwith fittings not approvcd For the specific installation. 3. Solvent-ccnicnt joints bctwcen differcnl types of plastic pipc. 4. Saddle-type fittings.
605.10 ABS plastic. Joints bctween ABS plastic pipe or fittings shall comply with Scctions 605.10.1 through 605.10.3. 605.10.1 Mechanical joints. Mechanical joints on water pipes shall bc madc with all elastomeric seal conforming to ASTM D 7 139. Mechanical joints shall only be installetl in underground systems, unless otherwise approvcd. Joinls shall hc installed only in accordance with the manufacturer's instructions. 605.10.2 Solvent cementing. Joint surfaccs shall be clean and frce from ~noisturc.Solvent cement that c,onfornls to ASTXj D 2125 shall be applicd to all joint surfaces. The joint shall he made whilc the cement is wet. Joints shall be made in accordance with ASTM D 2235. Solvent-cement joints shall be pcrniittcd above or below ground. 605.10.3 'Threaded joints. Threads shall conform to ASME R 1.20.1. Schedule 80 or heavier pipe shall bc permitted to be threaded with dies specifically designed for plastic pipe. Approved thread lubricant or tapc shall be applied on the male threads only. 605.11 Aslaestos-cement. Joints bctween asbestos-cement c a slcevc coupling of the same pipc or fittings shall be ~ n a d with composition 3s the pipe, scaled with an elasto11ie1-icring confon~iinpto ASTM D 1869. 605.12 Brass. Joints bctwcen brass pipe or fittings shall comply with Scctions 605.12.1 through 605.12.4. 605.12.1 Brazed.joints.All joint surfaces shall be cleaned. An approved flux shall he applied where required. The joint shall be brazed with afillermctal conforming to AWS A5.S. 605.12.2 Mechanical joints. Mechanical joints shall be installcd in accordance wit11 Lhc manufacturer's inst~uctions.
605.14.2 Mechanical joints. Mechanical joints shall he installed in accordance with thc manufacturer's instructions. 605.14.3 Soldered joints. Solder joints shall be made in accordance with the methods of ASTM B 828. All cut tubc ends shall be reamed to the full inside diilmcter of thc tubc end. All joint surfaces shall be clcancd. A flux col~forrriing to ASTMB 813 shall be applicd. The joint shall be soldcrcd with a solder conforming to ASTM B 32. The joining of watcr supply piping shall be made with lend-free solder and fluxcs. "Lead free" shall mean a chcmical colnposition cclua1 to or lcss than 0.2-perccnt Icacl. 605.14.4 Threaded joints. Thrcads shall confo~-mto ASME B1.20.1. Pipe-joint compound or tape shall be appliecl on the male threads only. 605.14.5 Welded joints. All joint surfaccs shall be cleancd. The joint shall be weldcd with an approvcd filler mctal. 605.15 Copper tubing. Joints betwecn copper or copper-alloy tubing or fittings shall comply with Sections 605.1 5.1 through 605.15.4. 605.15.1 Brazed joi~lls.All joint surfaces shall he clcaned. An approved flux shall be applied where required. 'The joint shall bc brazed with a fillcrn~ctalconfonnir~gto AWS A5.X. 605.15.2 Flaredjoints. Flared joints for watcr pipc shall bc made by a tool designed for that operation. 605.15.3 Mechanical joints. Mechanical joints shall be installed in accordance with the nlan~rfacturcr's instructions. 605.15.4 Soldered joints. Solder joints shall be mndc in accorclancc with the methods of AS'I'M B 828. All cut tube cnds shall be rearncd to the full inside tli:~mcterof the tubc end. All joint surfaces shall bs cleancd. A flux conforming to ASTM B 81 3 shall bc applied. The juirit shall be soldered with a solder conforming to ASTM B 32. The joining of water supply piping shall be made with Izad-free soldcrs and fluxcs. "Lcad free" shall rncan a chemical composition equal to or lcss than 0.2-percent lead. 605,16 CPVCplastic. Joints between CPVC plastic pipc or fittings shall comply with Sections 605.10.1 through 605.16.3. 2006 lNTERNATlONAL PLUMBING CODE@
WATER SUPPLY AND DISTRIBUTION
605.16.1 Mechanical joints. Mechanical joints shall bc installed in accordancc with the manufacturer's instructions. 605.16.2 Solvent cementing. Joint surfaces shall be clean and frcc from moisture, and an approvcd primer shall be applicd. Solvent ccrnent, orange in color and conforming to ASTM F493, shall be applied to all joint surfaces. The joint shall be made while the cement is wet, and in accordance with ASTM D 2836 or ASTM F 493. Solvent-cement ioints shall bc pcrnmittcd above or below ground. Exception: A primer is not requircd where all of the following conditions apply: I. The solvent cemcnt uscd is third-party certified as conforming to ASTM F 493. 3. l'he solvent cement used is yellow in color. 3. Thc solvent cemcnt is used only for joining inch (12.7 mni) through 2 inch (51 mni) diameter CPVC pipe and fittings.
4. The CPVC pipe and fittings arc manufacturcd in accorda~icewith ASTM D 2846.
605.16.3 Threaded joints. Threads shall conform to ASME B 1.20. I. Schcdulc 80 or heavicr pipc shall be permittcd to bc threaded with dies specifically dcrigned tor pla\tic pipe. but the pressure ~ a t ~ nofg the plpe shall be retlucecl by 50 percent Thread by socket ~ilolcledfittingb shall bc permitted. Approved thrcad lubricant or tape shall be applied on the malc threads only. 605.17 Cross-linked polyethylene plastic. Joints betwecn cross-linkcd polyethylene plastic tubing or fittings shall comply with Sections 605.17.1 and 605.17.2. 605.17.1 Flared joints. Flared pipe ends shall be made by a tool dcsipncd for that operation.
