Previous Page Chapter 10 - Virtual Plant
395
Application Detail Virtual versions of scalable distributed control systems (DCS) are now available that support the development of control-system configuration, logic checkout, and operator training using a single PC or multi-node PC environment. These packages are designed to be used on a laptop or office PC. Using this capability, it is possible to configure all of the features that the control system supports (for example, continuous control, batch control, advanced control, and their associated workstation displays, alarms, and historian data collection) without purchasing system hardware. Using this capability, the execution is simulated for the operator interface and selected control modules defined for the plant control system. This capability is used for control logic checkout. And, using the control and I/O block and Fieldbus block simulation capability, field measurement values and status are manually supplied to the simulation—or provided by blocks used to simulate the process. The full range of OPC features in the control system are available and may be used for the development and testing of OPC interfaces. Plus, before your plant is even constructed, the OPC-compliant process simulation package is used for process and control design checkout Thus, most of the features of a complete control system are made available on the PC. Using the virtual plant, it is possible to accomplish the following: • Engineer systems anywhere - Engineering work is done without the constraints of working at a dedicated configuration station. The virtual plant is installed on a home or office computer or on a laptop. The work done on this computer is easily exported and quickly imported to the actual control system. • Verify control logic and display implementation - Software modules configured for your plant control are executed in your computer for control and display checkout. Using the simulate capability of the controller blocks and Fieldbus I/O blocks, the measurement value and status are examined during the checkout of control logic, operator displays, alarms, and trending. • Test OPC interfaces- The simulation environment fully supports OPC. Executing modules in the computer allows an OPC interface to be checked out completely. This feature is used to develop applications that can execute in the control system. • Support control system training - Dynamic process simulations are created to support operator and engineering training one controller at a time. Function blocks can be used to create a process model or a process simulation package can be incorporated in the
396
Advanced Control Unleashed
virtual plant to create a training tool. The control system provides an integrated development environment in which the continuous, sequential, and batch control for a plant are engineered. Using drag-and-drop techniques, the configuration of control is relatively easy, as shown in Figure 10-5.
Figure 10-5. Integrated Development Environment
The Fieldbus Foundation architecture has been adopted by the control system. The control functionality that is assigned to a controller or Fieldbus device in the control system is executed in the PC and the results displayed in the configured operator interface, without any change in the control or operator interface configuration. Using the simulate capability of the control system and Fieldbus input-output function blocks, field measurement values are available for control-system and operator-interface checkout as shown in Figure 10-6. Using the SIMULATE parameter of the controller and Fieldbus I / O blocks, it is possible to manually inject field measurement values and status to check out control logic, alarming, displays, etc. By changing the status or value associated with a measurement, the action taken by control logic execution of the control system in the virtual plant environment may be examined. Also, this capability is used to test whether block parameter values and status are displayed correctly in the screens designed for the operator interface. By changing the measurement value through the SIMULATE parameter, it is possible to force an alarm condition to verify assigned alarm priority and the manner in which alarms become visible to the operator; e.g., alarm banner in the operator interface.
Chapter 10 - Virtual Plant
397
Figure 10-6. Standard Support for I/O Simulation
Dynamic process simulations are created to support process design and operator and engineering training. Using the standard function block available in the control system, it is easy to create a simple dynamic model based on the process design. The standard calculation and dynamic blocks provided in the Analog Control and Math palette in control-system configuration tools may be used to construct a simple dynamic process model for testing control strategies and operator training. As shown in Figure 10-7, the process is simulated using function blocks that are wired to simulate inputs and outputs of I / O function blocks. Application packages that support an OPC interface are compatible with the virtual scalable DCS. For example, as shown in Figure 10-8, this OPC capability allows the high-fidelity dynamic process simulation software to be used with the control-system configuration for plant and control design as well as for control checkout and operator training. Many process-simulation packages support checkout and operator training by the use of enhanced tieback simulations. These process-simulation applications utilize the simulate capability of the control system and Fieldbus I / O blocks, as illustrated in Figure 10-8. An application and interface are provided in the simulation environment to allow the simulated control-system execution to be coordinated with the process-simulation execution. Using this application, it is possible to examine the state of the control simulation and whether I / O and control blocks are correctly set for simulation. Also, from this interface, it is possible to change the simulated control execution to be faster or slower than
398
Advanced Control Unleashed
Figure 10-7. Process Models Constructed from Function Blocks
Figure 10-8. High-Fidelity Process Simulation
real time and to pause the execution. Common requirements such as the initialization of the simulation, block mode, and block dynamics are addressed. An OPC interface is provided to allow process-simulation packages to also invoke the same requests that are made through this user interface to the control simulation.