I
605.17.2 Mechanical joints. Mechanical joints shall bc installed in accordance with the manufacturer's instructions. Fittings Sor cross-linked polyethylene (PEX) plastic tubing as described in ASTM I:877, ASTM F 1807, ASTM F 1960, and ASTIvI F 2080 shall be installed in accordance with thc manufacturcr's instructions. 605.18 Steel. Joints between galvanized stccl pipc or fittings shall con~plywith Sections 605.18.1 and 605.18.2. 605.18.1 Threaded joints. Threads shall conform to ASME R1.1-0.1.Pipe-joint co~npoundor tapc shall be appliecl o11 thc rnalc threads only. 605.18.2 Mechanical joints. Joints shall bc made with an approved clastomct.ic scal. Mechanical joints shall be installcd in accordance with thc manufacturcr's instructions. 605.19 Polybutylene plastic. Joints between polybutylene plastic pipe and tubing or fittings shall comply with Sections 605.19.1 through 605.19.3. 605.19.1 FLared joints. Flarcd pipe cncls shall bc made by a tool designed for that operation. 605.19.2 Heat-ft~sion joints. Joints shall he of the sockct-fusion or butt-f~~sion type. Joint surfaces shall be 2006 INTERNATIONAL PLUMBING CODE@
clean and free from moisture. All joint surfaces shall bc heated to melt temperature and joinccl. The joint shall be undisturbed until cool. Joints shall bc niacle in accordance with ASTM D 2657. ASTM D 3309 or CAN3-B 137.XM.
605.19.3 Mechanical joints. Mcchanical joints shall be installed in accordance with the niunufacturcr's instructions. Mctallic lock rings employcd with insert fittings as described in ASTM D 3309 or CAN3-B 137.8M sh:rll bc installcd in accordance with the manufacturcr's instructions. 605.20 Polyethylene plastic. Joints bctwccn polyctliylenc plastic pipe and tubing or fittings shall comply w ~ t hScctions 605.20.1 through 605.20.4. 605.20.1 Flared joints. Flared jonits shall hc pcrm~ttcd where so indicated by the pipe rnanufacrurer. Flared joints shall be made by a tool tlcsigned for that operation. 605.20.2 Heat-fusion joints. Joint surfaces shall bc clean and free from nloisture. All joint surfaces sllall be heatcd to melt temperature and joined. The joint shall bc undisturbed until cool. Joints shall he made in accordance with ASTM D 2657. 605.20.3 Mechanical joints. Mechnnlcal joints shall bc installed in accordance with the manufacturcr's instructions. 405.20.4 Installation. I'olyethylene pipe shall bc cut square, with acutter designed for plastic pipc. Except where joined by heat fusion, pipe ends shall bc charnfcred to remove sharp edges. Kinked pipe shall not he inslallcd. The minimurn pipe bending radius shall not bc ICSS than 30 pipe diameters, or the minimum coil radius. whiclievcr is greater. Piping shall not be bent beyond straightening of the curvature of thc coil. Bends shall not be permitted within 10 pipc diamcters of any fitting or valve. Stiffener inscrts installed with compression-type couplings and fittings shall not extend beyond the clamp or nut of the coupling or fitting. 605.21 Polypropylene (PP) plastic. Jo~ntsbetwecn PP plastic pipe and fittings shall coniply with Scction 605.21.1 or 605.21.2. 605.21.1 I-Ieat-fusion joints. Heat-fusion joints for polypropylene pipe and tubing joints shall be installcd with socket-type heat-fused polypropylene filtings, butt-fusion polypropylene fittings or electrofusion polypropylenc fittings. Joint surf'~ccsshall be clean and free Tram nioisturc. Thc joint shall be undisturbed until cool. Joi~ltsshall be made in accordance with ASTM F 2389. 605.21.2 Mechanical and compression sleeve joints. Mechanical and compression sleeve joints shall bc installed in accordance with the manufacturer's instructions. 605.22 PVC plastic. Joints between PVC plastic pipe or fittings shall comply with Sections 605.22.1 through 605.22.3. 605.22.1 Mechanical joints. Mechanical joints on water pipc shall be made with an clastomeric scal conforming to ASTM D 3 139. Mechanical joints shall not bc installed in above-ground systems unless othcralisc approved. Joi~lts shall bc installcd in accordance with the rn:~nt~fxturer's instructions.
WATER SUPPLY AND BlSTRlBUTlON
605.22.2 Solvent cementing. Joint surfaces shall be clcan and free from moisture. A purple primer that conforms t o ASTM F 656 shall be applied. Solvent cement not purple in colcrr and confomming to AS'l'lVl D 2564 or CSA-B 137.3 shall bc applied to all joint surfaces. The joint shall be madc while the cemcnt is wet and shall be in accordance with ASTM D 2855. Solvent-cement joints shall he permitted above or below ground. 605.22.3 Threaded joints. Threads shall confonn to ASME B 1.20.1. Schedule 80 or heavier pipc shall be perlnitted to bc threaded with dies specifically designed for plastic pipe, but the pressure rating of thc pipe shall be reduced by 50 percent. Thread by socket molded fittings shall be pemmittcd. Approvcd thrcad lubricant or tape shall be applied on the malc threads only. 605.23 Stainless steel. Joints between stainless steel pipe and fittings shall con~plywith Sections 605.23.1 and 605.23.2. 605.23.1 Mechanical joints. Mechanical joints shall be installed in accordance with the manufacturer's instructions. 605.23.2 Welded joints. All joint surfaces shall be cleaned. The joint shall be welded ;~utogenouslyor with an approvcd filler metal as referenced in ASTM A 312. 605.24 Joints between different materials. Joints between different piping materials shall be made with a mechanical joint of the con~pressionor 11iechanical-sealing type, or as permitted ill Scctions 605.24.1. 605.24.2 and 605.24.3. Connectors or adapters shall have an clastoincric seal conforming lo ASTiVl D 1869 or ASTR4 F 477. Joints shall be installed in accordance with the manufacturer's instructions. 605.24.1 Copper or copper-alloy tubing to galvanized steel pipe. Joints between copper or copper-alloy tubing and galvanized steel pipe shall be ~ n a d ewith a brass fitting or dielectric fitting. Thc coppcr tubing shall be soldered to the fitting in a11 approved manner. and the fitting shall be screwed to thc threaded pipe. 605.24.2 Plastic pipe or tubing to other piping material. Joints betwcen different gracics of plastic pipe or between plastic pipc and othcr piping malerial shall be made with an approved adapter litting. 605.24.3 Stainless steel. Joints between stainless steel and different piping materials shall be rllacte with a mechanical joint of the comp~.cssionor mechanical scaling type or a dielcctric fitling. SECTION 606 INSTALLATION OF THE BUILDING WATER DlSTRlBUTlON SYSTEM 606.1 Location of full-open valves. Full-open valves shall be installed in the following locations:
I. On the building water service pipe from the public water supply near the curb.
2.
011 the watcr distribution supply pipc at the entrance into thc structul-c.
3. On thc discharge side of cvcry watcr meter.
4. On the base of every watcr riser pipe in occupancics other than multiple-family rcsitlentinl occupancics that are two stories or lcss in height and in one- and two-family residential occupancies. 5. On the top of every watcr down-fccd pipc in occupancics othcrthan one- and two-family residential occupnncics. 6. On the entrance to cvery watcr supply pipc to a dwelling unit, except wherc supplying a single fixture equipped with individual stops. 7. On the water supply pipe to a gravity or pressurized water tank
8. On the water supply pipe to every watcr hcater. 606.2 Location of shutoff' valves. Shutoff valves shall bc installed in the following locations: 1. On the fixture supply to each plumbing fixture othcr than bathtubs and showers in one- and two-family rcsidential occupancies, and other than in individual sleeping units I that are provided with unit shutoff valves in hotels, n~otels,boarding houses and sirnilar occupancics. 2. On the water supply pipe to each sillcock 3. On the waler supply pipe to each appliancc or mcchanical equipmcnt.
606.3 Access to valves. Access shall bc provided to a11 I full-open valves and shutoff talvcs. 606.4 Valve identificatior~.Service and hose bibb valvcs shall bc identified. All other valves installed in locations that arc not adjacent to the tixture or appliance shall be identified. indicating the fixturc or appliance served. 606.5 Water pressure booster systems. Water prcssure booster systems shall be provided as required by Scctions tj06.5.1 through 606.5.10. 606.5.1 Water pressure booster systems required. Where thc water pressure in the public watcr main or it~dividual water supply system is insufficient to supply the minimum pressures and quantities specified in this code, the supply shall be supplemented by an clcvatcd watcr- tank, a hydropneurnatic pressure booster system or a watcr pressure booster pump installed in accordance with Section 606.5.5. 606.5.2 Support. A11 water supply tanks shall be suppol tcd Code. in accordance ~viththe Itzret-r7ntroniJ R~liltlir~,i. 606.5.3 Covers. All water supply tanks shall be cove~.cdlo keep out unauthorized persons, dirt and vermin. The covcrs of gravity tanks shall be vented with a return bend vent pipc with an arca not lcss than the arca of the down-fccd riscr pipe, and the vent shall be screencd with a corrosion-resistant screen of not lcss than 16 by 20 nlcsh per inch (630 by 787 rnesh per In). 606.5.4 Overflows for water supply tanks. Each gravity or suction water supply tank shall be provided with an ovcrflow with a diameter not less than that shown in T a l h 606.5.4. The overflow outlet shall discharge at a point not I less than 6 inches (152 mm) above the roof or roof drain: floor or floor drain: or ovcr an opcn water-supplied fixturc. 2006 INTERNATIONAL PLUMBING CODE@
WATER SUPPLY AND DISTRIBUTION
The ovcrilow outlet shall bc covered with a corrosion-resistant scrccn of not lcss than 16 by 20 mesh per inch (630 by ) by 0.7-5-inch (6.4 mln) hardware cloth 787 mcsh per n ~and or shall terminate in a horizontal angle scat chcck valvc. Drainagc from overflow pipes shall be dirccted s o as not to trceze on roof walks. TABLE 606.5.4 SIZES FOR OVERFLOW PIPES FOR .WATER SUPPLY TANKS . .. . . .. . -- .- . . -
-
-
MAXIMUM CAPACITY OF WATER SUPPLY LINE TO TANK (gpm)
I,
.
.
-
o rI :
Over 1,000 . .
-
(
DIAMETER OF OVERFLOW PlPE
..
1
:
i
8
.
606.5.5 Low-pressurccutoff required on booster pumps. A low-pressurc cutoff shall be installed on :ill booster p ~ ~ n in ~ pa swatcr pressure booster system to prevent crcation of a vacuum or ncgativc prcssure on the suction sidc of the pump whcn a positive pressure of I 0 psi (68.94 kPa) or ICSS O C C L I ~ Son thc suction sidc of the pump. 606.5.6 Potable water inlet control and location. Potablc watel inlets lo gravity tanks shall be controlled by a fill valve or other automalic bupply valve ~nstalledsoas to prcvent the tank from ovcrtlowing. The inlet shall be terminatcdso as to provide an alr gap not lcss than 4 inchcs (102 mm) above the O ~ ~ m ~ ~ . 606.5.7 'rank drain pipes. A valvcd pipe shall be provided at the lowest point of each tank to permit emptying of the tank. Thc tank drain pipe h a l l discharge as required for overflow pipes and shall not be smaller in size than ipecified in Tablc 606.5.7.
/(
...
-
TABLE 606.5.7 SIZE OF DRAIN PIPES FOR WATER TANKS . . --. .~~ ~
-
-TANK CAPACITY (gallons) . . -
~-
.
/' .
606.5.10 Pressure relief for tanks. Every pressure tank in a hydropneumatic prcssurc booster syste~nshall be prorcctcd with a pressure rclief valve. Thc prcssure rclicf valvc shall be set at a ~naximumpressurc equal to the rating of thc tank. The relief valve shall be installed on the supply pipe to thc tank or on the talk. The relicf valve shall discharge by gravity to a safe place of disposal.
-:!
I ~nilh= 25.4 mm, I gallon per nlinutc = 3.?85 I,/ni.
-~
Exception: This section shall not apply to pressurized captive air diaphragnv'bladdcr tanks.
606.6 Water supply sgsten~test. Upon completion of a rcction of or the entire water supply system, thc system, or portion completed, shall be tcsted in accordance with Scction 317.
I
~..