Chapter 10 - Virtual Plant
399
Rules of Thumb Rule 10.1.— The actual control system configuration and displays must be imported and exportedfromthe virtual plant. The use of a reconstructed or emulated control system and operator interface is fundamentally unsound. The actual configuration and displays and all the features of the actual system must be used. Rule 10.2.— The use of actual hardware instead of a virtual plant is costly, delays and restricts the access, and decreases the utility of a simulation for training and testing. If an engineer needs something he can touch, give him last year's obsolete controller. Rule 10.3.— The process simulation must use an OPC interface to the controlsystem configuration and software tools. This will facilitate the connection of the system to other advanced diagnostic, data-analysis, and control tools. Rule 10.4.— The definition of the informationflowbetween the control system and the process simulation should be configurable and easily done without requiring programming knowledge. The connection should be as simple as browsing and dragging and dropping tags in an interface table. Rule 10.5.— The process simulation and control system should support execution fast or slower than real time. Also, the ability should be provided to freeze both. Rule 10.6.— The virtual plant should support single commands to initiate setup of the process simulation and control system to a known state. There should be an ability to easily capture and restore the state of the process and control system. Rule 10.7.— It should be possible to run the virtual plant in a single PC or be distributed between multiple PC's. No change in control-system configuration should be required to relocate where the process simulation and control system is executed. Rule 10.8.— The process-simulation software must be graphical and have highlevel and a wide variety of physical property packages, state equations, and configurable functional blocks and unit operations. Custom simulations that require the setup and numerical integration of differential equations are too complex to construct and maintain and do not have all the physical properties and their dynamic interaction with process conditions. If you spent the millions of dollars to create a custom simulation of an entire plant, only the programmers who created the custom model could debug and modify it.
400
Advanced Control Unleashed
Rule 10.9.— To verify that the configuration matches the control definition and to teach operators how to use the interface, an enhanced tieback simulation is suf-
ficient. Configuration engineers prefer to use a tieback simulation to test their work so they don't have to get involved in the process or learn how to start and stop a process simulation. Also, these tieback models have an input and output file card channel (FCC) screen that lets the configuration engineer conveniently set and monitor input and output signals. Rule 10.10.— To test whether the control definition is correct, to learn how the process and control system behave for upsets, startups, and failures, and to prototype advanced control solutions, a high-fidelity dynamic process simulation is
needed. While the configuration engineer is too busy and will move on to the next project too quickly to take advantage of a high-fidelity virtual plant, it is a valuable ongoing resource for operators and engineers at the plant and can lead to real-time optimization. While this method does not check the I/O file card channels, these assignments are verified anyway as a part of the normal course of the checkout of the field wiring.
Guided Tour This tour illustrates the potential ease of use and convenience of an integrated interface that is possible for control simulation embedded in an industrial control system. The following areas are addressed: • Control Simulation Setup • Coordination of Process and Control Simulation • Viewing Simulation State Modern control systems allow modules for control, monitoring and calculate applications to be engineered independent of where they are executed. Thus, a module is assigned to execute on controller hardware or a PC platform with no change in its configuration. Such capability makes it possible to take a control system configuration and quickly use this to construct engineering and operator training system based on PC platforms i.e. no controller hardware. Modules that have been engineered for the plant control and normally execute in hardware controllers are re-assigned to run in the PCs that have the control system software installed, as shown below. When these modules are loading in the module folder on the PC as shown in Figure 10-9, the assigned modules automatically begin to execute at their configured rate of execution. Late binding of module information in the communications between the PC stations allows the operator and engineering interface to access the inputs, alarms, and calculate values associated with these modules without any change in system configuration.