-
606.5.9 Pressure tanks, vacuum rclicf. All water pressurc tanks shall be providcd with a vacuum rclicf valvc at the top n prcssure of the tank that will operate up to a i n a x ~ ~ n un ~atcr ~i~ of of 200 psi (1380 kPn) and up to a n ~ a x i t n utcmpcraturc 200°F (93°C). The minimum sizc of such vacuum lclief valve shall bc 0.50 inch (12.7 mm).
. .
DRAIN PIPE (inches) ~
-1
7
SECTION 607 HOT WATER SUPPLY SYSTEM
607.1 Where requii-ed.In residential occupancics. hot watcr shall bc supplied to all plumbing fixtures and cquipn~entutilized for bathing, washing, culinary purposcs, clcansing, laundry or building maintcnancc. In nonresidential occupancics, hot water shall be supplicd for culinary purposcs. clcansing. laundry or building ~naintcnancepurposes. In nonrcsidcntial occupancies, hot water or tc~npcredwater shall be supplied for bathing and washing pulposes. Tempcred watcr shall bc supplied through a water temperature limiting device that conforins to ASSE 1070 and shall limit (he tcmpcrcd watcr to a lnaxirnum of 110°F (43°C). 'This provision shall not supersede thc rccluircmcnt for protective shower valves in accordancc with Section 423.3. 607.2 Hot water supply temperature maintenance. Wl~erc the developed length of hot watcr pip~ngt r o ~ nthc source of hot water supply to thc fartheat fixturc excceds 100 fect (30 480 mm), the hot water supply sy\tem shall I,e providcd with a method of maintaining the temperature in accordancc with thc Ivztertzatioi~alEizergy Coiz~rn~utioil Code. 607.2.1 Piping insulation. Circulating hot watcr system p~pingshall be insulated in accordancc with the I~tei-~rcltinr?nl Et~ergyC n i ~ s e n a t i nCode. i~
[El 607.2.2 Hot nater systeli~controls. Automatic clrculating hot watc~ 5ystcm pumps or hcat tlace sliall he arranged to be conveniently turncd off automat~cnllyor manually. when the hot water system IS not in open~tion.
For SI:
I ~ n c h= 1-5.4 mtn, 1 gallon = j.785 I,
606.5.8 Prohibited location of potable supply tanks. Potablc watcr gravity tanks or manholes of potablc water e\aure tanhs sllall not be located ducctly under any soil or wastc piping or any source of contamination. 2006 INTERNATIONAL PLUMBING CODE'
607.2.3 Recirc~~latingpump. Whcre a thermostatic niixing valve is used in a system with a hot water recirculating pump. the hot w:~tcror ten~pcredwater return line shall bc and the routed to thccold watcr inlet pipe of the watcr hc,i~tcr cold water inlet pipc or the hot water- I-ctur-11 connection of the thennostatic mixing valve. 607.3 Thern~alexpansion control. A means of controlling increased pressure caused by therinal expansion shall bc pro-
WATER SUPPLY AND DISTRIBUTION
vided whcrc ~ccluiredin accordance wlth Sect~ons607.7.1 arid 007.1.2.
607.3.1 I9essure-reducing valve. For water service system sizes up to and including 2 inches (5 1 ~ n m )a, device for controlling pressure shall bc installed whcre, because of thermal expansion, the pressure on the downstream side of a prcssurc-reducing valve exceeds thc pressure-reducing v:llvc setting. 607.3.2 Bacl(flow prevention device or check valve. Wherc n hackflow prevention device, check valve or other device is installcd on a water supply system utilizing storage watcr heating equipment cuch that thermal expansion causes an 1ncrea5ein pressure, a device for controlling pressure shall be ~nbcalled. 607.4 Flow of hot water to fixtures. Fixture fittings, faucets and divertcrs shall be installcd and adjusted so that the flow of 1101 watcr from Ihc iittings corresponds to the left-hand side of the t?xtl~refitting.
I
608.5 Chemicals and other substances. Chcrt~icalsand othcs substances that producc either toxic conditions. taste: odor or discoloration in a potable water systc~ushall not he introduced into, or utilized in, such systems. 608.6 Cross-connection control. Cross conncclions shall bc prohibited, except where approved protective devtccs arc installed. 608.5.1 Private water supplies. Cross connections betv~eena private water supply and a potablc p ~ ~ b lsupply ic shall be prohibited. 608.7 Stop-and-waste valves prohibited. Combination stop-and-waste valves or cocks shall not he installcd underground. 608.8 identification of potable and nonpotable water. 111all buildings whcre two or rnorc watcr distribution systems, one potable watcr and the other nonpotablc watcr, are installed, each system shall be identified either by ctjlor marking or metal tags in accordance with Sections 608.8.1 through 608.8.1.
Exception: Showcr and tub/shower mixing valves conforming to ASSE 1016 or CSA B125, wbcre the flow of hot watcr cor~cspondsto the ~narkingson the device.
608.8.1 Information. Pipe identification shall includc the contents of the piping system a r ~ dan arrow indicat~ngthe direction of flow. Hazardous piping systems shall also contain infoimatlon addressing the nature of the hazard. Pipc identification shall be repeated at maxi~numintel-vals of 25 feet (7620 n ~ u and ) at each point where the piping passcs through a wall. floor or roof. Lettering shall be readily obsel-vablc tvithin the room or space whcrc thc piping is located.
SECTION 608 PROTECTION OF POTABLE WATER SUPPLY 608.1 General. A potable water supply system shall be designed, installed and maintained in such a manner so as to prcvent contaniination from ionp potable liquids, solids or gases being introduccd into the potable water supply through cross-conncctior~sor any other piping connections to the system. I3acktlow preventcr applications shall conform to Table 608. 1, except as specifically stated in Sections 608.2 through 608.16.10.
I
608.2 Plumbing fixtures. The ?upply lines ancl littings for cvery plumbing fixture shall bc installcd so as to prevent backflow. Plulnblng fixture fittings shall provide backflow protection in accordance with ASME A1 12.18.1. 608.3 Devices, appurtenances, appliances and apparatus. All devices. appurtenances, appliances and apparatus intended to serw some special fi~nction?such as steriliz;~tion,distillation: processing. cooling, or storage of ice or foods, and that connect to the water supply syste~n,shall be provided with protection against backflow and contaniination of the water supply system. Water pumps, filters. softeners, tanks and all other appliances and devices that handle or treat potable. water shall he protected against contamination. 608.3.1 Special equipment, water supply protection. The water supply for hospital iixtures shall be protected against backflow with a reduced pressure principle backflow prcvcliter, an at~nosphericor spill-proof vacuum breaker, or an air gap. Vacuum breakers for bedpan washer hoses shall not be locntcd Icss than 5 lee1 (1523 mm) above the floor. V~lcuumbrcalcers for hosc connections in health care or lahor:ltory areas shall not be less than 6 feet (1 829 mm') above the floor. 608.4 Water service piping. Water service piping shall bc protcctcd in accordance with Sections 003.2 and 603.2.1.
608.8.2 Color. The color of the pipe identification shall be discernablc and consistent throughout the building. 608.8.3 Size. The size of the background color field and Icttering shall comply with Table 608.8.3.
-.;,
-
~
~~
1
! 1
TABLE 608.8.3 SIZE OF PlPE IDENTIFICATION ~
PlPE DIAMETER -
-
LENGTH BACKGROUND I COLOR FIELD (inches) -. .~ --,
L
Ainc"eS!_
.
~
~
~
I
SIZE OF LETTERS (inches)
1
I
I--.~
over 10
1.-
~
-32 . .~
For SI: 1 inch = 25.4 mm.
508.9 Weutilization prohibited. Watcr util ired for the cooling of equipment or other processes shall not be rcturncd lo the potable watcr system. Such watcr shall be dlschargccl into a dlainage s)lstcm through an ulr gap or shall be utilized for ~lonpotahle purposes.
608.10 Reuse of piping. Piping that has been utilized for any purpose other than conveying potable watcr shall )lot bc utilized for conveying potablc water, 608.11 Painting of water tanks. The interior surface (>fapotablc water tank shall not be lined, painted or repaired with any material that changes the taste, odor, color or potability of the watcr supply when the tankis placed in, or returned to, scrvicc. 2006 INTERNATIONAL PLUMBING CODE'
WATER SUPPLY AND DISTRIBUTION
-
-
.
.-
TABLE 608.1 APPLICATION OF BACKFLOW - . PREVENTERS -. - ' APPLICATION^ DEGREE OF HAZARDa 1
.
- - .-
-.
-
.~
-
,
-
-
.I
i .-t~
- .-
I
.
Becltl'low preventcr with i~ltcrrnediate ntn~osphcric vents .~~~ -~ -~
~
--
~
--
~ . ~.
~
' ~ i ~orl low l hazard L
.
--
.-.
~
!
-
ASSE
~ .,
~
~
--_. ~
I
-
- -
I
. -
.
-
.
-
~
- -.
-
-
.
.~
.
Sizes 'I,,"
-
1
I"
.
1
head haclcp~.es~urc or backsiphonage sizes 'I,", 'I,", I "
.
..
1
Low head bba~kp~cssure ad backsiphonage
. .-+. ~.
.
I 1Backsiphonage only I Sizes 'I4'' - 4"
~~-~ . . -4-- .
Pressure vacuurn brcaker asscmhly
i ~ i or~ low h hazard
Reduced pressure detcc~orfire protection birckflo\v prcvc~rtionassc~nblies
,
~. .
.
i ~ i gorl low ~ hazard
~- ---.
1 I I High or low hazard
-
2006 INTERNATIONAL PLUMBING CODE@
-
~
ASSE 024. CSA 864,6
.
- ~-
-
-.
-~
-
-
~-
- -
~~
-
.
~-
~
-~
IAS E
1020, CSA B64.1.2
lASSE
1047
j-~
I -
1
-
~-
1056 --- -
1.ow head backpressure or backsiphonage i Sizcs 'I,,", I" 2
~
/ASSE 1035, CSA B64.7
l ~ a c k s i ~ h o n only a~e ~ i ~ 'I.,"-2" e s
/
I
1
~--!
. +
-
.
---- --
I
j ASSE 1052: CSA 864.2.1 .I
1
or backpressurc I, ~ a c k s i p l t o n a ~ e (Fire sprinkler svstcnis)
~ . . . ~ . .
I ~ a c u u r nhrcakcr wall Irydrnnts. frost-resistanl, aulo~naticdraining Iype : . _ . . . For ST: I inch = 75.4 ulnl. a. 1,ow h:~~ard-SeeP(1llutio1i(Section 202). Hljili Iin/a~-d--SeeCotrtalnit~ationiSectioli 202). 1). Scc Hachpl-cssurciSection 202). Scc Hackpl-chsuse. lo\\, head (Section 202). Sec Hi~cksiphonage(Section 207).
~. - .- - -
'ASSE I01 I, CSA B63.3, (CSA 864.2.1
1~acksiyhona~ only e
!Hifih or low h z a r d
Spillproof vacuum breaker
~-
1
1
-~.
-~
I
/LOW
I ~ i g hor low liazard
1
.--.::~~-
~1.~
~~
-
I
-~
-
-
!,A.SsE l 0 l 5 , AWWA C 5 10, iCSA B64 iCSA B65.5.1
/working pressur.c, backpressule or [backsiphonage Isires1b"- 1"
. .
/ ~ - a h o r ~ o rf'auccl -y backflow prcrcntcr
~-~
--
JLUM head bnckpresiure. l-ated
lHilh or low hr~nu-d
II
---
-.
A
I
- - --
--
I-
I Backpressure or baclcsiphonage
iHigh or low hazard I
--
-
I (See Sect~on608.13.4)
-
1
1 Hosc ~onnrclron\ acuum breaker
-.
--
2_ CS4 B64,3
1
1
Low h a ~ a r d
-I
- .-
-.
I
-
1st connection h ~ i c l d l o rp ~ a i e n t c r
. .
..