Chapter 10 - Virtual Plant
401
Figure 10-9. Module Assignment for Execution
Within the PC nodes that make up the virtual plant environment, an application may be added to provide process simulation. The process-simulation application may use OPC to read the actuator positions from the I / O blocks within the modules. Based on these values, the process-simulation package may calculate the process inputs and writing these values to the simulate parameter of the input blocks. Thus, within the accuracy of the process simulation, the measurement and control response will duplicate what is seen in the actual installation. To provide an effective engineering or training system, it is necessary to coordinate the process-simulation package execution with the controlmodule execution. A simulate interface is provided in the control system for this coordination as illustrated in Figure 10-10. Through the selection provided in the Setup, it is possible to: • Enable or Disable the Simulate function of I / O blocks. • Change Control and Output blocks to their setup mode so the process-simulation application may change these outputs to a known starting point in the simulation. • Initialize the dynamic blocks in all modules assigned to the node so that they are at steady-state solution. • Allow the operating state of all modules to be saved or restored at any point in time. This allows the simulation to be restarted at different conditions.
402
Advanced Control Unleashed
Figure 10-10. Interface for Simulation Coordination
• Allow all modules assigned to the node to be run faster or slower than real time. This capability allows the control simulation to match the speed of the process simulation. The simulate state of individual modules is examined by selecting the Summary tab as shown in Figure 10-11.
Figure 10-11. Examining Module Simulation State
Chapter 10 - Virtual Plant
403
The status of module I/O blocks to support simulation is examined by selecting the Summary tab. From this view, it is possible to view all modules assigned to a selected area. A frown face is used to identify conditions that would prevent a process simulation from interacting with the control. These can be of the following types: • Simulate - One or more I/O blocks do not have simulation enabled. • Status - The input status of an I/O block is Uncertain or Bad. This might indicate that the process simulation is is calculating an incorrect value or no value. • Mode - The I/O block is not in its normal mode of operation. When a module is selected from this view, details concern the I/O and control blocks in the module are automatically displayed. Also, the user may enable or disable simulation of an individual block from this interface. Using this capability, the user can simulate disturbance in the process during control-system checkout and operator training
Theory The software and the associated configuration of some modern control systems are designed to be independent of the hardware, and thus may execute in multiple operating environments without change. When this approach is taken, it is possible to distribute control-system functionality in a variety of ways without needing to reengineer the software or reconfigure the associated applications. All features of the control system are combined on a single platform or distributed between multiple PCs to support configuration and dynamic checkout of the controls and interface associated with a process control system. This approach makes it easier to update the hardware platform since migration issues are minimized. This capability is used to allow portions of the controller software to be executed in the workstation. Internally, this software capability was utilized by control-system manufacturers to facilitate checkout of new controller code. By installing the controller software on a PC, the superior debugging tools provided on the PC can be used in troubleshooting the software. Also, the capability of installing the controller software on a PC has been used to create internal demonstration systems where it was not practical to have controller hardware. Also, some control-system manufacturers have realized that this capability to run all the control software on a single PC would be valuable to customers in configuration development, simulation and operator training. Thus, as illustrated in Figure 10-12, some manufactures offer this capability as a standard feature that is purchased independent of the control system hardware. This design approach allows the controller software, Fieldbus
404
Advanced Control Unleashed
software, and workstation software to run on a single PC or in a multinode environment as shown in Figure 10-12.
Figure 10-12. A Complete Training and Testing Center
When a control system utilizes the Fieldbus Foundation function block architecture, the function blocks used to define control, calculation and measurements may be distributed in a variety of ways. For example, the function blocks assigned to multiple controllers may be reassigned to a single PC or to multiple PCs without modification or the need to reconfigure block parameters. Also, as defined in the Fieldbus standard, a SIMULATE parameter is available in each I / O function block. A person may supply a value and status to the I / O function block for the field measurement when simulation is enabled, as illustrated in Figure 10-13. This capability is used to check out control logic and operator displays. Also, using simple tieback from output blocks to the simulation input values of input blocks, it is possible to provide simple process simulation for operator training. An OPC interface is provided in modern control systems to allow applications to access function-block information. Utilizing this capability, an application may enable simulation in I / O blocks and write the simulated value and status to be used in place of the field measurement. This capability, combined with the ability to redistribute control functionality without reconfiguration, provides a strong foundation for the integration of high-fidelity simulation with the control system configuration in a single or multi-PC environment.