I (Fire sprinklcr systems) 1 Sizcs 2" - 16" .'~.~~
-
~~
-
1
-
i
Dual-chec1,->alve-type backtlow preventcr -
-
1
I~ackpressurcor baclcsiphonage Sizes 1'; - 16'
Double check detector tire protection backClow prcvcntior~assemblies -
- -
T
~
i ~ a c l a i p h o n a p only e ~.-/
1
-
_0
~
I
- -
--
'jASSE 1022, CSA B64.3.1
~ ~ a c l ~ ~ r c sors ubacksiphonage re I Sizes 1:' - "/a"
Doublc check backflow PI-evention \Low hazard assembly and double check fire ororccrion baekflow orevention asse~nhly
-~
- -
~ASSE1002, CSA B 125
~ --~ -
~-~-?
Imw hazard
B;~r.o~nctric loop
..
-
iBackpressure or backsiphonage Sizes 'I "- 'I,." !I
ILow hazard
-. - .
.
.
i ~ a c k s i p h o n a ~only c
..-
-
iBnckl'low prevencer for carbonated beverage machines .. ,
- .. - .
-
-...-
-
I APPLICABLE STANDARDS +.-
i
/ ~ n l i s i p h u n - t ySill ~ e \;al\;es for gravity 1I water closct flush tanks. .. .. . -
.{
-
-
-
-
~
DEVICE
--
-
I
-
~
-~
.
-
1 ASSE 1019, CSA B64 2.2
I ,-
-
.
~
-
-
~
WATER SUPPLY AND DISTRIBUTION
I
I
I
I
608.12 Purnps and other appliances. Watcr pumps, ljlters, soficncrs, tanks and all other devices that handlc or treat potable water shall be protected against contamination.
are dcsigned for installation under con~inuous-prcss~~re co~lditioriswhen thc c1itica.1level is installcd at thc rccluircd height.
608.13 Backflow protection. Means of protection against backflow shall be provided in accordance with Sections 608.13 1 through 608.13.0.
608.13.9 Chemical dispenser backflow devices. Backflow devices for chcmical dispensers shall comply with ASSE I055 or shall be equipped with an air gap fitting.
608.13.1 Air gap. The minimum recluircd air gap shall be mcasurcd vertically from the lowest end of a potable water outlet to [he flood levcl rim of the fixture or receptacle into which such potablc water outlet discharges. Air gaps shall con~plywith ASME A 1 12.1.2 and air gap fittings shall comply with ASME A1 12.1.3.
608.14 Localion of backflow preventers. Acccss shall be provided to backtlow preventers as specified by the inst;tllntion instnictions of the approvcd manufacturer.
608.13.2 Reduced pressure principle backflow preventers. Keduced pressure principle backflow preventers shall conform to ASSE 1013, A\V\VA C511, CSA B64.4 or CSA B64.4.1. Reduced pressure detector assembly backflow prcvcntcrs shall conform to ASSE 1047. Thcsc devices shall be perrnitted to bc installed where sub, j e c ~to continuous pressure conditions. The relief opening shall discharge by air gap and shall he prevented from being su b~nergcd. 608.13.3 Backflow preventer with intermediate atmospheric vent. Backflow prcventers with intermediate atmospheric vents shall conform to ASSE 1012 or CSA B64.3. Thcsc devices shall be pcrtnittcd to bc installed where subject to continuous pressure conditions. The relief opening shall discharge by air gap and shall be prevented tiom being submerged. 608.13.4 Barometric loop. Barornctric loops shall precede the point of conncction and shall extend vertically to a height of 35 fect ( 10 668 mm). A barometric loop shall only bc utilized as an atmospheric-type or pressure-type vacuum breaker. 608.13.5 Pressure-type vacuum hreakers. Pressure-type vacuum breakers shall conform to ASSE 1020 or CSA R64.1.2 and spillproof vacuum breiikcrs shall comply with ASSE 1056. Thcse devices are dcsigned for installation ~ ~ n dcontinuous cr Dressurc conditions when the critical levcl is installcd at thc rcquired height. Pressure-typc vacuum breakers shall not bc installed in locations where spillage could cause damage to the structure. 608.13.6 Atmospheric-typc vacuum breakers. Pipeapplicd atmospheric-type vacuum breakcrs shall conform to ASSE 100 I or CSA B64.1.1. Hose-connection vacuum brcakcrs shall confor111to ASSE 101 1, ASSE 1019, ASSE 1035> S S E ,052. CSA BM.2; CSA 864.2.1. CSA B64.2.1. I . CSA B61..2.2 or CSA B64.7. These devices shall operate under normal atmospheric pressurc when thc critical lcvel is installcd at thc required height. 608.13.7 Double check-valve assemblies. Double checkvalve assemblies shall conform to ASSE 1015, CSA B64.5, CSA BhJ.5.l or AWWA CSLO. Dod,lc-detector check-valve assemblies shall conform to ASSE 1048. These devices shall be capable of operating urlclcr continuous pressure conditions. 608.13.8 Spillproof vacuum hreakers. Spillproof vacuunl brcakcrs (SVB) shall confor~nto ASSE 1056.Thcse devices
608.14.1 Outdoor enclosures for backtlow prevention devices. Outdoor enclosures for h;rckflow prevention tievices shall comply with ASSE 1060. 608.15 l'rotection of potable water outlets. All potablc water openings and outlets shall be protected againsl backtlow In accordancc with Section 608.15.1, 608.15.2, 608.15.3, 608.15.4,608.15.4.1 or608.15.4.2. 608.15.1 Protection by air gap. Openings and outlcts shall be protected by an air gap between the openlng and the fixturc flood level I irn as specified in Table608. 15. 1. Opening$ and outlets equipped for hose connection shall he protectcd by means other than an air gap. 608.65.2 Protection by a reduced pressure principle backflow preventer. Opcnings and outlets shall he protected by a I-educed pressure principle backflow prcvcntcr. 608.15.3 Protection by a backflow preventer with intermediate atmospheric vent. Openings and outlcts shall bc protected by a backtlow prevcnter with an intermcdiatc atmospheric vcnl. 608.15.4 Protection by a vacuunl breaker. Opcnings and outlets shall be protected by atmospheric-type or prcssure-type vacuum breakers. The critical levcl of thc vacuuln brcaker shall be set a minimum of 6 inchcs ( 152 m ~ a abovc ) thc tlood level rim of the fixture or device. Fill valvcs shall be set in accordance with Section 425.3.1. Vacuum breakcrs shall not be instalIed ur~dcrexhaust hoods or similar locations that will contain toxic fumes or vapol-s. Pipc-applied vacuum breakers shall bc installed not lcss than 6 inchcs (1 52 mrn) above the flood level rim of the fixture, rcccptor or device served. 608.15.4.1 Deck-mounted and integral vacuum breakers. A p p r o v e d d e c k - m o u n t e d o r equipment-mounted vacuum breakers and faucets with intcgral atmospheric or spillproof vacuum brcakcrs shall be installcd in accordancc with the manuhcl~irer'sinstruclions and the requircmc~ltsfor labeling with thc critical level not lcss than 1 inch (25 mm) abovc the flood level rim. 608.15.4.2 Hose connections. Sillcocks, llosc hihbs. mall hydrants and other openings with a hose col~nection shall be protected by an atmospheric-typc or prcssurc-type vacuuln hrcakcr or a pcrmancntly attached hose connection vacuum brcakel-. Exceptions: 1. This scctiori shall no1 apply to water heater and boilcr drain valvcs that arc prcw~dedw ~ t hhocc 2006 INTERNATIONAL PLUMBING CODE@
WATER SUPPLY AND DISTRIBUTION
,-
.
.
.--~-~
~
TABLE 608.15.1 MINIMUM REQUIRED AIR GAPS
.
~
-~-
~
~.~ .
~
~. ~. . . ~
-
MINIMUM AIR GAP
.c.n w a v f r o m a . ~ ~ ~_/~ ._:lo?se ~ ~ ~to~a.vval!(inches) ~~
FIXTURE -~
1
~.;
.~ ~
lLavatorics and other fixtures with effective opening not greater than 'I, inch i I .in diamctcr . - .. ~. . .+---
,
~-
-
'Sink, laundry trays, gooseneck back Pducrta and other fixtures with effective
i,
openings . not gres~erih;m 3/4 inch in diamcter ~~
-
~-
-
-~ -~
~
~
~
~~
~~~
10vcr-rim bath iillcrs and other fixtures with effective openings 1101 greater I than 1 inch in di;unetcr 1 . . - . - . - - ._ - . .-
I
.i
iDrinlting water t'ountains, single orifice not grcaler than 'It6 inch i l l diamcter / 1 or multiplc oriliccs with a total area of 0.1 50 square inch (ama of circle 'I,, incll ir14i;lmeler) . . . - . 1
1
(
~
~~
1
I
~ffefect~vc openings greater than 1 ~nch I
-
-
. ..
..
_
.
^-_--...-..-.----.i-.-..__.-.-..--.
/
Two times the diameter of'the effective o~eninn i L-_--
Three limes the diameter of ..thc cfkctivc or,e~lirl!: . . .. 1
I i
i
For SI: I inch = 75.4 mm. a. A p p l i c a h l c w h ~ ~ walls ~ e I ) I . O ~ ? ~ ~ I - ~ I Carespaced ~~OIIS from thencarest inside-edge of [hespout opening adistzmcs grc:lttrthan three Lirncs llle di;iinctcr~)f~hc. ci'fc~tivc opening 111. n single wall, o r a distance greater than four tinies the diameter o f the effective opening for t\\o intersecting walls.
connection tlirc;~dsand that are intended only for tank or vcs\cl draining.
1. Where systems arc installed as a portion of thc
2. This section shall not apply to water supply valves intcndcd for connection of clothes washing machines whcrc bacliflow prevention is otherwise provided or is integral with thc n~achinc.
watcr distribution systcm in acco~.dancewith thc requirements of this code and arc not providcd with a fire dcpart~ncntconnection; isolation ol'thc water supply system shall not be requil.cd.
608.16 Conilectioi~sto the potable water system. Connections to the potablc wzltcr system shnll conform to Sections 608.16. I 1h1-ough608.16.10.
2. Isolation of the water distribution system is not
608.16.1 Beverage dispensers. The water supply conncc-
1
Exceptions:
tion to beverage dispensers shall bc protected against backflow by a backflow preventer conforming to A S S E 1022, CSA B63.3.J or by an air gap. The bacl
608.16.2 Connections to boilers. The potable supply to the boiler shall bc equipped with a backflow preventer with an intcrmcdiate ;~tmosphericvent complying with ASSE 1012 or CSA B64.3. Wherc conditioning chcmicals arc introduced into the systcm. the potable water connection shall be protected by an air gap or a reduced pressurc principle backflow preventer, complying with A S S E 1013. C S A B64.4 or AWWA C5 I I .
608.16.3 Heat exchangers. Heat exchangers utilizing an essentially toxic trimsfer fluid shall be separated from the potablc watcr by double-wall construction. An air gap open to the atrnosphcre shall be provided between the two walls. Heat cxchangcrs utilizing an essentially nontoxic transfer fluid slyall bc permitted to be of single-wall construction. 608.16.4 Connections to al~tornaticfire sprinkler systems and standpipe systems. The potable water supply to automatic fire sprinkler and standpipe systcms shall be protccted against b:~ckflowby a d o ~ ~ bcheck-valve lc asselllbly or a reduced pressure principle backflow prevcnter.
2006 INTERNATIONAL PLUMBING CODE@
required for clelugc, prcaction or dry pipc systems.