Chapter 10 - Virtual Plant
405
Figure 10-13. Input/Output Function Blocks Support the Simulate Parameter
The major benefits realized from structuring the interface to the control system around OPC and Fieldbus function blocks are: • Standard Component Object Model (COM) /OLE Automation models, tools and languages (VB, C++, Delphi) are used to access the server. • OPC interfaces provide a common protocol that reduces driver effort by an estimated 50% to 80%. • OPC is Distributed COM (DCOM) based, so distributed capability is built-in. The OPC server of this control system abstracts the deployment of the controller and Fieldbus-based control items from the OPC client. For example, consider a system that employs a large number of Fieldbus devices. In order to simulate such a system easily, the measurement and control function blocks need to be reassigned to run on a workstation. If the OPC server is set u p correctly, the OPC client does not need to know that control execution has been reassigned. The same client configuration connects to the actual scalable DCS or the control assigned to a PC with no change in configuration. The flexibility to extend a dynamic process-simulation tool is important where proprietary process elements exist, including Unit Operations, Reaction Kinetics, Property Packages, and Pressure-Drop Correlations. With the OLE Automation Extensibility Interfaces supported by the simulation tool, extensions are easily written using standard OLE automation
406
Advanced Control Unleashed
tools and plugged seamlessly into the simulation engine process. Customers do not have to rely on the simulator manufacturer to provide the required functionality. The OLE automation interface, OPC browser interfaces, and tools based on these technologies help customers flexibly configure large, integrated simulation systems. Maps must be created to associate elements in the control system with elements in the process-simulation system. This mapping is generated during the configuration phase of a project. Both visual drag-and-drop and more automated programmatic generation features are desirable for flexible map configuration. While computing power continues to increase at phenomenal rates, the computational problem of performing rigorous dynamic simulations for a large plant will remain more than one machine can handle for some time. The process models and control-system sections in a final application are generally distributed, to some degree. Adopting hardware and software interface standards such as OPC helps reduce the cost and development times for operator training projects. Using OPC, it is possible to distribute the virtual plants between multiple PC nodes as illustrated in Figure 10-14.
Figure 10-14. Distribution of Virtual Plant Among PCs
To allow control-system execution to be coordinated with the process simulation, command parameters are added to the PC nodes that execute the control-system modules. Typically, a user interface is provided that allows a process designer or operator training instructor to use these parameters
Chapter 10 - Virtual Plant
407
in setting up the simulation. Some common types of request that are supported by the virtual plant are: • Enable or disable I/O simulation for all blocks assigned to a PC node. • All time-dependent blocks (dynamic blocks) contained in modules assigned to the node are initialized to their steady-state condition (based on input value). • Set target mode of output blocks to Manual or Auto so it is possible to write initial values. • Set target mode of output blocks to Normal mode so normal operation is achieved. In addition, node parameters will typically be provided that allow the control system to execute faster or slower than real time. This capability reduces the time needed for control checkout and operator training. Support is also normally provided for stopping the execution of all blocks assigned to the PC with a single request. The instructor interface to the virtual plant may allow all modules assigned to a node to be examined. Modules that are not correctly set up for simulation are automatically identified. The blockmodes and simulate parameters are independently changed. The module summary indicates if modules are correctly set up for simulation. The module detail view indicates abnormal conditions for simulation. Block Mode, Simulate, and OUT values are changed and Simulation is enabled or disabled with a single request. To allow the control simulation to be coordinated with process simulation, these node parameters are accessed by the process-simulation application, as illustrated in Figure 10-15. A PC node parameter may also be used to specify an execution factor. The modules in the node run faster or slower than their configured execution rate based on the factor. However, time-dependent calculations in the block still use the configured execution rate in their calculation. Thus, true faster or slower than real time response is exactly provided. Typically, the virtual plant may support speed factors from 1/30 to 30 times real time. How fast the virtual plant can run depends upon the distribution of the models among multiple PCs, the speed of the PC processors, and the complexity of the process models.
408
Advanced Control Unleashed
Figure 10-15. Coordination of Simulation Using PC Node Parameters
References 1.
Mansy, Michael, M., McMillan, Gregory, K., and Sowell, Mark, S., "Step Into the Virtual Plant," Chemical Engineering Progress, February, 2002, pp 56-61.
2.
Butler, Douglas, L., Cameron, Robert, A., Eckelman, Larry, D., and McMillan, Gregory K., "Virtual Plants for Hands On Advanced Control," ISA, Houston, September 10-13, 2001, Paper 1053.
3.
Lo, P., et. al., "Distillation Tower Pump Failure," Control, October, 2000, pp. 71-82.
4.
Stanley, Peter, "Dynamic Simulation for Insight," Chemical Processing, December, 1999, pp. 47-50.
5.
Chin, K., "Learning in a Virtual World," Chemical Engineering, December, 2000, pp. 107-110.