608.16.3.1 Additives or nonpotablc source. Where system5 under continuous pressurc contain chc~nical addrt~vesor antifreeze, or urhcre systcni\ arc connectctl to a nonpotahlc secondary watcr supply, the potable watcr supply shall be protccted against hackflow by a reduced pressure principle backflow prcventer. Wherc chemical additives or antifreeze are ztddcd to only a por-tion of an automatic firc sprinkler or standpipe system. the rcduced pressure principle backflow preventer shall be penilitted to hc located so as to isolate that portion of the system. Where systems are not under continuous pressure, the potable water supply shall bc protected against backflow by an air gap or a pipc applied atmospheric vacuum breaker conforming to ASSE 1001 or CSA B64.1 . l . 608.16.5 Connectioi~sto lawn irrigation systems. Thc potablc water supply tolawn irrigation systen~sshall be protcctcd against backflow by all atmospllcric-type vacuum breaker, a pressure-type vacuurn breaker or a 1.cducet1prcssure principle baclcflow prcventer. A valvc shall not be installeddownstrcain fi-om an atmospheric vacuum hreakcr. Where che~nicalsare introduced intolhc system: lhe potable water supply shall be protected against b;rckflow by a reduced pressure principle backflow prevcnter. 608.16.6 Connections subject to backpressurc. Where a potablc water cor~ncctionis madc to a nonpot:tble I~ne,lixture, tank. vat. pump or other equlplrlcnt subjcct to
WATER SUPPLY AND DlSTRlBUTlON
back-pressure, thc potable writer connection shall bc protccted by a reduccd prcssure principle backflow prcvcnter.
608.16.7 Chemical dispensers. Where che~nicaldispensers connect lo the potable water distribution system, the aratcrsupply systcm sllall bc protected against backflow in accortlancc with Section 508.13. I, 608.13.2. 608.13.5, 608.13.6, 608.13.8 or608.13.9. 608.16.8 Portable cleaning equipincnt. Where the poitahle cletu~ingcquipn~entconnccts to the water distribution systcm, thc water supply systcni shall be protected against backflow in accordance with Section 608.13.1, 608.13.3, 608.13.3. 608.l7.7 or608.13.5. 608.16.9 Dental pump equipment. Where dcntal pulnplng equipnlent connects to the watcr distribution system, the watcr supply system shall bc protected aga~nstbacl
i
~-
TABLE 608.17.1 DISTANCE FROM CONTAMINATION TO PRIVATE WATER. SUPPLIES AND PUMP SUCTION LINES .-. . ~ . . ~-- ~ - ..~ ---~
-
~~
~
-
-~
~
~~
-
~~
i
Barnyard .
-
j
~-
~
~
~~
.
~
~~
-~~
~-
lSecpagcpils (Septic tank / .. .
-
4-,..
~
-
-- .
.
. - ~ ~
---
.
--
-~
-
..
iselver . . . Isubsul-f~ce disl~osal fields .~
-
r
~
-1
L?!L -. 25
-.
~. ~
I
1-
SO~.-.
-.
25
,.
-
~
~
..
-
~
-
.
608.17.7 Cover. Every potable water well shall be ccluippcd with an overlapping water-tight cover at the lop of the well casing or pipe sleeve such that contaminated watcr ol-other substances are prcvcnted from entering the well through the annular opening at the top of the well casing, wall or pipe sleeve. Covers shall extend down\vard at least 7, inchcs (5 1 mm) over the outsidc of the well casing or wall. A dug wcll cover shall be provided with a pipe sleevc permitting the withdrawal of the pump suction pipc, cylinder or jet body without disturbing the cover. Where pump sections or discharge pipcs enter or leavc a well through the side of the casing, the circle of contact shall be watcr tight. 608.17.8 Drainage. All potable watcr wells and springs shall hc constructed such that surface drainage will bc diverted away from the wcll or spring.
1
SECTlON 609 HEALTH CARE PLUMBING 609.1 Scope. This section shall govern those aspects of health care plunlbing systems that clifier from plumbing systems in other structures. Health care plumbing systems shall collform to the requirements of this section in addition to Ihc othcr rcc]uirements of this codc. The provisions of this scclioli shall apply to thc spccial devices and equipment installed and rnaintained in the following occupancies: nursing horncs, homes for the aged, orphanages, infirmarics, first aid stations, psychiatric
~
--
~-
10 50
-
~---
1
~!
1
~
For SI:
608.17.6 Dug or horcd well casings. Dug or bored well casings shall be of water-tight concrete, tile, or gal\,anized or corrugated metal pipe to a niinirnum distance of I0 feet (3048 mm) below the ground surface. Where the water table is more than 10 feet (3048 mm) below the ground surface, the watcr-tight casing shall extend bclow the tablc surface. Well casings for dug wells or bored wells constructed with sections of concrete, tile, or g a l ~ a n i ~ cord corrugated nictal pipe shall be surrounded by 6 inchcs (152 mru) of grout poured into thc hole betwecn the outsidc of the casing and the ground to a minimum dcpth of 10 feet (3048 mm).
I
~-..?
~
! 1
I
1~. Subsurfacc piis .
608.17.5 Drilled or driven well casings. Drilled or driven well casings shall be of steel or othcr approved material. Where drilled wells extcnd into a rock forrnafion, the well casing shall extcnd to and set firmly in the formation. Thc annular space between the earth and the outside of the casing shall be filled with cement grout to a minimuni distance of 10 fcet (3048 mm) below the ground surface. In an instance of casing to rock installation, the grout shall cxtcnd to the rock surface.
~
100-
.
,
--
-
_..
-- -
--
)
_
-
1
608.17.4 Water-tight casings. Each we1 l shall be providcd with a water-tight casing to a minimum distance of 10 feet (3048 mni) below the ground surface. All casings shall cxtend at least 6 inches (153, nun) al3ove the wcll plalform. The casing shall he large enough to permit installation of a separate. drop pipc. Casings shall bc scaled at thc bottom in an impermeable stratum or extend several fect into thc water-bearing stratum.
~-
-.
~~~~
.
II
~
/ Pu~nphouscfloor drain of cast iron draining I1~~ to ground surface -
-~
DISTANCE (feet)
-- - -
-
[Far111silo 1 Paslur-c .
-
~
SOURCE OF CONTAMINATION
605.17.3 Depth. Private potable wcll supplics shall not bc developed from a watcr tablc less than 10 Feet (3048 m ~ n ) below tlie ground surhcc.
~
I
~L
~
50
~
I
_. --.
I foot = 304.8 mm.
608.17.2 Elevation. Well sites shall be positively drained and shall bc at higlicr elevations than potential sources of contamination.
2006 INTERNATIONAL PLUMBING CODE@
WATER SUPPLY AND DISTRIBUTION
.'L I.~ I I I ~clinics,